QO Plug-On Circuit Breakers QO™ and QOU Miniature Circuit Breakers
Class 685, 690, 730, 912, 950 / Refer to Catalog: 0730CT9801
QO Arc-Fault Circuit Breaker (QO-CAFI)
1P
QO-CAFI
Plug-On Neutral
1P
QO-CAFI
Pigtail
QO arc-fault circuit breakers provide protection for Series and Parallel Type Arcing as
required by the NEC and local code adoption, and comply with UL1699.
Table 7.6: QO-CAFI Circuit Breakers
Circuit
Breaker
Type [15]
Ampere
Rating
One–Pole 120 Vac Two–Pole 120/240 Vac
10 k AIR
1 Space
Required
22 k AIR
1 Space Required
10 k AIR
2 Space Required
22 k AIR
2 Space Required
Combination
Arc-fault
Interrupter
(Pigtail
Neutral)
15
20
QO115CAFI
QO120CAFI
QO115VHCAFI
QO120VHCAFI
QO215CAFI [16]
QO220CAFI [16]
QO215VHCAFI [16]
QO220VHCAFI [16]
Plug-On
Neutral
Combination
Arc-fault
Interrupter
15
20
QO115PCAFI
QO120PCAFI
QO115VHPCAFI
QO120VHPCAFI
QO Dual Function Circuit Breaker
1P QO-DF
Plug-on Neutral
1P QO-DF
Pigtail
QO Combination Arc Fault and Ground Fault Circuit Interrupters (Dual Function) provide
overload and short circuit protection, plus arc fault and ground fault protection in
accordance with the NEC, UL1699 and UL943.
Table 7.7: QO-DF Circuit Breakers
Circuit Breaker Type [15]
Ampere
Rating
1P 120 Vac
10 k AIR
1 Space Required
1P 120 Vac
22 k AIR
1 Space Required
Combination Arc-fault and Ground Fault
Circuit Interrupter (Pigtail Neutral)
15
20
QO115DF
QO120DF
QO115VHDF
QO120VHDF
Plug-On Neutral Combination Arc-fault and
Ground Fault Circuit Interrupter
15
20
QO115PDF
QO120PDF
QO115VHPDF
QO120VHPDF
QO Ground-Fault Circuit Breakers (GFI)
1P
QO-GFI
2P
QO-GFI
Qwik-Gard
™
circuit breakers provide overload and short circuit protection, combined with
Class A ground fault protection. Class A denotes a ground fault circuit interrupter that will
trip when a fault current to ground is 6 mA or more, for people protection. Do not connect
to more than 250 feet of load conductor for the total one-way run to prevent nuisance
tripping.
Table 7.8: QO-GFI Circuit Breakers
Circuit
Breaker
Type
Ampere
Rating
[17]
Qwik-Gard Circuit Breakers With Ground Fault Circuit Interrupter
1P 120 Vac
2P Common Trip
120/240 Vac
3P Common
Trip
208Y/120 Vac
10 k AIR
1 Space
Required
22 k AIR
1 Space Required
10 k AIR
2 Spaces Required
10 k AIR
3 Spaces
Required
Ground-Fault
Circuit
Interrupter
(Pigtail
Neutral)
15
QO115GFI QO115VHGFI QO215GFI QO315GFI
20
QO120GFI QO120VHGFI QO220GFI QO320GFI
25 — —
QO225GFI
—
30
QO130GFI QO130VHGFI QO230GFI QO330GFI
35 — —
QO235GFI
—
40 — —
QO240GFI QO340GFI
45 — —
QO245GFI
—
50 — —
QO250GFI QO350GFI
60 — —
QO260GFI [18]
—
Plug-On
Neutral
Ground-Fault
Circuit
Interrupter
15
QO115PGFI[19]
— — —
20
QO120PGFI[19]
— — —
7
MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
[15] UL Listed as HACR type for use with air conditioning, heating and refrigeration equipment haing motor group combinations and marked for use with HACR type circuit breakers.
[16] For 120/240 V only, not for 208Y/120 V.
[17] 10–30 A circuit breakers are suitable for use with 60
o
C or 75
o
C conductors. 35–60 A circuit breakers are suitable for use with 75
o
C conductors.
[18] Suitable only for feeding 240 Vac and 208 Vac two-wire loads. Does not contain load neutral connection.