Submittal Sheet
[Ui] rated insulation voltage
690 V power circuit conforming to IEC 60947-4-1
600 V power circuit conforming to UL 508
690 V signalling circuit conforming to IEC 60947-4-1
690 V signalling circuit conforming to IEC 60947-5-1
600 V signalling circuit conforming to UL 508
600 V power circuit conforming to CSA C22.2 No 14
600 V signalling circuit conforming to CSA C22.2 No 14
Insulation resistance
> 10 MOhm signalling circuit
Inrush power in VA
30 VA at 68 °F (20 °C)
Hold-in power consumption in VA
4.5 VA at 68 °F (20 °C)
Heat dissipation
1.3 W
Control circuit voltage limits
0.2...0.75 Uc at <= 122 °F (50 °C) drop-out
0.8...1.15 Uc at <= 122 °F (50 °C) operational
Connections - terminals
Screw clamp terminals 1 cable(s) 0...0.01 in² (1.5...4 mm²) - cable stiffness: solid
Screw clamp terminals 1 cable(s) 0...0.01 in² (0.75...4 mm²) - cable stiffness: flexible
- without cable end
Screw clamp terminals 1 cable(s) 0...0 in² (0.34...2.5 mm²) - cable stiffness: flexible -
with cable end
Screw clamp terminals 2 cable(s) 0...0.01 in² (1.5...4 mm²) - cable stiffness: solid
Screw clamp terminals 2 cable(s) 0...0.01 in² (0.75...4 mm²) - cable stiffness: flexible
- without cable end
Screw clamp terminals 2 cable(s) 0...0 in² (0.34...1.5 mm²) - cable stiffness: flexible -
with cable end
Operating rate
3600 cyc/h
Auxiliary contacts type
Type instantaneous (1 NO)
Signalling circuit frequency
<= 400 Hz
Minimum switching current
5 mA signalling circuit
Minimum switching voltage
17 V signalling circuit
Mounting support
Plate
Rail
Tightening torque
11.5 lbf.in (1.3 N.m) - on screw clamp terminals - with screwdriver Philips No 2
11.5 lbf.in (1.3 N.m) - on screw clamp terminals - with screwdriver flat Ø 6 mm
Operating time
10...20 ms coil de-energisation and NO opening
10...20 ms coil energisation and NO closing
Safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO
13849-1
Non overlap distance
0.02 in (0.5 mm)
Mechanical durability
10 Mcycles
Electrical durability
1.3 Mcycles 6 A AC-3 at Ue <= 440 V
Mechanical robustness
Shocks contactor closed, on X axis 10 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Y axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Z axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on X axis 6 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Y axis 10 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Z axis 10 Gn for 11 ms IEC 60068-2-27
Vibrations contactor closed 4 Gn, 5...300 Hz IEC 60068-2-6
Vibrations contactor opened 2 Gn, 5...300 Hz IEC 60068-2-6
Height
2.28 in (58 mm)
Width
1.77 in (45 mm)
Depth
2.24 in (57 mm)
Product weight
0.4 lb(US) (0.18 kg)
Environment
standards
BS 5424
IEC 60947
NF C 63-110
VDE 0660
product certifications
CSA
UL
IP degree of protection
IP2x conforming to VDE 0106
protective treatment
TC conforming to IEC 60068
TC conforming to DIN 50016
ambient air temperature for operation
-13...122 °F (-25...50 °C)
ambient air temperature for storage
-58...176 °F (-50...80 °C)
2 / 3