MicroLogic™ Electronic Trip Units PowerPact P- and R-Frame Trip Units
www.se.com/us
Class 612 / Refer to Catalog 0612CT0101
PowerPact P- and R-Frame MicroLogic Trip Units
PowerPact P- and R-Frame MicroLogic Trip Units
Standard
Trip Unit
Ammeter
Trip Unit
Power
Trip Unit
Harmonic
Trip Unit
Adjustable
Rating Plug
MicroLogic (Standard) 3.0 and 5.0 Trip Units
PowerPact™ P- and R-frame molded case circuit breakers may be specified with any of
the following MicroLogic Electronic Trip Units.
True RMS sensing
LI, LSI trip configurations
Field-interchangeable long-time rating plugs
LED long-time pickup indication
Test kits available
Thermal imaging
MicroLogic (Ammeter) 3.0A, 5.0A and 6.0A Trip Units
Includes all features listed for MicroLogic standard trip unit, as well as:
LSIG trip configurations
Digital ammeter—phase and neutral (4-pole only)
Phase loading bar graph
LED trip indication
Zone-selective interlocking (ZSI) (short-time & ground-fault)
Optional Modbus™ communications—PowerLogic™ compatible
MicroLogic (Power) 5.0P and 6.0P Trip Units
Power measurement and advanced protection features includes all features listed for
MicroLogic ammeter trip unit, as well as:
LSI trip configuration with programmable ground fault alarm
LSIG (Ground-fault trip) with programmable ground fault alarm
Incremental “fine tuning” of L, S, I, and G pickup and delay settings
LCD dot matrix display and LED trip indication
Advanced user interface
Advanced protection IDMTL—selectable long-time delay bands
Neutral protection
Power measurement
Contact wear indication
Modbus communications—PowerLogic compatible
Local and remote settings
MicroLogic (Harmonic) 5.0H and 6.0H Trip Units
Power quality measurement and advanced protection features. Includes all features
listed for the MicroLogic power trip unit, as well as:
Enhanced power measurements functions
Power quality measurements
Adjustable Rating Plugs for PowerPact™ P-Frame and R-Frame and MasterPact™
NT and NW Circuit Breakers—Selection
To provide maximum design flexibility, system protection, and field upgradeability, each
MicroLogic™ trip unit is equipped with an interchangeable long-time rating plug. Each
trip unit requires an adjustable rating plug to determine the long-time pickup range of the
circuit breaker. These plugs are factory installed on new trip units, or can be ordered
separately for field-installable upgrades.
Adjustable rating plugs are offered in eight different ranges of long-time pickup
adjustments. The following chart show the ranges of adjustments. Each adjustment
times the sensor rating (lr x In) of the circuit breaker sets the long-time pickup value of
the circuit breaker.