Installation Guide

© 2005 Schneider Electric USA All Rights Reserved
40266-122-02 CTL Load Centers
05/2005 Instruction Bulletin
3
INSTALLATION–QOT CIRCUIT BREAKERS
1. Turn off all power supplying this equipment before working on or
inside equipment.
2. To install tandem type QOT circuit breakers, hold circuit breaker
at 30–45° angle.
3. Insert nose of mounting cam into pan mounting rail slot as far as
possible (until bottom of circuit breaker case hits rail bead).
4. Rotate circuit breaker until plug-on jaws fully engage on bus bar
connectors.
NOTE: Bottom of circuit breaker case should remain against rail bead.
CAUTION
HAZARD OF EQUIPMENT DAMAGE
The QOT mounting cam is thick, hardened steel. Excessive force upon it to
improperly install a tandem unit where no pan mounting slot is provided will destroy
the circuit breaker case.
Do not modify the mounting rail or circuit breakers.
Failure to follow this instruction will result in equipment damage.
TYPE QO
TYPE QO
TYPE QO-T
TYPE QO-T
Rail Bead
Mounting Cam
2.25
[57]
3.60
[91]
40005-472-01
40266-122-02.fm Page 3 Tuesday, May 24, 2005 2:19 PM