Submittal Sheet
Product datasheet
Characteristics
LC1K0610B7
Main
Range
TeSys
Product or component type
Contactor
Product name
TeSys K
Device short name
LC1K
Device application
Control
Contactor application
Motor control
Complementary
Utilisation category
AC
-3
AC
-4
Poles description
3P
Pole contact composition
3 NO
System Voltage
690 V AC 50/60 Hz power circuit
<= 690 V AC 50/60 Hz signalling circuit
[Ie] rated operational current
6 A at <= 440 V AC AC
-3 power circuit
Control circuit type
AC 50/60 Hz
[Uc] control circuit voltage
24 V AC 50/60 Hz
Motor power kW
1.5 kW at 220...230 V AC 50/60 Hz AC-3
2.2 kW at 380...415 V AC 50/60 Hz AC-3
1.5 kW at 400 V AC 50/60 Hz AC-4
3 kW at 660...690 V AC 50/60 Hz AC-3
3 kW at 440 V AC 50/60 Hz AC-3
3 kW at 480 V AC 50/60 Hz AC-3
3 kW at 500...600 V AC 50/60 Hz AC-3
Auxiliary contact composition
1 NO
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
[Ith] conventional free air thermal current
20 A at <= 122 °F (50 °C) power circuit
10 A at <= 122 °F (50 °C) signalling circuit
Irms rated making capacity
110 A AC power circuit conforming to NF C 63-110
110 A AC power circuit conforming to IEC 60947
110 A AC signalling circuit conforming to IEC 60947
Rated breaking capacity
110 A at 415 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
110 A at 220...230 V conforming to IEC 60947
110 A at 380...400 V conforming to IEC 60947
70 A at 660...690 V conforming to IEC 60947
[Icw] rated short-time withstand current
90 A <= 122 °F (50 °C) 1 s power circuit
85 A <= 122 °F (50 °C) 5 s power circuit
80 A <= 122 °F (50 °C) 10 s power circuit
60 A <= 122 °F (50 °C) 30 s power circuit
45 A <= 122 °F (50 °C) 1 min power circuit
40 A <= 122 °F (50 °C) 3 min power circuit
80 A 1 s signalling circuit
90 A 500 ms signalling circuit
110 A 100 ms signalling circuit
20 A <= 50 °C >= 15 min power circuit
Associated fuse rating
25 A gG at <= 440 V power circuit
25 A aM power circuit
10 A gG signalling circuit conforming to IEC 60947
10 A gG signalling circuit conforming to VDE 0660
Average impedance
3 mOhm at 50 Hz - Ith 20 A power circuit
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
1 / 3