Product Overview

3
[Ui] rated insulation
voltage
600 V for signalling circuit certifications UL
600 V for signalling circuit certifications CSA
690 V for signalling circuit conforming to IEC 60947-1
600 V for power circuit certifications UL
600 V for power circuit certifications CSA
690 V for power circuit conforming to IEC 60947-4-1
Electrical durability 1 Mcycles 32 A AC-1 at Ue <= 440 V
1.65 Mcycles 18 A AC-3 at Ue <= 440 V
Power dissipation per
pole
0.8 W AC-3
2.5 W AC-1
Protective cover With
Mounting support Plate
Rail
Standards EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
CSA C22.2 No 14
Product certifications BV
CCC
CSA
DNV
GL
GOST
RINA
UL
LROS
Connections - terminals Power circuit: screw clamp terminals 2 cable(s) 0...0.01
in² (1.5...6 mm²) - cable stiffness: solid - without cable end
Power circuit: screw clamp terminals 1 cable(s) 0...0.01
in² (1.5...6 mm²) - cable stiffness: solid - without cable end
Power circuit: screw clamp terminals 2 cable(s) 0...0.01
in² (1...4 mm²) - cable stiffness: flexible - with cable end
Power circuit: screw clamp terminals 1 cable(s) 0...0.01
in² (1...6 mm²) - cable stiffness: flexible - with cable end
Power circuit: screw clamp terminals 2 cable(s) 0...0.01
in² (1.5...6 mm²) - cable stiffness: flexible - without cable
end
Power circuit: screw clamp terminals 1 cable(s) 0...0.01
in² (1.5...6 mm²) - cable stiffness: flexible - without cable
end
Control circuit: screw clamp terminals 2 cable(s) 0...0.01
in² (1...4 mm²) - cable stiffness: solid - without cable end
Control circuit: screw clamp terminals 1 cable(s) 0...0.01
in² (1...4 mm²) - cable stiffness: solid - without cable end
Control circuit: screw clamp terminals 2 cable(s) 0...0 in²
(1...2.5 mm²) - cable stiffness: flexible - with cable end
Control circuit: screw clamp terminals 1 cable(s) 0...0.01
in² (1...4 mm²) - cable stiffness: flexible - with cable end
Control circuit: screw clamp terminals 2 cable(s) 0...0.01
in² (1...4 mm²) - cable stiffness: flexible - without cable
end
Control circuit: screw clamp terminals 1 cable(s) 0...0.01
in² (1...4 mm²) - cable stiffness: flexible - without cable
end
Tightening torque Control circuit: 15.04 lbf.in (1.7 N.m) - on screw clamp
terminals - with screwdriver Philips No 2
Control circuit: 15.04 lbf.in (1.7 N.m) - on screw clamp
terminals - with screwdriver flat Ø 6 mm
Power circuit: 15.04 lbf.in (1.7 N.m) - on screw clamp
terminals - with screwdriver Philips No 2
Power circuit: 15.04 lbf.in (1.7 N.m) - on screw clamp
terminals - with screwdriver flat Ø 6 mm
Operating time 4...19 ms opening
12...22 ms closing
Safety reliability level B10d = 20000000 cycles contactor with mechanical load
conforming to EN/ISO 13849-1
B10d = 1369863 cycles contactor with nominal load
conforming to EN/ISO 13849-1