Submittal Sheet
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.3...0.6 Uc drop-out at 140 °F (60 °C), AC 50/60 Hz
0.8...1.1 Uc operational at 140 °F (60 °C), AC 50 Hz
0.85...1.1 Uc operational at 140 °F (60 °C), AC 60 Hz
Inrush power in VA
140 VA at 68 °F (20 °C) (cos ϕ 0.75) 60 Hz
160 VA at 68 °F (20 °C) (cos ϕ 0.75) 50 Hz
Hold-in power consumption in VA
13 VA at 68 °F (20 °C) (cos ϕ 0.3) 60 Hz
15 VA at 68 °F (20 °C) (cos ϕ 0.3) 50 Hz
Heat dissipation
4...5 W at 50/60 Hz
Auxiliary contacts type
Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Type mirror contact (1 NC) conforming to IEC 60947-4-1
Signalling circuit frequency
25...400 Hz
Minimum switching current
5 mA signalling circuit
Minimum switching voltage
17 V signalling circuit
Non-overlap time
1.5 ms on de-energisation (between NC and NO contact)
1.5 ms on energisation (between NC and NO contact)
Insulation resistance
> 10 MOhm signalling circuit
Environment
IP degree of protection
IP20 front face conforming to IEC 60529
protective treatment
TH conforming to IEC 60068-2-30
pollution degree
3
ambient air temperature for operation
23...140 °F (-5...60 °C)
ambient air temperature for storage
-76...176 °F (-60...80 °C)
permissible ambient air temperature around the device
-40...158 °F (-40...70 °C) at Uc
operating altitude
9842.52 ft (3000 m) without derating in temperature
fire resistance
1562 °F (850 °C) conforming to IEC 60695-2-1
flame retardance
V1 conforming to UL 94
mechanical robustness
Vibrations contactor open 2 Gn, 5...300 Hz
Vibrations contactor closed 4 Gn, 5...300 Hz
Shocks contactor open 10 Gn for 11 ms
Shocks contactor closed 15 Gn for 11 ms
height
4.8 in (122 mm)
width
2.17 in (55 mm)
depth
4.72 in (120 mm)
product weight
1.9 lb(US) (0.86 kg)
Offer Sustainability
Green Premium product
Green Premium product
Compliant - since 0501 - Schneider Electric declaration
of conformity
Compliant - since 0501 - Schneider Electric declaration of conformity
Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Available
Available
Available
Available
WARNING: This product can expose you to chemicals
including:
WARNING: This product can expose you to chemicals including:
Antimony oxide & Antimony trioxide, which is known to
the State of California to cause cancer.
Antimony oxide & Antimony trioxide, which is known to the State of California to cause
cancer.
For more information go to www.p65warnings.ca.gov
For more information go to www.p65warnings.ca.gov
Contractual warranty
Warranty period
18 months
3 / 3