TeSys™ GV Manual Starters and Protectors
Dimensions
Refer to Catalog 2520CT0001
TeSys GV7 Manual Starter and Protector Dimensions
Table 18.214: TeSys GV7 Manual Starter and Protector Dimensions
1 GV7R
Panel Mounting Flush Mounting Side by Side
1.38
35
1.38
35
1.38
35
=
4.92
125
=
2xØ0.24
2xØ6
= =
1.14
29
1.14
29
1.85
47
3.0
76
3.46
88
3.27
83
= =
4.25
108
4.25
108
= =
4.25
108
= =
Minimum Clearance
x1 x2
x1
x1
x2
x2
in. (mm) in. (mm)
Painted or insulated metal plate, insulation or insulated bar 0 (0) 1.18 (30)
Bare metal plate
U < 440 V
0.20 (5) 1.38 (35)
440 V < U < 600 V
0.39 (10) 1.38 (35)
U > 600 V
0.79 (20) 1.38 (35)
NOTE: Minimum distance between 2 units mounted side by side = 0.
Motor Controllers GV7R
Add-on Auxiliary Contacts, GV7AE11, GV7AB11
2/T1
4/T2
6/T3
1/L1
3/L2
5/L3
21 24
22
11 14
12
91 94
92
81 84
82
NOTE: A self-adhesive label, supplied with the contact, can be affixed to the front face of the starter to allow
personalized marking according to the function of the contact or contacts.
GV7AU●●● GV7AS●●●
GV7AD111, AD112
D1D4
C1C2
98
97
50 ms
98
97
50 ms
– KA1
2324
1314
– KA1
98
97
50 ms
– KM1
– KA1
A1A2
A1A2
B1
– KA1
2122
18
CONTACTORS AND STARTERS-IEC