TeSys™ D Enclosed Starters Motor Starters and Protectors
Refer to Catalog MKTED210011EN
Table 18.149 Overload Relay Range (Select code
from below)
[18.149] (cont'd.)
Code
Range
For use on
Contactors
17–25
D25–D32 [52]
17–25 D80
25 17–25
D40, D50, D65
30 23-28
D25–D32 [53]
32 23–32 D25–D32
32 23–32
D40, D50, D65
40 30–40
D40, D50, D65
50 37–50
D40, D50, D65
53 30–38 D80
55 30–40 D80
57 37–50 D80
59 48–65 D80
61 55–70 D65–D80
63 63–80 D65–D80
65 48–65
D40, D50, D65
Table 18.150: Catalog Number Nomenclature
Catalog Number Example
LE1D093A62 O G 7 1 07
Base Catalog
No.
Control Power
Transformer (Primary
Voltage) [54]
Contactor/
Starter Coil
Voltage
Coil Frequency
Overload Relay
Type
Overload
Relay
Range
See
Table 18.146
or Table
18.147
None = O [55]
208 V = L
240 V = M
480 V = T
600 V = X
24 Vac/Vdc = B
120 Vac = G
208 Vac = L
240 Vac = U
480 Vac = T
600 Vac = X
7 = dual (50/60
Hz)
6 = 60 Hz.
D=DC [56]
0 = None
1 = Class 10 Trip
2 = Class 20 Trip
See Table
18.149
TeSys D dimensions: page 18-71
18
CONTACTORS AND STARTERS-IEC
[52] Available for Class 20 only.
[53] Available for Class 10 only.
[54] If a control transformer is used, the only options available are 24 or 120 V as the secondary of the transformer. Also, DC voltages are not available when control power transformer is used.
[55] Letter O, not zero.
[56] For 9–65 A contactors, only dual frequency coils are available; for 80 A contactors, the 24–240 V coils are dual frequency only (50/60 Hz). The 480–600 V coils are 60 Hz. only. See catalog
MKTED210011EN for other restrictions.