LC1D65AG7
Main
Range
TeSys
Product name
TeSys D
Product or component type
Contactor
Device short name
LC1D
Contactor application
Motor control
Resistive load
Utilisation category
AC
-1
AC
-3
AC
-4
Poles description
3P
Pole contact composition
3 NO
System Voltage
<= 690 V AC 25...400 Hz power circuit
<= 300 V DC power circuit
[Ie] rated operational current
80 A (<= 140 °F (60 °C)) at <= 440 V AC AC-1
power circuit
65 A (<= 140 °F (60 °C)) at <= 440 V AC AC-3
power circuit
Motor power kW
11 kW at 400 V AC 50/60 Hz AC-4
30 kW at 380...400 V AC 50/60 Hz AC-3
37 kW at 500 V AC 50/60 Hz AC-3
37 kW at 660...690 V AC 50/60 Hz AC-3
18.5 kW at 220...230 V AC 50/60 Hz AC-3
Motor power hp
40 hp at 460/480 V AC 50/60 Hz 3 phases motors
5 hp at 115 V AC 50/60 Hz 1 phase motors
10 hp at 230/240 V AC 50/60 Hz 1 phase motors
20 hp at 200/208 V AC 50/60 Hz 3 phases motors
20 hp at 230/240 V AC 50/60 Hz 3 phases motors
50 hp at 575/600 V AC 50/60 Hz 3 phases motors
Control circuit type
AC 50/60 Hz
[Uc] control circuit voltage
120 V AC 50/60 Hz
Auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand
voltage
Conforming to IEC 60947
Overvoltage category
III
[Ith] conventional free air thermal
current
80 A at <= 140 °F (60 °C) power circuit
10 A at <= 140 °F (60 °C) signalling circuit
Irms rated making capacity
1000 A at 440 V power circuit conforming to IEC
60947
140 A AC signalling circuit conforming to IEC
60947-5-1
250 A DC signalling circuit conforming to IEC
60947-5-1
Rated breaking capacity
1000 A at 440 V power circuit conforming to IEC
60947
[Icw] rated short-time withstand
current
100 A 1 s signalling circuit
120 A 500 ms signalling circuit
140 A 100 ms signalling circuit
520 A <= 104 °F (40 °C) 10 s power circuit
900 A <= 104 °F (40 °C) 1 s power circuit
110 A <= 104 °F (40 °C) 10 min power circuit
260 A <= 104 °F (40 °C) 1 min power circuit
Associated fuse rating
125 A gG at <= 690 V coordination type 1 power
circuit
125 A gG at <= 690 V coordination type 2 power
circuit
10 A gG signalling circuit conforming to IEC
60947-5-1
Average impedance
1.5 mOhm at 50 Hz - Ith 80 A power circuit
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
1 / 3