Technical Data Bulletin

© 2020 Schneider Electric
All Rights Reserved
12/2/2020
7-85
www.se.com/us
Enclosures
Circuit Breaker Enclosures
Class 610
PowerPact Circuit Breaker Enclosures
The enclosures for the family of PowerPact circuit breakers B- through Q-frame are
cULus listed unless otherwise noted.
The enclosures are suitable for service entrance equipment when neutral assembly is
installed.
The short circuit current rating of the enclosed circuit breakers is equal to the rating of
the circuit breaker installed unless otherwise noted.
All enclosures will accept 100% rated circuit breakers unless otherwise noted.
PowerPact B-Frame Circuit Breaker Enclosures
The enclosures' maximum short circuit ratings are 65 kA at 600Y, 65 kA at 480 Vac,
100 kA at 240 Vac and 50 kA at 250 Vdc unless otherwise noted.
Enclosures accept 100% rated circuit breakers
[8]
.
Table 7.169: PowerPact B-Frame Circuit Breaker Enclosures
Circuit Breaker
Enclosure Catalog Number
Accessory Catalog Number
Cat. No. Prefix
Rating
Poles
Neutral Assembly
Kit
Service Ground Kit
NEMA 1 Flush NEMA 1 Surface NEMA 3R
BDL, BGL, BJL
15–100 A
2, 3
B125F B125S B125RB
SN100FA
PKOGTA2BDL, BGL, BJL
110–125 A
2, 3 SN225KA
BKL 15–30 A 2 SN100FA
NEMA 4, 4X, 5
Type 304 Stainless
Steel
NEMA 12
With Knockouts
NEMA 12
Without Knockouts
BDL, BGL, BJL
15–100 A
2, 3
B125DS B125A
B125AWK[1]
SN100FA
PKOGTA2BDL, BGL, BJL
110–125 A
2, 3 SN225KA
BKL 15–30 A 2 SN100FA
PowerPact H- and J-Frame Circuit Breaker Enclosures
The enclosures' maximum short circuit ratings are 25 kAIR at 600 Vac, 65 kAIR at 480
Vac, 125 kAIR at 240 Vac and 20 kA at 250 Vdc unless otherwise noted. Enclosures
accept 100% rated circuit breakers
[2]. The enclosures are not compatible with earth-
leakage or ground-fault modules.
H- and J-frame circuit breakers with MicroLogic trip units can be used with these
enclosures, but have the following limitations:
No communication accessories can be mounted in the enclosure (no IFM or Front
Display Module, IFE, etc).
The trip unit will not be accessible or visible without the removal of the cover (except
J250F and J250S).
For LSIG, there is no room for the NCT to mount in the enclosure.
Table 7.170: PowerPact H- and J-Frame Circuit Breaker Enclosures
Circuit Breaker
Enclosure Cat. No.
Neutral Assembly Kit
Cat. No.
Service Ground Kit
Cat. No.
Cat. No. Prefix
Rating
Poles
NEMA 1 Flush NEMA 1 Surface NEMA 3R
HDL 15–100 A 3
HD100S [3][4][5]
SN100FA PKOGTA2
HDL, JDL
125–225 A
3
JD250S [6][4][5]
SN225KA
PKOGTA2
125–250 SN400LA
HDL, HGL
15–100 A 2
H150F H150S
H150R [7]
SN100FA
PKOGTH150
125–150 A 2 SN400LA
HJL, HLL
15–100 A 2
J250F
J250S [8] J250R [7][9]
SN100FA
PKOGTH150
HDL, HGL, HJL, HLL
15–100 A 3
125–150 A 3
SN400LA[10]
JDL, JGL, JJL, JLL
150–250 A
2, 3 PKOGTJ250
NEMA 4, 4X, 5 [11] Type
304 Stainless Steel [12]
NEMA 4, 4x, 5 [11]
Type 316 Stainless
Steel [12]
NEMA 12/3R Without
Knockouts [12]
HDL, HGL, HJL, HLL
15–100 A
2, 3
J250DS [13] J250SS [13] J250AWK [13]
SN100FA
PKOGTH150
125–150 A
2, 3
SN400LA[10]
JDL, JGL, JJL, JLL
150–250 A
2, 3 PKOGTJ250
7
MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
[1] For NEMA 3R applications, remove drain scerw from bottom end well.
[2] Use only 90°C (minimum) rated wire sized per ampacity of 75°C rated conductors for 100% rated circuit breakers.
[3] Rated for 240 Vac maximum. Short circuit current rating is 25 kAIR at 240 Vac.
[4] Accepts standard 80% rated circuit breakers only. Not rated for 100% rated circuit breakers.
[5] Use copper conductors only.
[6] Rated 480 Vac maximum. Short circuit current rating is 18 kAIR at 480 V.
[7] For conduit entry through the top end wall use one of the following Square D conduit hubs: A200L for 2.00 in., A250L for 2.50 in., A300L for 3.00 in., A350L for 3.50 in. or A400L for 4.00 in.
[8] Add suffix BE if no knockouts are required on the end walls.
[9] For access to the circuit breaker’s standard, ammeter or energy trip unit panel/LCD, add suffix T.
[10] For 200% neutral use copper wire only.
[11] Complete rating is NEMA 3, 3R, 4, 4X, 5, and 12.
[12] For NEMA 3R applications, remove drain screw from bottom endwall.
[13] Add suffix VW for visibility to the standard, ammeter or energy trip unit of the PowerPact circuit breaker.