Brochure

18-50
© 2019 Schneider Electric
All Rights Reserved
Motor Starters and Protectors TeSys™ LS1 Fuse Holders
www.se.com/us
Refer to Catalog MKTED210011EN
TeSys™ LS1 Fuse Holders
45 mm wide (same dimensions as GV2ME)
Available with screw clamp and spring type terminals
Mounts directly to LC1D09–D38 contactors (with use of GV2AF3 or GV2AF4)
Meets application needs for fusible starter
Uses GV2AE instantaneous contact blocks to open control circuits
DIN rail mounted
LS1D30
Table 18.166: TeSys LS1 Fuse Holders
Description Fuse Type
Dimensions
Use In
Catalog
Number
in. mm
Spring terminals, 3-pole
CC, KTK-R
0.41 x 1.5 10.3 x 38 US Markets LS1D303
Screw clamp terminals, 3-
pole
CC, KTK-R
0.41 x 1.5 10.3 x 38 US Markets LS1D30
Spring terminals, 3-pole aM, gG
0.39 x 1.5 10 x 38
European
Markets
LS1D323
Screw clamp terminals, 3-
pole
aM, gG
0.39 x 1.5 10 x 38
European
Markets
LS1D32
Auxiliary main pole adder aM, gG
0.39 x 1.5 10 x 38
European
Markets
LA8D324 [72]
Table 18.167: Specifications
Type
LS1D30, LS1D303
LS1D32, LS1D323,
LS1DT32
Max. voltage
600 V 3 Phase
Max. current 30 A
Conforming to standards
IEC 60947-1, 60947-2, 60947-4-1, EN60204,
BS4841, UL 508, CSA 222.2 No. 14, NFC 63-650,
63-120, 79-130, VDE 0113, 0660
Product approvals
UL, CSA
BV
Protective treatment “TH”
Ambient air temperature—operation -58 to 158 °F (-50 to +70 °C)
Wiring
Number of conductors and cross sectional area (c.s.
a.)
Solid cable
2 x 16–8 AWG (1–6 mm
2
)
Flexible cable without cable end
2 x 14–8 AWG (1–6 mm
2
)
Flexible cable with cable end
2 x 16–10 AWG (1–4 mm
2
)
Resistance to mechanical impact conforming to IEC 60947-1
§7-1-6
0.5 J
Tightening torque 15 lb-in (1.7 N•m)
Sensitivity to phase failure
No
Operating positions
30
30
90
90
Rated voltage
600 V
E164862
CCN NLDX
LR43364
Class 3211 04
Table 18.168: Environmental Specifications and Approvals
Shock resistance
30 g (conforming to IEC 600 68-2-27)
Vibration resistance
5 g (5 to 150 Hz) (IEC 600 68-2-26)
Ambient temperature
–40 to 176 °F (–40 to +80 °C) for storage
–4 to 140 °F (–20 to +60 °C) open operation
–4 to 104 °F (–20 to +40 °C) enclosed operation
Maximum operating rate 25 operations per hour
Operating current of magnetic trip
Approximately 13 times the maximum thermal trip
(non-adjustable setting)
18
CONTACTORS AND STARTERS-IEC
[72] Can be mounted on left-hand or right-hand side of the 3-pole LS1D32 block.
9/13/2019