Product Overview

3
[Ui] rated insulation
voltage
1000 V for power circuit conforming to IEC 60947-4-1
600 V for signalling circuit certifications UL
600 V for signalling circuit certifications CSA
690 V for signalling circuit conforming to IEC 60947-1
600 V for power circuit certifications UL
600 V for power circuit certifications CSA
Electrical durability 1 Mcycles 200 A AC-1 at Ue <= 440 V
0.85 Mcycles 150 A AC-3 at Ue <= 440 V
Power dissipation per
pole
AC-3
AC-1
Protective cover With
Mounting support Plate
Rail
Standards EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
CSA C22.2 No 14
Product certifications BV
CCC
CSA
DNV
GL
GOST
RINA
UL
LROS
Connections - terminals Power circuit: connector 2 cable(s) 0.02...0.08 in² (10...50
mm²) - cable stiffness: solid - without cable end
Power circuit: connector 1 cable(s) 0.02...0.19 in²
(10...120 mm²) - cable stiffness: solid - without cable end
Power circuit: connector 2 cable(s) 0.02...0.08 in² (10...50
mm²) - cable stiffness: flexible - with cable end
Power circuit: connector 1 cable(s) 0.02...0.19 in²
(10...120 mm²) - cable stiffness: flexible - with cable end
Power circuit: connector 2 cable(s) 0.02...0.08 in² (10...50
mm²) - cable stiffness: flexible - without cable end
Power circuit: connector 1 cable(s) 0.02...0.19 in²
(10...120 mm²) - cable stiffness: flexible - without cable
end
Control circuit: screw clamp terminals 2 cable(s) 0...0 in²
(1...2.5 mm²) - cable stiffness: solid - without cable end
Control circuit: screw clamp terminals 1 cable(s) 0...0 in²
(1...2.5 mm²) - cable stiffness: solid - without cable end
Control circuit: screw clamp terminals 2 cable(s) 0...0 in²
(1...2.5 mm²) - cable stiffness: flexible - without cable end
Control circuit: screw clamp terminals 1 cable(s) 0...0 in²
(1...2.5 mm²) - cable stiffness: flexible - without cable end
Control circuit: screw clamp terminals 1 cable(s) 0...0 in²
(1...2.5 mm²) - cable stiffness: flexible - with cable end
Control circuit: screw clamp terminals 2 cable(s) 0...0 in²
(1...2.5 mm²) - cable stiffness: flexible - with cable end
Tightening torque Power circuit: 106.19 lbf.in (12 N.m) - on connector
hexagonal 0.16 in (4 mm)
Control circuit: 10.62 lbf.in (1.2 N.m) - on screw clamp
terminals - with screwdriver Philips No 2
Control circuit: 10.62 lbf.in (1.2 N.m) - on screw clamp
terminals - with screwdriver flat Ø 6 mm
Operating time 40...75 ms opening
20...35 ms closing
Safety reliability level B10d = 20000000 cycles contactor with mechanical load
conforming to EN/ISO 13849-1
B10d = 1369863 cycles contactor with nominal load
conforming to EN/ISO 13849-1
Mechanical durability 8 Mcycles
Operating rate 1200 cyc/h at <= 140 °F (60 °C)