Technical Data Bulletin
Table Of Contents
- Section 7 Miniature and Molded Case Circuit Breakers
- Selection Information
- QO™ and QOU Miniature Circuit Breakers
- Homeline™ Miniature Circuit Breakers
- Multi 9™ Miniature Circuit Breakers
- PowerPact™ Molded Case Circuit Breakers
- Mission Critical Circuit Breakers
- 500 Vdc Circuit Breakers
- Automatic Switches
- Motor Circuit Protectors
- PowerPact™ Circuit Breaker Accessories
- MicroLogic™ Electronic Trip Units
- MasterPact™ Power Circuit Breakers
- Enerlin’X Digital Solutions
- Ground-Fault Protection
- Dimensions and Shipping Weights
- Circuit Breaker Enclosures
7-24
© 2020 Schneider Electric
All Rights Reserved
12/2/2020
Homeline™ Miniature Circuit Breakers Plug-On Circuit Breakers
www.se.com/us
Class 1170 / Refer to Catalog 1100CT0501
Table 7.35 HOMT Quad Tandem 2P Circuit Breakers (cont'd.)
Ampere Rating [10]
AIR
(2) 2P Tandem—120/240 Vac
(Two Spaces Required)
2P 2P
30 A 40 A 10 kA HOMT230240
30 A 50 A 10 kA HOMT230250
NOTE: Typical catalog no. (i.e. HOMT215230) represents two 2P; outer poles (one
15 A 2P with common trip) and inner poles (one 30 A 2P with common trip).
Homeline Circuit Breaker Wire Sizes
Table 7.36: Wire Sizes for Homeline Circuit Breakers
Breaker Type Ampere Rating
Wire Size (AWG/kcmil) [11]
Aluminum
Copper
HOM
1P
15–30 A 14–8 AWG
14–8 AWG or
(2) 14–10 AWG
40–50 A 8–2 AWG 8–2 AWG
HOM
2P
15–30 A 14–8 AWG
14–8 AWG or
(2) 14–10 AWG
35–70 A 8–2 AWG 8–2 AWG
80–125 A 4–2/0 AWG 4–2/0 AWG
150–200 A 4 AWG–300 kcmil 4 AWG–300 kcmil
HOMT and Quad
15–30 A 14–8 AWG 14–8 AWG
Quad Only
40–50 A 6–12 AWG 6–14 AWG
HOM-GFI - 1P 15–20 A 14–10 AWG 14–10 AWG
HOM-GFI - 2P 15–50 A 12–4 AWG 14–6 AWG
Accessories for Homeline Circuit Breakers
Table 7.37: Accessories for Use with Homeline Circuit Breakers
Description
Cat. No.
Handle Attachments
Handle Tie: Converts any two adjacent 120/240 Vac single HOM circuit breakers to independent trip 2P
HOM1HT
Handle Tie: Converts any two adjacent 120/240 Vac
1P side-by-side HOMT circuit breakers to independent trip 2P
HOMTHT
Handle Clamp: Clamp for holding HOM 1P handle in the ON or OFF position
QO1LO
Handle Blocking Device: Attaches to standard HOM 2P circuit breakers for holding the handle in the OFF position
HOM2HBD
Handle Padlock Attachment: For padlocking 1P Standard HOM breakers in the ON or OFF position
HOM1PA
Handle Padlock Attachment: For
padlocking 2P Standard HOM circuit breakers in ON or OFF position
15–70 A HOM2PALA
80–125 A HOM2PAHA
150–200 A HOM2PAVHA
Handle Padlock Attachment: For padlocking 1P CAFI, DF, GFI, and EPD HOM breakers in ON or OFF position
HOMELEC1PA
Handle Padlock Attachment: For padlocking 2P CAFI, GFI, and EPD HOM breakers in ON or OFF position
HOMELEC2PALA
Handle Padlock Attachment: For padlocking center poles of Homeline Quad breakers in the OFF position
HOMQPA
Handle Padlock Attachment: For padlocking main circuit breakers in convertible load center in OFF position
50–125 A
QOM1PA [12]
100–225 A
QOM2PA [12]
Sub-Feed Lugs
125 A 2P plug-on—2 spaces required
HOML2125
225 A 2P plug-on—4 spaces required HOML2225 [13]
7
MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
[10] 15– 20 A tandem or quad tandem circuit breakers are suitable for use with 60
o
C or 75
o
C conductors. 25– 50 A tandem or quad tandem circuit breakers are suitable for use with 75
o
C
conductors only.
[11] 15–30 A circuit breakers are suitable for use with 60
o
C or 75
o
C conductors. 40–125 A circuit breakers are suitable for use with 75
o
C conductors.
[12] 50–125 A QOM1 frame size; 100–225 A QOM2 frame size.
[13] Requires four spaces (1 AWG–300 kcmil Al/Cu). Use only in 1Ø panel rated 150 A or greater.