Servicepak
™
Power Outlet Panels
www.se.com/us
Class 1140
1
LOAD CENTERS
Power Outlet Panels for Construction Sites
T
T
TT T
T
T T
TT
TT TT
TTT
T T
T
TT
T
1C 2C 3C
4C 5C 6C
8C
TT T
7C 9C
10C 11C 12C
13C 14C
•
Provide temporary power at construction sites.
•
Each receptacle protected by QO-GFI circuit breaker in compliance with NEC
®
requirements.
•
Each enclosure is rainproof.
•
10 kA short circuit current rating.
•
UL Listed as suitable for use as temporary site service equipment.
•
Provided with neutral bonding provisions.
•
Boxes have provisions for type “B’’ hubs to be field-installed.
Table 1.99: Construction Site Panels
Power
Outlet
Configuration
Service
[1]
Mains
Ampere
Rating
Circuit Breaker
(Included)
Receptacles
(Included)
Cat. No. [2]
Main Wire
Size
AWG [3]
A C D E F Cu Al
1C 1Ø2W 40 A
(1) QO120GFI
1 PAK10C1 14–6 12–6
2C 1Ø2W 40 A
(2) QO120GFI
2
PAK11C [4]
14–6 12–6
2C 1Ø2W 40 A
(2) QO120GFI
2 PAK11C1 14–6 12–6
3C 1Ø3W 70 A
(1) QO120GFI
(1) QO230GFI
1 1 PAK31CGFI 8–1 8–1
4C 1Ø3W 70 A
(1) QO120GFI
(1) QO220GFI
1 1 PAK36C1GFI 8–1 8–1
5C 1Ø3W 70 A
(1) QO120GFI
(1) QO250GFI
1 1 PAK51CGFI 8–1 8–1
6C 1Ø3W 70 A
(1) QO120GFI
(1) QO250GFI
1 1 PAK55CGFI 8–1 8–1
7C 1Ø3W 70 A
(2) QO120GFI
(1) QO220GFI
2 1 PAK72CGFI 8–1 8–1
8C 1Ø3W 70 A
(2) QO120GFI
(1) QO250GFI
2 1 PAK76CGFI 8–1 8–1
9C 1Ø3W 100 A
(1) QO120GFI
(2) QO250GFI
1 2 PAK1004CGFI 14–1 12–1
Power Outlet Panels for Recreational Vehicle Parks
A
20 A 125 V 2W and Grd.
NEMA 5-20R
B
30 A 125 V 2W and Grd
ANSI 73.13
C
50 A 125/250 V 3W and Grd.
NEMA 14-50R
D
20 A 250 V 2W and Grd.
NEMA 6-20R
E
30 A 125/250 V 3W and Grd.
NEMA 14-30R
F
50 A 250 V 2W and Grd.
NEMA 6-50R
All non-pedestal devices have provisions to field-install a Type “B’’ hub
on the bottom endwall for bottom feed from a conduit riser. Order Type
“B’’ bolt-on hub (B250 Max.) and two mounting screws
(Cat. No. 8002505501) and two hex nuts (Cat. No. 2340102000).
•
Provide electrical power to individual recreational vehicle park sites.
•
Each receptacle protected by appropriate GFI or Standard QO
™
circuit breaker.
•
All receptacles and circuit breakers included.
•
10 kA short circuit current rating.
•
UL Listed.
•
All enclosures are rainproof.
•
No neutral bonding provisions.
•
Loop-feed provisions.
Table 1.100: Recreational Vehicle Park Panels
Power Outlet
Configura-
tion
Serv-
ice
[1]
Mains
Am-
pere
Rating
Circuit Breaker
(Included)
Receptacles
(Included) [5]
Cat. No.
Main Wire Size
AWG/kcmil [6]
Phase and Neutral
A B C Cu Al
Underground or Overhead Loop-Feed Terminals—Non-Pedestal [2] [7]
11C 1Ø2W 40 A
(2) QO120GFI
2 PAK11CTG
14–6 12–6
12C 1Ø2W 50 A
(1) QO120GFI
(1) QO130
1 1
PAK41CTG [8]
(2) QO130
12–1
14C 1Ø3W 100 A
(1) QO120GFI
(1) QO250
(1) QO130
1 1 1
PAK75CTG
(Not Loop Feed)
[8]
14–1 12–1
Pedestal Mounted—Underground Loop-Feed Terminals [9] [10]
11C 1Ø2W 40 A
(2) QO120GFI
2 PAK11PG
(2)6–250 (2)6–250
12C 1Ø2W 50 A
(1) QO120GFI
(1) QO130
1 1
PAK41PG [8]
13C 1Ø2W 75 A
(1) QO120GFI
(2) QO130
1 2
PAK61PG [8]
14C 1Ø3W 100 A
(1) QO120GFI
(1) QO250
(1) QO130
1 1 1
PAK75PG [8]
[1] (1Ø2W 120 Vac) (1Ø3W 120/240 Vac)
[2] Devices have a bolt-on factory-installed closing cap. Order type “B’’ bolt-on hub separately from page 1-18.
[3] Equipment ground terminal suitable for (2) 14 or 12 AWG Cu or (2) 12 or 10 AWG Al.
[4] Receptacles in this device are in bottom endwall and are accessible with outer door padlocked. “Order Only’’ from Lexington—Minimum order quantity is 50 devices.
[5] 20 A receptacles protected by 20 A GFI circuit breaker.
[6] Two wires each per phase, neutral, and equipment ground—for loop feed (except PAK75CTG).
[7] Equipment ground terminal suitable for (2) 14–12 AWG Cu or (2) 12–10 Al.
[8] GFI circuit breaker can be substituted for standard 30 A circuit breaker. Add suffix "FI’’ to catalog number. Example: PAK41CTGFI.
[9] Stabilizer foot available for use in unstable ground, order HNPSF
[10] Equipment ground terminals suitable for (2) 10–2/0 AWG Cu or (2) 6–2/0 AWG Al.