LUB12
Main
Range
TeSys
Product name
TeSys U
Device short name
LUB
Product or component type
Non reversing power base
Device application
Motor
Poles description
3P
Suitability for isolation
Yes
[Ith] conventional free air thermal
current
12 A
Utilisation category
AC
-41
AC
-43
AC
-44
[Uc] control circuit voltage
110...220 V DC
110...240 V AC 50/60 Hz
24 V AC 50/60 Hz
24 V DC
48 V AC 50/60 Hz
48...72 V DC
Complementary
Auxiliary contact composition
1 NO + 1 NC
Auxiliary contacts type
Type linked contacts (1 NO + 1 NC) conforming to IEC 60947-4-1
Type mirror contact (1 NC) state of the power conforming to draft IEC 60947-1
System Voltage
230 V
440 V
500 V
690 V
Network frequency
40...60 Hz
[Ie] rated operational current
12 A at <= 440 V
12 A at 500 V
9 A at 690 V
[Ics] rated service breaking capacity
10 kA 500 V
4 kA 690 V
50 kA 230 V
50 kA 440 V
Typical current consumption
130 mA at 24 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD
140 mA at 24 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD
150 mA at 24 V DC I maximum while closing with LUCM
280 mA at 110...220 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD
280 mA at 110...240 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD
280 mA at 48...72 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD
280 mA at 48...72 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD
35 mA at 110...220 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD
35 mA at 110...240 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD
35 mA at 48...72 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD
35 mA at 48...72 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD
60 mA at 24 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD
70 mA at 24 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD
70 mA at 24 V DC I rms sealed with LUCM
Safety reliability level
B10d 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-
1
Operating time
35 ms opening with LUCA, LUCB, LUCC, LUCD, LUCM control circuit
50 ms at >= 72 V closing with LUCA, LUCB, LUCC, LUCD control circuit
60 ms at 48 V closing with LUCA, LUCB, LUCC, LUCD control circuit
70 ms at 24 V closing with LUCA, LUCB, LUCC, LUCD control circuit
75 ms closing with LUCM control circuit
Mechanical durability
15000000 cycles
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.