Technical Data Bulletin

© 2020 Schneider Electric
All Rights Reserved
12/2/2020
7-23
www.se.com/us
Plug-On Circuit Breakers Homeline™ Miniature Circuit Breakers
Class 1170 / Refer to Catalog 1100CT0501
Homeline Ground-Fault Circuit Breaker (HOM-GFI)
HOM 1P GFI
(With Ground Fault
Circuit Interrupter)
1 Space Required
HOM 2P GFI
(With Ground Fault
Circuit Interrupter)
2 Spaces Required
HOM-GFI circuit breakers provide overload and short circuit protection, combined with
Class A ground fault protection. Class A denotes a ground fault circuit interrupter that will
trip when a fault current to ground is 6 milliamperes or more.
Table 7.31: HOM-GFI Circuit Breakers
Circuit Breaker Type
Ampere
Rating
AIR
1P—120 Vac
1 Space Required
2P—120/240 Vac
Common Trip
2 Spaces Required
Ground-Fault Circuit
Interrupter(Pigtail
Neutral)
15 A 10 kA HOM115GFI HOM215GFI
20 A 10 kA HOM120GFI HOM220GFI
25 A 10 kA HOM225GFI
30 A 10 kA HOM230GFI
35 A 10 kA HOM235GFI
40 A 10 kA HOM240GFI
45 A 10 kA HOM245GFI
50 A 10 kA HOM250GFI
Plug-On Neutral Ground-
Fault Circuit Interrupter
15 A 10 kA
HOM115PGFI[6]
20 A 10 kA
HOM120PGFI[6]
Homeline Equipment Protection Device (HOM-EPD)
Homeline Equipment Protection Device—Circuit Breakers with 30 mA Equipment
Ground Fault Protection (UL Listed).
Table 7.32: HOM-EPD Circuit Breakers
Amperes
1P—120 Vac
2P—120/240 Vac
Common Trip
15 A HOM115EPD
HOM215EPD [7]
20 A HOM120EPD HOM220EPD
25 A HOM225EPD
30 A HOM230EPD
40 A HOM240EPD
50 A HOM250EPD
Homeline Tandem and Quad Tandem Circuit Breakers (HOMT)
Table 7.33: HOMT Tandem Circuit Breakers
Ampere Rating [8]
AIR
1P Tandem—120/240 Vac (One Space Required)
15 and 15 A 10 kA
HOMT1515 [9]
15 and 20 A 10 kA
HOMT1520 [9]
20 and 20 A 10 kA
HOMT2020 [9]
30 and 15 A 10 kA
HOMT3015 [9]
30 and 20 A 10 kA
HOMT3020 [9]
HOMT Quad
Circuit Breaker
2 Spaces Required
Table 7.34: HOMT Quad Tandem 1P Circuit Breakers
Ampere Rating [8]
AIR
2P Tandem—120/240 Vac
(Two Spaces Required)
1P 2P
(2) 15 A
15 A 10 kA HOMT1515215
(2) 15 A
20 A 10 kA HOMT1515220
(2) 15 A
25 A 10 kA
HOMT1515225 [7]
(2) 15 A
30 A 10 kA HOMT1515230
(2) 15 A
40 A 10 kA HOMT1515240
(2) 15 A
50 A 10 kA HOMT1515250
(2) 20 A
20 A 10 kA HOMT2020220
(2) 20 A
25 A 10 kA HOMT2020225
(2) 20 A
30 A 10 kA HOMT2020230
(2) 20 A
40 A 10 kA HOMT2020240
(2) 20 A
50 A 10 kA HOMT2020250
NOTE: Typical catalog no. (e.g. HOMT 1515230) represents two 1P, outer poles (two
15 A 1P CBs) and one 2P inner circuit breaker with common trip (one 30 A 2P CB).
Table 7.35: HOMT Quad Tandem 2P Circuit Breakers
Ampere Rating [8]
AIR
(2) 2P Tandem—120/240 Vac
(Two Spaces Required)
2P 2P
15 A 15 A 10 kA HOMT215215
15 A 20 A 10 kA HOMT215220
15 A 25 A 10 kA HOMT215225
15 A 30 A 10 kA HOMT215230
15 A 40 A 10 kA HOMT215240
15 A 50 A 10 kA HOMT215250
20 A 20 A 10 kA HOMT220220
20 A 25 A 10 kA HOMT220225
20 A 30 A 10 kA HOMT220230
20 A 40 A 10 kA HOMT220240
20 A 50 A 10 kA HOMT220250
25 A 25A 10 kA HOMT225225
25 A 30 A 10 kA HOMT225230
25 A 40 A 10 kA HOMT225240
25 A 50 A 10 kA HOMT225250
30 A 30 A 10 kA HOMT230230
7
MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
[6] New Plug-on Neutral
[7] This product is discontinued.
[8] 15– 20 A tandem or quad tandem circuit breakers are suitable for use with 60
o
C or 75
o
C conductors. 25– 50 A tandem or quad tandem circuit breakers are suitable for use with 75
o
C
conductors only.
[9] UL Listed as HACR type for use with air conditioning, heating and refrigeration equipment haing motor group combinations and marked for use with HACR type circuit breakers.