Technical Data Bulletin

© 2020 Schneider Electric
All Rights Reserved
12/2/2020
7-31
www.se.com/us
PowerPact Family
PowerPact™ Molded Case Circuit Breakers
Class 611, 612
The PowerPact Advantage
Proven Performance: Industry-leading circuit breaker innovation and protection for
heavy-duty commercial and industrial applications.
Smart: Integrated metering options provide a cost-effective solution to reduce energy
consumption, optimize energy costs, and improve energy availablility for your facilities.
Flexible: Full range of thermal-magnetic and electronic trip molded case circuit
breakers from 15 to 3000 A, delivering the ratings, configurations, and operators for
your unique applications.
Simple: Common catalog numbers, standardized ratings, and a full range of field-
installable accessories make product selection, installation and maintenance easier
than ever.
Common Design Features: Mounting holes, door trim, and handle accessories
B-Frame
125 A
H-Frame
150 A
J-Frame
250 A
Q-Frame
250 A
L-Frame
600 A
M-Frame
800 A
P-Frame
1200 A
R-Frame
3000 A
Electronic Trip
Version
Electronic Trip
Version
Table 7.46: PowerPact Interrupting Ratings
Voltage
Interrupting Rating
B D G J K L R
240 Vac 10 kA 25 kA 65 kA 100 kA
65 kA [1]
125 kA 200 kA
480 Vac 18 kA 35 kA 65 kA
65 kA [2]
100 kA 200 kA
600 Vac 14 kA 18 kA 25 kA
65 kA [2] 50 kA [3]
100 kA
Table 7.47: Common Catalog Numbering System
Frame
Rating
Termination Poles
Voltage Amperage[4]
Suffix Code Suffix Code
H G L 3 6 1 5 0 A B S A
1=1Pole
2=2Pole
3=3Pole
4=4Pole
4=480 V
6=600 V
2A/2B Auxiliary Switch 110 Vac Shunt Trip
Frame Designation Interrupting Rating Terminations
B 125 A Frame 240 Vac 480 Vac 600Vac A I-Line
H 150 A Frame
B 10 kA
L Lugs on Both Ends
J 250 A Frame
D 25 kA 18 kA 14 kA
F Bus Bar (No Lugs)
Q 250 A Frame
G 65 kA 35 kA 18 kA
M Lugs Line Side Only
L 600 A Frame
J 100 kA 65 kA 25 kA
P Lugs Load End Only
M 800 A Frame
K 100 kA 65 kA 65 kA
N Plug-in
P 1200 A Frame L 125 kA 100 kA 50 kA D Drawout
R 3000 A Frame R 200 kA 200 kA 100 kA S Rear Connected Studs
For more information:
B-Frame Circuit Breakers, page 7-32
H- and J-Frame Circuit Breakers, page 7-33
Q-Frame Circuit Breakers, page 7-36
L-Frame Circuit Breakers, page 7-38
P-Frame Circuit Breakers, page 7-41
R-Frame Circuit Breakers, page 7-42
PowerPact™ H- and J-Frame Electronic Motor Circuit Protectors, page 7-48
Motor Circuit Protectors and Motor Protector Circuit Breakers, page 7-50
Automatic Switches, page 7-46
500 Vdc Circuit Breakers, page 7-45
Mission Critical Circuit Breakers, page 7-44
PowerPact™ Circuit Breaker Accessories, page 7-51
Motor Operators and Rotary Handles, page 7-52
Locks, Installation Accessories, and Rear Connections, page 7-54
Mechanical Lugs, page 7-54
Compression Lugs and Power Distribution Connectors (PDC), page 7-57
Terminal Nuts, Terminal Pads, Terminal Shields and Accessories, page 7-59
Plug-In and Drawout Mountings, page 7-60
MicroLogic™ Electronic Trip Units, page 7-61
MicroLogic™ Trip Unit Accessories, page 7-64
7
MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
[1] B-frame K interrupting rating is 100 kA at 240 Vac
[2] P-frame K interrupting is 50 kA at 480 and 600 Vac.
[3] P-frame L interrupting is 25 kA at 600 Vac.
[4] For amperage of M,-, P- or R-frame circuit breakers, add a zero to the three amperage digits; for example, 120 = 1200 A.