Technical Data Bulletin
Table Of Contents
- Section 7 Miniature and Molded Case Circuit Breakers
- Selection Information
- QO™ and QOU Miniature Circuit Breakers
- Homeline™ Miniature Circuit Breakers
- Multi 9™ Miniature Circuit Breakers
- PowerPact™ Molded Case Circuit Breakers
- Mission Critical Circuit Breakers
- 500 Vdc Circuit Breakers
- Automatic Switches
- Motor Circuit Protectors
- PowerPact™ Circuit Breaker Accessories
- MicroLogic™ Electronic Trip Units
- MasterPact™ Power Circuit Breakers
- Enerlin’X Digital Solutions
- Ground-Fault Protection
- Dimensions and Shipping Weights
- Circuit Breaker Enclosures
7-86
© 2020 Schneider Electric
All Rights Reserved
12/2/2020
Circuit Breaker Enclosures
Enclosures
www.se.com/us
Class 610
PowerPact L-Frame Circuit Breaker and Molded Case Switch Enclosures
All enclosures accept 80% rated circuit breakers. The enclosures will also accept 100%
rated circuit breakers to 400 amps. The enclosures have a blank top end wall and require
field-cut openings. For details and hub catalog numbers see page 3–10.
Table 7.171: PowerPact L-Frame Circuit Breaker Enclosures
Circuit Breaker Cat. No.
NEMA 12/3R Enclosures
Without Knockouts
Neutral Assembly Kit
Copper Only Neutral
Assembly Kit
Service Ground KitCat. No. Prefix
Rating
Poles
LDL, LGL, LJL, LLL, LRL
250–400 A
3
L600AWK [14][15][16]
SN400LA SNC400LX
PKOGTA4
400–600 A SN1000MA SNC800LX
LGL, LLL, LRL
250–400 A
3
L600AWKMC [17][15]
SN400LA SNC400LX
PKOGTA4
400–600 A SN1000MA SNC800LX
PowerPact Q-Frame Circuit Breaker Enclosures
The enclosures for the PowerPact Q Frame Circuit Breaker are UL listed. The short
circuit ratings of these enclosed circuit breakers are equal to the interrupter ratings, at
the supply voltage marked on the circuit breaker installed, unless otherwise noted.
Table 7.172: PowerPact Q-Frame Circuit Breaker Enclosures
Circuit Breaker Enclosure Cat. No.
Neutral Assembly Kit
Cat. No.
Service Ground Kit
Cat. No.
Cat. No. Prefix
Rating
Poles
NEMA 1 Flush
NEMA 1Surface NEMA 3R
QBL, QDL, QGL, QJL [18]
70–225 A
2 —
Q22200NS [19] Q22200NRB [19]
— PKOGTA2
2, 3 Q23225NF Q23225NS Q23225NRB
PowerPact M- and P-Frame Circuit Breaker Enclosures
All enclosures will accept 80% rated circuit breakers. The P1200 enclosures will accept
100% rated circuit breakers to 800 A. If a CT neutral is required, the enclosure will no
longer accept a 200% neutral. The M800R and the P1200R enclosures have a blank top
end wall and require field-cut openings. For details and hub catalog numbers see page
3-10.
Table 7.173: PowerPact M- and P-Frame Circuit Breaker Enclosures
Circuit Breaker Cat. No.
Cat. No. Prefix
Rating
Poles Enclosure
Neutral
Assembly Kit
200% Neutral
Kit
CT Neutral Kit
[20][21]
Service Ground
Kit
NEMA 1 Flush NEMA 1 Surface NEMA 3R
MGL, MJL. PGL, PJL,
PKL, PLL
300–800 A
2, 3
— M800S M800R AL800SN
SN800SNI
and 2 each
SN1200
S33576MK PKOGTA4
PGL, PJL, PKL, PLL
250–1200 A
2, 3
— P1200S P1200R SN1200 — S33576MK PKOGTA4
NEMA 4, 4X, 5 [22]
Type 304 Stainless
Steel [15]
NEMA 4, 4X, 5 [22]
Type 316 Stainless
Steel [15]
NEMA 12/3R
Without Knockouts
[15]
MGL, MJL. PGL, PJL,
PKL, PLL
300–800 A
2, 3
M800DS M800SS M800AWK AL800SN — S33576MK PKOGTA4
PGL, PJL, PKL, PLL
250–1200 A
2, 3
— — P1200AWK SN1200 — S33576MK PKOGTA4
PowerPact L-Frame 500 Vdc Circuit Breaker Enclosures
The PowerPact L-frame circuit breaker enclosure's maximum short circuit rating is 20
kAIR at 250 Vdc and 50 kAIR at 500 Vdc.
Listed for use ONLY on UPS systems.
Table 7.174: DC CIrcuit Breaker Enclosures for LG and LL DC-Rated Circuit
Breakers
Circuit Breaker [23]
Cat. No.
Cat. No. Prefix
Ampere
Rating
Poles
NEMA 1 Surface
Enclosure
Replacement
Ground Lugs
Service Ground
Kit
LGL, LLL
300–600 A 3 L1200S
8010440301 Standard
700–1200 A 4 L1200S
7
MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
[14] Will accept PowerPact L-frame circuit breakers and Motor Protectors with suffixes M38X
[15] For NEMA 3R applications, remove drain screw from bottom endwall.
[16] Add suffix VW for visibility to the standard, ammeter or energy trip unit of the PowerPact circuit breaker.
[17] Will accept PowerPact L-frame Molded Case Switches.
[18] When the QJL circuit breaker is installed in the enclosure, the enclosure is limited to Short Circuit Current ratings of 65 kAIR at 240 V and 100 kAIR at 208 V.
[19] Limited to 200 A.
[20] Order current transformer kit S33576 seperately.
[21] Current transformers applicable only on PowerPact P circuit breakers. Current limitations are 400–800 A and 400–1200 A respectively for the M800 and P1200 family of enclosures.
[22] Complete rating is NEMA 3, 3R, 4, 4X, 5, and 12.
[23] Use 500 Vdc or 250 Vdc rated circuit breakers only.