Homeline Load Centers, Indoor,
Homeline™ Load Centers
Class 1170 / Refer to Catalog 1100CT0501
HOM Standard Load Center Main Lugs, Fixed Mains
(1Ø3W—120/240 Vac Indoor—UL Listed)
Table 1.50: Fixed Main Lugs Load Centers (Accepts Only HOM Plug-on Circuit Breakers - Not compatible with HOM Plug-on Neutral
Circuit Breakers)
Mains
Rating
Spaces
Max.
Single
Pole
Circuits [1]
Max.
Tandem
Circuit
Breakers
Load Center
Box, Interior and Cover [2]
Main Wire Size
AWG/kcmil
Equipment Ground
Bar Kit
(Order Separately)
Box No.
[3]
Al Cu
I
N
D
O
O
R
Main Lugs—10 kA Short Circuit Current Rating Order HOM Circuit Breakers (See page 1-18) Factory-installed Fixed Main Lugs
 70 A 2 4 2
HOM24L70F/S [4] [5]
12–3 14–4 PK3GTA1 2
100 A 6 12 6
HOM612L100F/S [4] [6]
8–1 PK7GTA 4
125 A 4 8 4 HOM48L125GC 12–2/0 14–2/0 PK7GTA Included 21
HOM Plug-on Neutral Load Center Main Lugs, Convertible Mains
(1Ø3W—120/240 Vac Indoor—UL Listed)
Table 1.51: Convertible Main Lugs Plug-on Neutral Load Centers (Compatible with HOM Plug-on Circuit Breakers and HOM Plug-on
Neutral Circuit Breakers)
Mains
Rating
Spaces
Max.
Single
Pole
Circuits [1]
Max.
Tandem
Circuit
Breakers
Load Center
Box, Interior and Cover [2]
Main Wire Size
AWG/kcmil
Equipment Ground
Bar Kit
(Order Separately)
Box No.
[3]
Al Cu
I
N
D
O
O
R
Convertible Mains—Factory-installed Main Lugs
QOM1 Main Frame Size—Convertible to Main Circuit Breaker (See page 1-24)
125 A
8 16 8 HOM816L125PC
6–2/0
6–1 PK9GTA 6
12 24 12 HOM1224L125PC 6–1 PK15GTA  6
16 32 16 HOM1632L125PC 6–1/0 PK15GTA 8
20 40 20 HOM2040L125PC 6–1/0 PK18GTA 8
30 60 30 HOM3060L125PC 6–2/0 PK23GTA 10
Convertible Mains—Factory-installed Main Lugs
QOM2 Main Frame Size—Convertible to Main Circuit Breaker (See page 1-24)
225 A
30 60 30 HOM3060L225PC
4–300 4–250
PK23GTA 10
40 80 40 HOM4080L225PC PK27GTA 12
42 84 42 HOM4284L225PC PK27GTA 12
60 120 60
HOM60120L225PC [7] PK27GTA
25
Convertible Mains—Factory-installed Main Lugs—Ground Bar Included
QOM1 Main Frame Size—Convertible to Main Circuit Breaker (See page 1-24)
125 A
8 16 8 HOM816L125PGC
6–2/0
6–1
PK9GTA, PK9GTA W/
LK100AN Included
6
12 24 12 HOM1224L125PGC 6–1
PK9GTA, PK9GTA W/
LK100AN Included
6
20 40 20 HOM2040L125PGC 6–1/0
PK9GTA, PK9GTA W/
LK100AN Included
8
24 48 24 HOM2448L125PGC 6–1/0
PK9GTA, PK18GTAL
Included
8
Convertible Mains—Factory-installed Main Lugs—Ground Bar Included
QOM2 Main Frame Size—Convertible to Main Circuit Breaker (See page 1-24)
225 A
30 60 30 HOM3060L225PGC
4–300 4–250
PK9GTA, PK18GTAL
Included
10
16 32 16 HOM1632L225PGC
PK9GTA, PK9GTA W/
LK100AN Included
9
20 40 20 HOM2040L225PGC
PK9GTA, PK9GTA W/
LK100AN Included
9
40 80 40 HOM4080L225PGC
PK18GTAL and
PK15GTA Included
12
42 84 42 HOM4284L225PGC
PK18GTAL and
PK15GTA Included
12
Above listings through 200 A mains rating meet Federal Specification W-P-115c as Type 1, Class 2.
Field-Installed Main Circuit Breaker Kits,
QOM1 Frame Size
50–125 Amperes
Table 1.52: QOM1 Frame Size—Use with Convertible Main Load Centers Only
Main Circuit Breaker
Rating [8]
Convertible
Load Center Mains Rating
22 k AIR [9]
Lug Wire Size [10] AWG/
kcmil
Main Circuit Breaker
50 A 100–125
QOM50VH
12–2/0 Al or Cu
60 A 100–125
QOM60VH
70 A 100–125
QOM70VH
80 A 100–125
QOM80VH
90 A 100–125
QOM90VH
100 A 100–125
QOM100VH
110 A 125
QOM110VH
125 A 125
QOM125VH
1
LOAD CENTERS
[1] Maximum single pole branch circuits utilizing HOM and/or HOMT circuit breakers.
[2] C at end of catalog number indicates combination flush/surface cover included with device.
[3] See page 1-29
[4] F/S at end of catalog number indicates to order F for flush device or S for surface device. The cover does not have a door.
[5] HOM-GFI and HOM-AFI branch circuit breakers are limited to number 10 maximum wire.
[6] 70 A maximum branch circuit breaker, 100 A maximum back feed main circuit breaker.
[7] Door kit available separately. Order QOCDK60.
[8] Do not exceed the load center mains rating.
[9] 22 k AIR main circuit breaker UL Listed for use ahead of QO, QOT and QO-PL 10 k AIR branch circuit breakers to permit their application on systems with up to 22 kA available fault current.
[10] Wire range listed for QOM circuit breaker kits is the wire range of that circuit breaker. To find out maximum wire size permitted in a particular load center per UL, see Main Wire Size in that
load center table.