TeSys™ D Enclosed—Fusible, Circuit Breaker, and Non-Fusible
LE1D096B62OU70
IEC combination starters combine the requirements of motor overload and short circuit
protection in one convenient compact package. All devices provide Type 2 Coordination
through 30 hp at 460 V. Devices are available in Type 1 and Type 12/3R enclosures. The
IEC combination starter line accepts standard TeSys D accessories and all Insta-Kits
pilot devices and control power transformer kits. Standard capacity control power
transformers with built-in fuse block can be installed in the standard enclosure. For extra
capacity, please refer to your local distributor or nearest Square D/Schneider Electric
sales office.
NOTE: Use tables and notes from page 18-42 to complete the catalog numbers.
Table 18.151: Enclosed Full Voltage Non-Reversing Fusible Combination Starters
[57]
Maximum Three-Phase Horsepower Ratings Fuse Clip Rating
Auxiliary
Contacts
Current
Rating of
Contactor
Catalog Number[58][59]
208 V 230 V 460 V 575 V
Amperes
UL Class N.O. N.C.
Type 1 Type 12/3R
2 2 5 7.5 30 A J 1 1 9 LE1D098B62O●●●● LE1D098B72O●●●●
3 3 7.5 10 30 A J 1 1 12 LE1D128B62O●●●● LE1D128B72O●●●●
5 5 10 15 30 A J 1 1 18 LE1D188B62O●●●● LE1D188B72O●●●●
7.5 7.5 15 20 60 A J 1 1 25 LE1D258C62O●●●● LE1D258C72O●●●●
10 10 20 25 60 A J 1 1 32 LE1D328C62O●●●● LE1D328C72O●●●●
10 10 30 30 60 A J 1 1 40 LE1D408C62O●●●● LE1D408C72O●●●●
15 15 40 40 100 A J 1 1 50 LE1D508D62O●●●● LE1D508D72O●●●●
20 20 40 50 100 A J 1 1 65 LE1D658D62O●●●● LE1D658D72O●●●●
25 30 60 60 200 A J 1 1 80 LE1D808E62O●●●● LE1D808E72O●●●●
30 40 75 75 200 A J 1 1 115 LE1D118E62O●●●● LE1D118E72O●●●●
40 50 100 100 200 A J 1 1 150 LE1D158E62O●●●● LE1D158E72O●●●●
Table 18.152: Enclosed Full Voltage Reversing Fusible Combination Starters[57]
Maximum Three-Phase Horsepower Ratings Fuse Clip Rating
Aux. Contacts
Each Contactor
Current
Rating of
Contactor
Catalog Number[58][60]
200 V 230 V 460 V 575 V
Amperes
UL Class N.O. N.C.
Type 1 Type 12/3R
2 2 5 7.5 30 A J 1 1 9 LE2D098B62O●●●● LE2D098B72O●●●●
3 3 7.5 10 30 A J 1 1 12 LE2D128B62O●●●● LE2D128B72O●●●●
5 5 10 15 30 A J 1 1 18 LE2D188B62O●●●● LE2D188B72O●●●●
7.5 7.5 15 20 60 A J 1 1 25 LE2D258C62O●●●● LE2D258C72O●●●●
10 10 20 25 60 A J 1 1 32 LE2D328C62O●●●● LE2D328C72O●●●●
10 10 30 30 60 A J 1 1 40 LE2D408C62O●●●● LE2D408C72O●●●●
15 15 40 40 100 A J 1 1 50 LE2D508D62O●●●● LE2D508D72O●●●●
20 20 40 50 100 A J 1 1 65 LE2D658D62O●●●● LE2D658D72O●●●●
25 30 60 60 200 A J 1 1 80 LE2D808E62O●●●● LE2D808E72O●●●●
30 40 75 75 200 A J 1 1 115 LE2D118E62O●●●● LE2D118E72O●●●●
40 50 100 100 200 A J 1 1 150 LE2D158E62O●●●● LE2D158E72O●●●●
Table 18.153: Enclosed Full Voltage Non-Reversing Circuit Breaker Combination Starters[57]
Maximum Three-Phase Horsepower Ratings
Auxiliary
Contacts
Circuit Breaker
Maximum
Current Rating
Current
Rating of
Contactor
Catalog Number [58][60]
200 V 230 V 460 V 575 V N.O. N.C.
Type 1 Type 12/3R
2 2 5 7.5 1 1 30 A 9 LE1D099E62O●●●● LE1D099E72O●●●●
3 3 7.5 10 1 1 30 A 12 LE1D129E62O●●●● LE1D129E72O●●●●
7.5 7.5 15 20 1 1 30 A 25 LE1D259E62O●●●● LE1D259E72O●●●●
7.5 10 20 25 1 1 50 A 32 LE1D329F62O●●●● LE1D329F72O●●●●
10 10 30 30 1 1 50 A 40 LE1D409F62O●●●● LE1D409F72O●●●●
15 15 40 40 1 1 100 A 50 LE1D509G62O●●●● LE1D509G72O●●●●
20 20 40 50 1 1 100 A 65 LE1D659G62O●●●● LE1D659G72O●●●●
25 30 60 60 1 1 150 A 80 LE1D809G62O●●●● LE1D809G72O●●●●
30 40 75 75 1 1 200 A 115 LE1D119H62O●●●● LE1D119H72O●●●●
40 50 100 100 1 1 200 A 150 LE1D159J62O●●●● LE1D159J72O●●●●
18
CONTACTORS AND STARTERS-IEC
[57] Insta-kit design available in Type 1 and Type 12 enclosures only.
[58] Replace (••••) with the corresponding coil voltage code from Table 18.148 Voltage Codes for Enclosed Starters, page 18-42 followed by the corresponding O/L relay suffix number from
Table 18.149 Overload Relay Range, page 18-42.
[59] For fuse clips different from the ones proposed, specify your requirement using Table 18.145.
[60] For a breaker size different from the ones proposed, specify your requirement using Table 18.145.
9/13/2019