Brochure
© 2019 Schneider Electric
All Rights Reserved
18-55
www.se.com/us
TeSys™ D DC Coils
Replacement Parts
Refer to Catalog MKTED210011EN
TeSys™ D—DC Coils
NOTE: DC coils for new TeSys D contactors LC●D09-D38, LC1DT20-DT40,
LC●D40A-65A, LC1DT60A-80A, and LC●D80-D95 are not replaceable.
Table 18.177: For Old D2 LP1D80 and LC1D80
[7]
Rated Nominal Voltage
V
Catalog Number
Catalog Number
Wide Range [8]
12 LX4D7JD LX4D7JW
24 LX4D7BD LX4D7BW
36 LX4D7CD LX4D7CW
48 LX4D7ED LX4D7EW
60 LX4D7ND —
72 LX4D7SD LX4D7SW
110 LX4D7FD LX4D7FW
125 LX4D7GD —
220 LX4D7MD LX4D7MW
250 LX4D7UD —
440 LX4D7RD —
600 LX4D7XD —
Specifications
Average consumption
22 W 23 W
Operating range
at θ < 55 °C / 131 °F
80–110%
nominal voltage
70–120%
nominal voltage
Table 18.178: For TeSys D LC1D115, 150
Rated Nominal Voltage
V
Catalog Number
24 LX4D8BD
48 LX4D8ED
60 LX4D8ND
72 LX4D8SD
110 LX4D8FD
125 LX4D8GD
220 LX4D8MD
250 LX4D8UD
440 LX4D8RD
Average Consumption
Inrush 365 W, Sealed 5 W
Operating range at θ < 55 °C / 131 °F 70%–120% of nominal voltage
TeSys D contactors: page 18-7 and page 18-9
TeSys D overload relay accessories: page 18-21
TeSys D replacement coils: page 18-53
TeSys D dimensions: page 18-60 to page 18-68
18
CONTACTORS AND STARTERS-IEC
[7] For old style contactors where the catalog number includes the auxiliary contact arrangement (for example, LP1D8010). The new style TeSys DC controlled contactors (for example,
LC1D80BD) do not have replaceable coils.
[8] Wide range coils cannot be used with contactors using both front- and side-mounting auxiliaries.
9/13/2019