TeSys™ D Contactors and Overload Relays Contactors and Overload Relays
Refer to Catalog MKTED210011EN
TeSys™ D Reversing Contactors
Each 3-pole device is prewired with line and load side power wiring for reversing
applications. Each 4-pole device is prewired with load side power wiring.
Table 18.27: TeSys D Mechanically-Interlocked Reversing Contactors
Maximum Horsepower Ratings Maximum Current (A)
Continuous
Current
Rating (A)
No. of
N.O.
Power
Poles
Built In
Auxiliary
Contacts
(per
contactor)
Catalog
Number
[48]
Single-Phase
Three-Phase
Inductive
AC3
Resistive
AC1
115 V 230 V 200 V 230 V 460 V 575 V N.O. N.C.
LC2D25
1/3 1 2 2 5 7.5 9
20 25
3 1 1
LC2D09 [49]
4 1 1 LC2DT20
1/2 2 3 3 7.5 10 12
25 25
3 1 1
LC2D12 [49]
4 1 1 LC2DT25
1 3 5 5 10 15 18
32 32
3 1 1
LC2D18 [49]
4 1 1 LC2DT32
2 3 7.5 7.5 15 20 25
40 40
3 1 1
LC2D25 [49]
4 1 1 LC2DT40
2 5 10 10 20 25 32
50 50
3 1 1
LC2D32 [49]
2 5 10 10 20 25 38 3 1 1
LC2D38 [49]
3 5 10 10 30 30 40
60 60
3 1 1 LC2D40A
4
[50]
3 7.5 15 15 40 40 50
80
70 3 1 1 LC2D50A
5 10 20 20 40 50 65
80
3 1 1 LC2D65A
4
[50]
7.5 15 25 30 60 60 80
125 110
3 1 1 LC2D80
4
[50]
7.5 15 25 30 60 60 95 3 1 1 LC2D95
30 40 75 100 115
200 160
3 1 1
LC2D115[51]
4
LC2D115004
[51]
40 50 100 125 150 3 1 1
LC2D150 [51]
E164862
CCN NLDX
LR43364
Class 3211 04
TeSys D contactor accessories: page 18-14
TeSys D replacement coils: page 18-52
TeSys D dimensions: page 18-60 to page 18-68
TeSys™ D Capacitor Contactors
LC1DFK LC1DGK LC1DTK LC1DWK
Table 18.28: TeSys D Capacitor Contactors
Maximum Operational Power, kVAR Instantaneous Auxiliary Contacts
Catalog
Number [52]
Three-Phase
N.O. N.C.
230 V 460 V 575 V
6 12.5 15 1 2 LC1DFK
8 16.7 20 1 2 LC1DGK
10 20 25 1 2 LC1DLK
12.5 25 30 1 2 LC1DMK
16.5 33.3 40 1 2 LC1DPK
20 40 50 1 2 LC1DTK
30 60 80 1 2 LC1DWK12
Table 18.29: Coil Voltage Codes for TeSys D Capacitor Contactor (50/60 Hz)
Voltage 24 48 110 120 220 230 240 380 400 415 440
Coil Code B7 E7 F7 G7 M7 P7 U7 Q7 V7 N7 R7
18
CONTACTORS AND STARTERS-IEC
[48] Includes mechanical interlock without electrical contacts. Installer to complete wiring for electronically interlocking contactor operating coils by using a N.C. auxiliary contact integrated in the
contactor or optional LADN or LAD8N auxiliary contact block.
[49] For LC2D09–LC2D38, electrical interlock can be included by adding a V to the end of the catalog number (for example LC2D09B7V).
[50] For these items, order two non-reversing contactors and one mechanical interlock separately. See page 18-7 for selection.
[51] Includes mechanical interlock (LA9D11502) with prewired electrical contacts for interlocking contactor operating coils.
[52] Complete the catalog number with the voltage code from Table 18.29 (for example, LC1DFKG7).