SPECIFICATIONS
Powerlink 3500G4 Controller
Operating Environment (external
panelboard ambient)
Temp.: 23°F to 104°F (-5°C to 40°C)
RH: 95%, noncondensing
Storage Environment Temp.: -F to 185°F (-20°C to 85°C)
RH: 95%, noncondensing
Standards UL Listed 916, Energy Management Equip.
FCC: Part 15, Class A
NEC: Class 1 and Class 2 Control Circuits
ESD Immunity: IEC 1000, level 4
RF Susceptibility: IEC 1000, level 3
Electrical Fast Transient Susceptibility: IEC 1000, level 3
Electrical Surge Susceptibility: IEC 1000, level 4 (power line)
Electrical Fast Transient Susceptibility: IEC 1000, level 3
(interconnection lines)
Ordering
Description Catalog Number
Powerlink NF3500G4 Controller NF3500G4
Typical Powerlink NF3500G4 Network Diagram
Features
INPUT TERMINALS*
2-wire 16
2-wire with status feedback** 8
3-wire
8
Analog 4
INPUT TYPES
2-wire normally open (NO) or normally closed (NC)
2-wire NO or NC, w/auto blink notification
2-wire maintained toggle
2-wire momentary toggle
2-wire momentary ON or momentary OFF
3-wire momentary
Input timers (1 sec - 18 hr)
Input synchronization
Sentry Switch support
ON delay/OFF delay
0-5V (Analog)
0-10V (Analog)
4-20mA (Analog)
TIME SCHEDULER
Independent schedules 64
ON-OFF periods/schedule 999
Special event/holiday periods 64
7-day 24-hr repeating schedule
Automatic daylight savings
Sunrise/sunset with offsets
Network time sync (TCP connection required)
NETWORK VARIABLES
Communications inputs (net. accessible) 256
Remote sources (per controller) 128
Maximum subscriptions 256
ZONES
Maximum number 256
Maximum number of sources per zone
4
Max. number of remotely operated circuit
breakers (per subnet)
168
Configurable source logic
Blink notice
ON-time / OFF-time / Delay-OFF
NETWORKING
RS-232 port
RS-485 port
Ethernet (100BaseT port)
PROTOCOLS
Modbus ASCII/RTU, Modbus TCP
BACnet/IP, BACnet MS/TP
DMX512
C-Bus
FRONT PANEL
Backlit LCD display
Password or front panel disable
MEMORY
Non-volatile memory - programs and configuration
Flash memory for firmware upgrade
VIEWING OPTIONS
Event log
Breaker Strike Counter and Breaker ON-time
Alarm viewing via Event Log
Alarm viewing via e-mail
Web-based set up, control, and status monitoring
*Terminals accept 24-18 AWG conductors
** 7.5 mA maximum load per input terminal