Automatic Switches PowerPact Automatic Switches
www.se.com/us
Class 600 / Refer to Catalog 0612CT0101
PowerPact Automatic Switches
J-Frame
Switch
L-Frame
Switch
Automatic molded case switches open instantaneously at a factory preset magnetic trip
point. Calibrated to protect only the molded case switch itself, when it is subjected to high
fault currents. The trip point is nonadjustable and provides no overload or low level fault
protection.
•
PowerPact™ H-, J-, and L-frame automatic switches are available in unit mount, I-
Line™, plug-in and drawout versions.
•
Accept the same lugs and accessories as equivalent thermal-magnetic circuit
breakers
[1].
•
May be interlocked with another switch or circuit breaker to form a source-changeover
system
•
UL Listed per UL 489 and CSA Certified.
Table 7.89: PowerPact™ B-Frame Automatic Molded Case Switches, 600 Vac
Circuit
Breaker
Poles
Ampere
Rating
D Withstand G Withstand J Withstand
Terminal
Wire Range
Cat. No.
Trip
Point
Cat. No.
Trip Point
Cat. No.
Trip Point
B-Frame
2 [2]
125 A BDL26000S12 1625 A BGL26000S12 1625 A BJL26000S12 1625 A LV426973 14–2/0 AWG Cu
3 125 A BDL36000S12 1625 A BGL36000S12 1625 A BJL36000S12 1625 A LV426974 14–2/0 AWG Cu
Table 7.90: H-, J-, and L-Frame PowerPact™ Automatic Molded Case Switches, 600 Vac
Circuit
Breaker
Poles
Ampere
Rating
G Withstand L Withstand R Withstand
Terminal
Wire Range
Cat. No.
Trip
Point
Cat. No.
Trip Point
Cat. No.
Trip Point
H-Frame
J-Frame
2
150 A
HGL26000S15 [2]
2250 A HLL26000S15 2250 A — — AL150HD 14 AWG–3/0 AWG Al/Cu
175 A JGL26000S17 3125 A JLL26000S17 3125 A — — AL175JD 4–4/0 AWG Al/Cu
250 A JGL26000S25 3125 A JLL26000S25 3125 A — — AL250JD 3/0 AWG–350 kcmil Al/Cu
3
150 A HGL36000S15 2250 A HLL36000S15 2250 A — — AL150HD 14 AWG–3/0 AWG Al/Cu
175 A JGL36000S17 3125 A JLL36000S17 3125 A JRL36000S17 3125 A AL175JD 4–4/0 AWG Al/Cu
250 A JGL36000S25 3125 A JLL36000S25 3125 A JRL36000S25 3125 A AL250JD 3/0 AWG–350 kcmil Al/Cu
L-Frame
3
400 A LGL36000S40X 4800 A LLL36000S40X 4800 A LRL36000S40X 4800 A AL150HD AL600LS52K3
(2) 2/0 AWG–500 kcmil Al/Cu
600 A LGL36000S60X 6600A LLL36000S60X 6600 A LRL36000S60X 6600 A AL250JD
4
400 A LGL46000S40X 4800 A LLL46000S40X 4800 A LRL46000S40X 4800 A AL150HD AL600LS52K4
(2) 2/0 AWG–500 kcmil Al/Cu
600 A LGL46000S60X 6600A LLL46000S60X 6600 A LRL46000S60X 6600 A AL250JD
Table 7.91: P-Frame and R-Frame PowerPact™ Automatic Molded Case Switches [3], 600 Vac
Frame Poles
Ampere
Rating
J Withstand K Withstand L Withstand
Terminal
Wire Range
Cat. No.
Trip Point
Cat. No.
Trip Point
Cat. No.
Trip Point
P
2
600 A PJL26000S60 10 kA PKL26000S60 24 kA
PLL24000S60 [4]
10 kA
AL800M23K
(3) 3/0 AWG–500 kcmil
Al or Cu
800 A PJL26000S80 10 kA PKL26000S80 24 kA
PLL24000S80 [4]
10 kA
1000 A PJL26000S10 10 kA PKL26000S10 24 kA
PLL24000S10 [4]
10 kA
AL1200P25K
(4) 3/0 AWG–500 kcmil
Al or Cu
1200 A PJL26000S12 10 kA PKL26000S12 24 kA
PLL24000S12 [4]
10 kA
3
600 A PJL36000S60 10 kA PKL36000S60 24 kA
PLL34000S60 [4]
10 kA
AL800M23K
(3) 3/0 AWG–500 kcmil
Al or Cu
800 A PJL36000S80 10 kA PKL36000S80 24 kA
PLL34000S80 [4]
10 kA
1000 A PJL36000S10 10 kA PKL36000S10 24 kA
PLL34000S10 [4]
10 kA
AL1200P25K
(4) 3/0 AWG–500 kcmil
Al or Cu
1200 A PJL36000S12 10 kA PKL36000S12 24 kA
PLL34000S12 [4]
10 kA
R
2
1200 A — — RKF26000S12 57 kA RLF26000S12 48 kA
R-frame circuit breakers can be
bus-connected or cable-connected.
For cable connections, RLTB kit or
equivalent bus structure is required.
Kit is included with 3000 A switches.
For all others, see page 7-59.
1600 A — — RKF26000S16 57 kA RLF26000S16 48 kA
2000 A — — RKF26000S20 57 kA RLF26000S20 48 kA
2500 A — — RKF26000S25 57 kA RLF26000S25 48 kA
3
1200 A — — RKF36000S12 57 kA RLF36000S12 48 kA
1600 A — — RKF36000S16 57 kA RLF36000S16 48 kA
2000 A — — RKF36000S20 57 kA RLF36000S20 48 kA
2500 A — — RKF36000S25 57 kA RLF36000S25 48 kA
3000 A — — RKF36000S30 57 kA RLF36000S30 48 kA
Accessories see page 7-51 and Supplemental Digest Section 3
Optional Lugs see page 7-56 and Supplemental Digest Section 3
Dimensions see page 7-83 and page 7-84
Enclosures see page 7-85
Table 7.92: Q-Frame (240 Vac) PowerPact™ Automatic Molded Case Switches
Circuit
Breaker
Poles
Ampere
Rating
J Withstand
Wire Range
Cat. No.
Trip Point
Q-Frame
[5]
2 225 A
QBL22000S22
4500 A
4 AWG–300 kcmil
3 225 A
QBL32000S22
4500 A
Table 7.93: B-, H-, J-, L- P-, and R-Frame Withstand Ratings [6]
Voltage
Withstand
D G J K L R
240 Vac 25 kA 65 kA 100 kA 65 kA 125 kA 200 kA
480 Vac 18 kA 35 kA 65 kA
50 kA [7]
100 kA 200 kA
600 Vac 14 kA 18 kA 25 kA
50 kA [7]
50 kA 100 kA
7
MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
[1] Q-frame switches do not have electrical accessories available.
[2] True 2P device. Others are a 2P in a 3P module.
[3] UL magnetic trip tolerances are -20% / +30% from the nominal values shown.
[4] P-frame L-interrupting is available in 480 Vac only.
[5] Withstand rating of 10 kA at 240 Vac.
[6] The withstand rating is the fault current at rated voltage that the molded case switch will withstand without damage when protected by a circuit breaker with an equal continuous current
rating.
[7] B- and R-frame withstand is 65 kA.