Technical Data Bulletin

7-88
© 2020 Schneider Electric
All Rights Reserved
Circuit Breaker Enclosures
Enclosure Accessories and Dimensions
www.se.com/us
Class 610
Enclosure Accessories
Table 7.177: Neutral Kit Terminal Data
Neutral Kit
Catalog Number
Terminal Lug Data -Total Available (Line
plus Load) AWG/kcmil AL/CU
All Copper Neutral Terminal Lug Data -Total
Available (Line plus Load) AWG/kcmil
100SNA
(2) 14–1/0 Cu or
(2) 12–1/0 Al plus (1) 14–4 Cu
SN100FA
(4) 14–1/0 Cu or
(4) 12–1/0 Al
SN225KA
(2) 4–300 Al/Cu plus (2) 14–1/0 Al/Cu
225SNA
(4) 6–350 Al/Cu
400SN
(2) 1–600 or
(4) 1–250 Al/Cu, plus (2) 4–300 Al/Cu
SN400LA
(2) 1–600 or
(4) 1–250 Al/Cu, plus (2) 4–300 Al/Cu
SN1000MA
(6) 3/0–500 Al/Cu, plus (1) 1–4/0 Al/Cu
SNC400LX
(2) 2–-600 Cu, plus (2) 6–250 Cu
SNC800LX
(4) 2–600 Cu, plus (1) 2–4/0 Cu
AL800SN
(6) 3/0–500 Al/Cu, plus (2) 6–250 Al/Cu
SN1200
(8) 3/0–750 Al/Cu, plus (2) 6–350 Al/Cu
S33576MK
(8) 3/0–500 Al/Cu, plus (2) 4–300 Al/Cu
Table 7.178: Service Ground Kit Terminal Data
Service Ground Kit Catalog
Number
Terminal Data
AWG/kcmil
Lugs Per Kit
PKOGTA2 10–2/0 Cu or 6–2/0 Al 2
PKOGTH150 14–2 Al/Cu 2
PKOGTJ250 6–300 Al/Cu 2
PKOGTA4 6–250 Al/Cu 4
Terminal Shields for Service Entrance Applications
Can be applied as line side barriers in service entrance applications
Will fit on top or bottom of the circuit breaker
J-Frame Short
Lug Shield
Table 7.179: Terminal Shields
Frame 2P 3P
PowerPact Q QSB2 QSB3
PowerPact H (3 AWG Max. Wire Size)
S37446
PowerPact H (3/0 Max. Wire Size)
S37447
PowerPact J S37448
PowerPact M MGJTC
PowerPact P PA12TC
LA/LH LAHTC
See Supplemental Digest Section 3 for special options for enclosures:
Stainless steel fronts
Pilot lights, push buttons
Lock-on SPL0
Key interlock systems
Legend plates
7
MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS