Technical Data Bulletin
Table Of Contents
- Section 1 Load Centers
- EZ Selector - Selection Assistance
- QO™ Miniature Circuit Breakers
- QO™ Load Centers
- Homeline™ Miniature Circuit Breakers
- Homeline™ Load Centers
- QO/Homeline Load Center Value Packs and Accessories
- QO/Homeline Load Center Dimensions
- Combination Service Entrance Devices
- RC/QC Solar Ready CSEDs
- Homeline Solar Ready PoN CSEDs
- Wiser Energy™
- Enclosed Devices
- Servicepak™ Power Outlet Panels
© 2020 Schneider Electric
All Rights Reserved
10/30/2020
1-19
www.se.com/us
Homeline Plug-On Circuit Breakers Homeline™ Miniature Circuit Breakers
Class 1170 / Refer to Catalog 1100CT0501
Homeline Dual Function Circuit Breaker (HOM-DF)
HOM 1P DF
Plug-on Neutral
HOM 1P DF
Pigtail
Homeline Combination Arc Fault and Ground Fault Circuit Interrupters (Dual Function)—
Provide overload and short circuit protection, plus arc fault and ground fault protection in
a single device in accordance with the NEC, UL1699 and UL943.
Table 1.43: HOM-DF Circuit Breakers
Circuit Breaker Type
Ampere
Rating
Poles
120 Vac
Cat. No.
Combination Arc-Fault and Ground Fault Circuit
Interrupter with Pigtail Neutral
15 A 1
HOM115DF [6]
20 A 1
HOM120DF [6]
Plug-On Neutral Combination
Arc-Fault and Ground Fault
Circuit Interrupter
15 A 1
HOM115PDF [6]
20 A 1
HOM120PDF [6]
Homeline Equipment Protection Device (HOM-EPD)
Homeline Equipment Protection Device—Circuit Breakers with 30 mA Equipment
Ground Fault Protection (UL Listed).
Table 1.44: HOM-EPD Circuit Breakers
Amperes
1P—120 Vac
2P—120/240 Vac
Common Trip
15 A HOM115EPD HOM215EPD
20 A HOM120EPD HOM220EPD
25 A — HOM225EPD
30 A — HOM230EPD
40 A — HOM240EPD
50 A — HOM250EPD
Homeline Tandem and Quad Tandem Circuit Breakers (HOMT)
Table 1.45: HOMT Tandem Circuit Breakers
Ampere Rating [7]
AIR
1P Tandem—120/240 Vac (One Space Required)
15 and 15 A 10 kA
HOMT1515 [6]
15 and 20 A 10 kA
HOMT1520 [6]
20 and 20 A 10 kA
HOMT2020 [6]
30 and 15 A 10 kA
HOMT3015 [6]
30 and 20 A 10 kA
HOMT3020 [6]
HOMT Quad
Circuit Breaker
2 Spaces Required
Table 1.46: HOMT Quad Tandem 1P Circuit Breakers
Ampere Rating [7]
AIR
2P Tandem—120/240 Vac
(Two Spaces Required)
1P 2P
(2) 15 A
15 A 10 kA HOMT1515215
(2) 15 A
20 A 10 kA HOMT1515220
(2) 15 A
25 A 10 kA HOMT1515225
(2) 15 A
30 A 10 kA HOMT1515230
(2) 15 A
40 A 10 kA HOMT1515240
(2) 15 A
50 A 10 kA HOMT1515250
(2) 20 A
20 A 10 kA HOMT2020220
(2) 20 A
25 A 10 kA HOMT2020225
(2) 20 A
30 A 10 kA HOMT2020230
(2) 20 A
40 A 10 kA HOMT2020240
(2) 20 A
50 A 10 kA HOMT2020250
NOTE: Typical catalog no. (e.g. HOMT 1515230) represents two 1P, outer poles (two
15 A 1P CBs) and one 2P inner circuit breaker with common trip (one 30 A 2P CB).
Table 1.47: HOMT Quad Tandem 2P Circuit Breakers
Ampere Rating [7]
AIR
(2) 2P Tandem—120/240 Vac
(Two Spaces Required)
2P 2P
15 A 15 A 10 kA HOMT215215
15 A 20 A 10 kA HOMT215220
15 A 25 A 10 kA HOMT215225
15 A 30 A 10 kA HOMT215230
15 A 40 A 10 kA HOMT215240
15 A 50 A 10 kA HOMT215250
20 A 20 A 10 kA HOMT220220
20 A 25 A 10 kA HOMT220225
20 A 30 A 10 kA HOMT220230
20 A 40 A 10 kA HOMT220240
20 A 50 A 10 kA HOMT220250
25 A 25A 10 kA HOMT225225
25 A 30 A 10 kA HOMT225230
25 A 40 A 10 kA HOMT225240
25 A 50 A 10 kA HOMT225250
30 A 30 A 10 kA HOMT230230
30 A 40 A 10 kA HOMT230240
30 A 50 A 10 kA HOMT230250
NOTE: Typical catalog no. (i.e. HOMT215230) represents two 2P; outer poles (one
15 A 2P with common trip) and inner poles (one 30 A 2P with common trip).
1
LOAD CENTERS
[6] UL Listed as HACR type for use with air conditioning, heating and refrigeration equipment haing motor group combinations and marked for use with HACR type circuit breakers.
[7] 15– 20 A tandem or quad tandem circuit breakers are suitable for use with 60
o
C or 75
o
C conductors. 25– 50 A tandem or quad tandem circuit breakers are suitable for use with 75
o
C
conductors only.