Technical Data Bulletin
Table Of Contents
- Section 7 Miniature and Molded Case Circuit Breakers
- Selection Information
- QO™ and QOU Miniature Circuit Breakers
- Homeline™ Miniature Circuit Breakers
- Multi 9™ Miniature Circuit Breakers
- PowerPact™ Molded Case Circuit Breakers
- Mission Critical Circuit Breakers
- 500 Vdc Circuit Breakers
- Automatic Switches
- Motor Circuit Protectors
- PowerPact™ Circuit Breaker Accessories
- MicroLogic™ Electronic Trip Units
- MasterPact™ Power Circuit Breakers
- Enerlin’X Digital Solutions
- Ground-Fault Protection
- Dimensions and Shipping Weights
- Circuit Breaker Enclosures
7-22
© 2020 Schneider Electric
All Rights Reserved
12/2/2020
Homeline™ Miniature Circuit Breakers Plug-On Circuit Breakers
www.se.com/us
Class 1170 / Refer to Catalog 1100CT0501
Homeline Standard Plug-On Circuit Breakers
HOM 1P
1 Space Required
HOM 2P
2 Spaces Required
HOM2200BB
Branch Circuit Breaker
4 Spaces Required
The Square D Homeline circuit breakers are in a 1 in. wide format for 1-pole circuit
breakers. They are designed to plug into Homeline load centers.
Table 7.27: Standard HOM Plug-on Circuit Breakers
Ampere
Rating
AIR
1P—120 Vac,
1 Space Required
2P—120/240 Vac Common Trip
2 Spaces Required.
15 A 10 kA
HOM115 [1][2] HOM215 [2]
20 A 10 kA
HOM120 [1][2] HOM220 [2]
25 A 10 kA
HOM125 [2] HOM225 [2]
30 A 10 kA
HOM130 [2] HOM230 [2]
35 A 10 kA —
HOM235 [2]
40 A 10 kA
HOM140 [2] HOM240 [2]
45 A 10 kA —
HOM245 [2]
50 A 10 kA
HOM150 [2] HOM250 [2]
60 A 10 kA —
HOM260 [2]
70 A 10 kA —
HOM270 [2]
80 A 10 kA —
HOM280 [2]
90 A 10 kA —
HOM290 [2]
100 A 10 kA —
HOM2100 [2]
110 A 10 kA —
HOM2110 [2]
125 A 10 kA —
HOM2125 [2]
150 A 10 kA —
HOM2150BB [2][3]
175 A 10 kA —
HOM2175BB [2][3]
200 A 10 kA —
HOM2200BB [2][3]
Homeline High Magnetic Circuit Breakers (HOM-HM)
High magnetic trip circuit breakers are recommended for applications where high initial
inrush current may occur.
Table 7.28: HOM-HM Circuit Breakers
Amperes
1P—120/240 Vac 2Ps
15 A
HOM115HM [4]
—
20 A
HOM120HM [2]
—
Homeline Combination Arc Fault Circuit Interrupters (HOM-CAFI)
HOM 1P CAFI
Plug-on Neutral
HOM 1P CAFI
Pigtail
Homeline Combination Arc Fault Circuit Interrupters—Provide overload and short circuit
protection, plus arc fault protection in accordance with the NEC and UL1699.
Table 7.29: HOM-CAFI Circuit Breakers
Circuit Breaker Type Ampere Rating
Poles
120 Vac
Cat. No.
One-Pole
Combination Arc-Fault Circuit
Interrupter with Pigtail Neutral
15 A 1
HOM115CAFI [2]
20 A 1
HOM120CAFI [2]
Plug-On Neutral Combination
Arc-Fault Interrupter
15 A 1
HOM115PCAFI [2]
20 A 1
HOM120PCAFI [2]
Two-Pole
Combination Arc-Fault Circuit
Interrupter with Pigtail Neutral
15 A 2
HOM215CAFI [2] [5]
20 A 2
HOM220CAFI [2] [5]
Homeline Dual Function Circuit Breaker (HOM-DF)
HOM 1P DF
Plug-on Neutral
HOM 1P DF
Pigtail
Homeline Combination Arc Fault and Ground Fault Circuit Interrupters (Dual Function)—
Provide overload and short circuit protection, plus arc fault and ground fault protection in
a single device in accordance with the NEC, UL1699 and UL943.
Table 7.30: HOM-DF Circuit Breakers
Circuit Breaker Type
Ampere
Rating
Poles
120 Vac
Cat. No.
Combination Arc-Fault and Ground Fault Circuit
Interrupter with Pigtail Neutral
15 A 1
HOM115DF [2]
20 A 1
HOM120DF [2]
Plug-On Neutral Combination
Arc-Fault and Ground Fault
Circuit Interrupter
15 A 1
HOM115PDF [2]
20 A 1
HOM120PDF [2]
7
MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
[1] UL Listed as SWD (switching duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.
[2] UL Listed as HACR type for use with air conditioning, heating and refrigeration equipment haing motor group combinations and marked for use with HACR type circuit breakers.
[3] Requires four spaces (1 AWG–300 kcmil Al/Cu). Use only in 1Ø panel rated 150 A or greater.
[4] This product is discontinued.
[5] For 120/240 V only, not for 208Y/120 V.