Multi 9 Circuit Breakers Busbar Offer Multi 9™ Miniature Circuit Breakers
Class 860 / Refer to Catalog LVCATM9OEM_EN
C60
SP
(UL1077) Comb Busbars
The comb busbars are used only for C60
SP
circuit breakers UL 1077 supplementary
protection in conformity with standards:
UL 1077 / CSA C22.2 No. 235 / IEC 60947-2 / GB 14048-2.
They perform distribution and subdistribution of the electric power supply and allow rapid
assembly and disassembly of equipment.
Table 7.43: C60
SP
Comb Busbars
Connection Accessories Comb Busbars Tooth Cover End-Piece
Function
The comb busbars make it easier to install Schneider Electric circuit breakers UL1077
supplementary protection.
Power supply directly in the cage of the circuit breaker.
The Tooth Caps are insulated protectors which may be
slipped onto the unused teeth of the comb busbar.
They come in strips with 1-pole spacing, but can be
snapped apart to be used individually.
Number of poles
1P
2P 3P
All
Voltage rating (Ue)
480Y/277 Vac 480Y/277 Vac 480Y/277 Vac
Catalogue numbers 10285
10286
10287
60488
Number of 18 mm modules
12 (8.5 in./216 mm) 12 (8.5 in./216 mm) 12 (8.5 i./216 mm)
Set of 1 1 1 20
Technical Specifications
Insulation voltage (Ui) 690 Vac
Impulse withstand voltage
(Uimp)
12 kV under 240 V
5 kV under 480Y/277 V or 277 V
Acceptable current at 40°C
(Ie)
63 A with 1 central power supply point 100 A with 2 power supply points
Power supply via cable directly in the cage of the device:
cross section max: 3 AWG (25 mm
2
)
cross section min: 10 AWG (5.27 mm
2
)