TeSys™ D Overload Relays
Table 18.24: TeSys D Overload Relays—Ambient Compensated, Bimetallic, Direct Mounting
Current Setting
Range (A)
For Direct Mounting
to LC1D/LC2D...
Class 10 with
Single-Phase
Sensitivity
Class 10 without
Single-Phase
Sensitivity
Class 20 with
Single-Phase
Sensitivity
Class 20 without
Single-Phase
Sensitivity
0.10–0.16
D09–D38
LRD01 LR3D01
0.16–0.25 LRD02 LR3D02
0.25–0.40 LRD03 LR3D03
0.40–0.63 LRD04 LR3D04 LRD04L LR3D04L
0.63–1 LRD05 LR3D05 LRD05L LR3D05L
1–1.6 LRD06 LR3D06 LRD06L LR3D06L
1.6–2.5 LRD07 LR3D07 LRD07L LR3D07L
2.5–4 LRD08 LR3D08 LRD08L LR3D08L
4–6 LRD10 LR3D10 LRD10L LR3D10L
5.5–8 LRD12 LR3D12 LRD12L LR3D12L
7–10 LRD14 LR3D14 LRD14L LR3D14L
9–13 D12–D38 LRD16 LR3D16 LRD16L LR3D21L
12–18
D18–D38
LRD21 LR3D21 LRD21L LR3D21L
16–24 LRD22 LR3D22
17–24 LRD22L LR3D22L
23–32 D25–D38 LRD32 LR3D32 LRD32L LR3D32L
30–38 D32–D38 LRD35 LR3D35
9-13 D40A–D65A LRD313 LR3D313 LRD313L
12-18 D40A–D65A LRD318 LR3D318 LRD318L
17-25 D40A–D65A LRD325 LR3D325 LRD325L
23-32 D40A–D65A LRD332 LR3D332 LRD332L
30-40 D40A–D65A LRD340 LR3D340 LRD340L
37-50 D40A–D65A LRD350 LR3D350 LRD350L
48-65 D40A–D65A LRD365 LR3D365 LRD365L
17-25 D40–D95 LRD3322 LR3D3322 LR2D3522 LR3D3522
23-32
D40–D95 [47]
LRD3353 LR3D3353 LR2D3553 LR3D3553
30-40
D40–D95 [47]
LRD3355 LR3D3355 LR2D3555 LR3D3555
37-50
D50–D95 [47]
LRD3357 LR3D3357 LR2D3557 LR3D3557
48-65
D50–D95 [47]
LRD3359 LR3D3359 LR2D3559 LR3D3559
55–70 D65–D95 LRD3361 LR3D3361 LR2D3561 LR3D3561
63–80 D65–D95 LRD3363 LR3D3363 LR2D3563 LR3D3563
80–104 D95 LRD3365
80–104 D115–D150 LRD4365
95–120 D115–D150 LRD4367
110–140 D150 LRD4369
Table 18.25: TeSys LR9D Electronic Overload Relays
Current Setting Range (A)
For Direct Mounting Beneath Contactor LC1D/
LC2D
Class 5/10/20/30
Selectable
0.1–0.5 D09–D38 LR9D01
0.4–2 D09–D38 LR9D02
1.6–8 D09–D38 LR9D08
6.4–32 D09–D38 LR9D32
22–110
N/A (Separate Mounting Only)
LR9D110S
Table 18.26: TeSys D Overload Relays—Solid State
Current Setting
Range (A)
For Direct Mounting Beneath
Contactor LC1
Class 10 Class 20
Class 10/20
Selectable
60–100 D115–D150 LR9D5367 LR9D5567 LR9D67
90–150 D115–D150 LR9D5369 LR9D5569 LR9D69
TeSys D contactor accessories: page 18-14
TeSys D overload relay accessories: page 18-21