Motor Starters and Protectors TeSys™ LS1 Fuse Holders
www.se.com/us
Refer to Catalog MKTED210011EN
TeSys™ LS1 Fuse Holders
•
45 mm wide (same dimensions as GV2ME)
•
Available with screw clamp and spring type terminals
•
Mounts directly to LC1D09–D38 contactors (with use of GV2AF3 or GV2AF4)
•
Meets application needs for fusible starter
•
Uses GV2AE instantaneous contact blocks to open control circuits
•
DIN rail mounted
LS1D30
Table 18.166: TeSys LS1 Fuse Holders
Description Fuse Type
Dimensions
Use In
Catalog
Number
in. mm
Spring terminals, 3-pole
CC, KTK-R
0.41 x 1.5 10.3 x 38 US Markets LS1D303
Screw clamp terminals, 3-
pole
CC, KTK-R
0.41 x 1.5 10.3 x 38 US Markets LS1D30
Spring terminals, 3-pole aM, gG
0.39 x 1.5 10 x 38
European
Markets
LS1D323
Screw clamp terminals, 3-
pole
aM, gG
0.39 x 1.5 10 x 38
European
Markets
LS1D32
Auxiliary main pole adder aM, gG
0.39 x 1.5 10 x 38
European
Markets
LA8D324 [72]
Table 18.167: Specifications
Type
LS1D30, LS1D303
LS1D32, LS1D323,
LS1DT32
Max. voltage
600 V 3 Phase
Max. current 30 A
Conforming to standards
IEC 60947-1, 60947-2, 60947-4-1, EN60204,
BS4841, UL 508, CSA 222.2 No. 14, NFC 63-650,
63-120, 79-130, VDE 0113, 0660
Product approvals
UL, CSA
BV
Protective treatment “TH”
Ambient air temperature—operation -58 to 158 °F (-50 to +70 °C)
Wiring
Number of conductors and cross sectional area (c.s.
a.)
Solid cable
2 x 16–8 AWG (1–6 mm
2
)
Flexible cable without cable end
2 x 14–8 AWG (1–6 mm
2
)
Flexible cable with cable end
2 x 16–10 AWG (1–4 mm
2
)
Resistance to mechanical impact conforming to IEC 60947-1
§7-1-6
0.5 J
Tightening torque 15 lb-in (1.7 N•m)
Sensitivity to phase failure
No
Operating positions
30
30
90
90
Rated voltage
600 V
E164862
CCN NLDX
LR43364
Class 3211 04
Table 18.168: Environmental Specifications and Approvals
Shock resistance
30 g (conforming to IEC 600 68-2-27)
Vibration resistance
5 g (5 to 150 Hz) (IEC 600 68-2-26)
Ambient temperature
–40 to 176 °F (–40 to +80 °C) for storage
–4 to 140 °F (–20 to +60 °C) open operation
–4 to 104 °F (–20 to +40 °C) enclosed operation
Maximum operating rate 25 operations per hour
Operating current of magnetic trip
Approximately 13 times the maximum thermal trip
(non-adjustable setting)
18
CONTACTORS AND STARTERS-IEC
[72] Can be mounted on left-hand or right-hand side of the 3-pole LS1D32 block.