Submittal

Overvoltage category III
[Ith] conventional free air thermal
current
10A 140°F (60°C) signalling circuit
25A 140°F (60°C) power circuit
Irms rated making capacity 250A 440 V power circuit IEC 60947
140A AC signalling circuit IEC 60947-5-1
250A DC signalling circuit IEC 60947-5-1
Rated breaking capacity 250A 440 V power circuit IEC 60947
[Icw] rated short-time withstand current 30A 104°F (40°C) - 10 min power circuit
61A 104°F (40°C) - 1 min power circuit
105A 104°F (40°C) - 10 s power circuit
210A 104°F (40°C) - 1 s power circuit
100A - 1 s signalling circuit
120A - 500 ms signalling circuit
140A - 100 ms signalling circuit
Associated fuse rating 10A gG signalling circuit IEC 60947-5-1
40A gG <= 690 V type 1 power circuit
25A gG <= 690 V type 2 power circuit
Average impedance 2.5mOhm - Ith 25A 50 Hz power circuit
[Ui] rated insulation voltage Power circuit 690V IEC 60947-4-1
Power circuit 600V CSA
Power circuit 600V UL
Signalling circuit 690V IEC 60947-1
Signalling circuit 600V CSA
Signalling circuit 600V UL
Electrical durability 2Mcycles 12A AC-3 <= 440 V
0.8Mcycles 25A AC-1 <= 440 V
Power dissipation per pole 1.56W AC-1
0.36W AC-3
Safety cover With
Interlocking type Mechanical
Mounting support Rail
Plate
Standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
Product certifications RINA
CCC
GL
BV
CSA
DNV
UL
LROS (Lloyds register of shipping)
GOST
Connections - terminals Power circuit screw clamp terminals 1 0.00…0.01in² (1…4mm²)flexible without cable end
Power circuit screw clamp terminals 2 0.00…0.01in² (1…4mm²)flexible without cable end
Power circuit screw clamp terminals 1 0.00…0.01in² (1…4mm²)flexible with cable end
Power circuit screw clamp terminals 2 0.00…0.00in² (1…2.5mm²)flexible with cable end
Power circuit screw clamp terminals 1 0.00…0.01in² (1…4mm²)solid without cable end
Power circuit screw clamp terminals 2 0.00…0.01in² (1…4mm²)solid without cable end
Control circuit screw clamp terminals 1 0.00…0.01in² (1…4mm²)flexible without cable end
Control circuit screw clamp terminals 2 0.00…0.01in² (1…4mm²)flexible without cable end
Control circuit screw clamp terminals 1 0.00…0.01in² (1…4mm²)flexible with cable end
Control circuit screw clamp terminals 2 0.00…0.00in² (1…2.5mm²)flexible with cable end
Control circuit screw clamp terminals 1 0.00…0.01in² (1…4mm²)solid without cable end
Control circuit screw clamp terminals 2 0.00…0.01in² (1…4mm²)solid without cable end
Tightening torque Power circuit 15.05lbf.in (1.7N.m) screw clamp terminals flat Ø 6 mm
Power circuit 15.05lbf.in (1.7N.m) screw clamp terminals Philips No 2
Control circuit 15.05lbf.in (1.7N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05lbf.in (1.7N.m) screw clamp terminals Philips No 2
Operating time 12...22 ms closing
4...19 ms opening
Safety reliability level B10d = 1369863cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000cycles contactor with mechanical load EN/ISO 13849-1
2