Brochure

© 2019 Schneider Electric
All Rights Reserved
18-7
www.se.com/us
TeSys™ D Contactors and Overload Relays Contactors and Overload Relays
Refer to Catalog MKTED210011EN
TeSys™ D Non-Reversing Contactors
LC1D09 LC1D093 LC1D40A
LC1D115 LRD22 LRD3
Table 18.22: TeSys D Contactors—3 or 4 Pole, Screw Terminal Connections
Maximum Horsepower Ratings Maximum Current (A)
Continuous
Current
Rating (A)
No. of Poles
Instantaneous
Auxiliary
Contacts
Catalog
Number [40]
Single-Phase
Three-Phase
Inductive
AC3
Resistive
AC1
N.O. N.C. N.O. N.C.
115 V 230 V 200 V 230 V 460 V 575 V
1/3 1 2 2 5 7.5 9
20 25
3
0
1 1
LC1D09 [41][42][43]
4
LC1DT20 [41]
2 2
LC1D098 [41]
1/2 2 3 3 7.5 10 12
25 25
3
0
1 1
LC1D12 [41][42][43]
4
LC1DT25 [41]
2 2
LC1D128 [41]
1 3 5 5 10 15 18
32 32
3
0
1 1
LC1D18 [41][42]
4
LC1DT32 [41]
2 2
LC1D188 [41]
2 3 7.5 7.5 15 20 25
40 40
3
0
1 1
LC1D25 [41][41]
4
LC1DT40 [41]
2 2
LC1D258 [41]
2 5 10 10 20 25 32
50 50
3 0 1 1
LC1D32 [41][42]
2 5 10 10 20 25 38 3 0 1 1
LC1D38 [41][42]
3 5 10 10 30 30 40
60 60
3
0
1 1
LC1D40A [41]
4 0 0
LC1DT60A [41]
3 7.5 15 15 40 40 50
80
70 3
0 1 1
LC1D50A [41]
5 10 20 20 40 50 65
80
3
LC1D65A [41]
4 0 0 0
LC1DT80A [41]
7.5 15 25 30 60 60 80
125 110
3
0
1 1 LC1D80
4
0 0
LC1D80004 [44]
2 2
LC1D80008 [44]
7.5 15 25 30 60 60 95 3 0 1 1 LC1D95
30 40 75 100 115
200 160
3
0
1 1
LC1D115
40 50 100 125 150 3 LC1D150
4 0 0 LC1D115004
Table 18.23: TeSys D Coil Voltage Codes [45]
Contactor Hz 24 V 48 V 110 V 120 V 125 V 208 V 220 V 240 V 250 V 440 V 480 V 600 V
AC
D09–D150 50/60 B7 E7 F7 G7 LE7 M7 U7
T7 [46] X7 [46]
LC1D80–LC1D150
50 B5 E5 F5
M5 [46]
U5
60 B6 E6 F6 G6 L6 M6 U6 T6
X6 [46]
DC
D09-D38,
DT20-D258
Low Consumption
BL EL FL ML UL
D09–D150 BD ED FD GD MD UD RD
18
CONTACTORS AND STARTERS-IEC
[40] Complete the catalog number by adding the coil voltage code from Table 18.23 for example, LC1D09G7).
[41] For ring tongue versions of LC1D09–LC1D65A and LC1DT20–LC1DT80A, add 6 to the catalog number prior to adding the voltage code (for example, LC1D09G7 becomes LC1D096G7
and LC1D50AG7 becomes LC1D50A6G7).
[42] For spring terminals versions of LC1D09– LC1D65A, add 3 to the catalog number prior to adding the voltage code (for example, LC1D12G7 becomes LC1D123G7 and LC1D40AG7
becomes LC1D40A3G7. Note that 40–65 A spring terminals are only on the control terminations and not on power terminations).
[43] For slip-on connector versions of LC1D09 and LC1D12 only, add 9 to the catalog number prior to adding the voltage code (for example, LC1D09G7 becomes LC1D099G7).
[44] For DC version of these devices, replace the C with a P (for example, LC1D80004•• becomes LP1D80004••). This applies only to 80 A, 4-pole devices.
[45] For additional voltage codes refer to the Control and Protection Components Catalog MKTED210011EN.
[46] Not available for LC1D80–LC1D150.
9/13/2019