Brochure

18-32
© 2019 Schneider Electric
All Rights Reserved
Motor Starters and Protectors TeSys™ GV Manual Starters and Protectors
www.se.com/us
Refer to Catalog MKTED210011EN
TeSys™ GV Family
GV2ME
The TeSys GV family of products are 3-pole, horsepower rated, UL 508 listed manual
starters. They include a manual disconnect, class 10 ambient-compensated thermal
overload relay, and instantaneous, magnetic trip mechanism in one compact unit.
Any GV manual starter can be used alone for local manual control of a motor with
individual full-load currents up to 220 A. The GV products may also be used in group
motor installations in accordance with National Electric Code article 430-53. Group motor
installations give you greater panel density for smaller size and require fewer parts and
less wiring for installation when compared to conventional panel designs.
The GV2P and GV3P products also have an additional UL508 Type E rating as a stand-
alone, self-protected manual combination starter. The UL508 Type E rating requires the
addition of line side insulating barrier GV2GH7 for the GV2P or a GV3G66 line side
insulating barrier and a GVAM11 short circuit signaling contact for the GV3P. The GV2P
and GV3P self-protected manual combination starters may also be combined with
specific size contactors from the LC1D product family for a UL508 Type F combination
starter construction. These products have a UL-listed short circuit current rating from 10–
100 kA depending on application size and voltage. Refer to the Motor Control Solutions
for the North American Market data bulletin (8536DB0901) for more information.
Table 18.123: GV2, GV3
Thermal
Setting
(A)
Maximum Horsepower Ratings
Group Motor
Applications
GV2ME
push button
[31]
GV2/3P
rotary
handle
Single-Phase
Three-Phase
115 V 200 V 230 V 115 V 200 V 230 V 460 V 575 V
Max. Fuse or
Circuit Breaker
Catalog
Number
Catalog
Number
GV2P
GV3P
0.10–0.16 450 A GV2ME01 GV2P01
0.16–0.25 450 A GV2ME02 GV2P02
0.25–0.40 450 A GV2ME03 GV2P03
0.40–0.63 450 A GV2ME04 GV2P04
0.63–1 1/2 450 A GV2ME05 GV2P05
1–1.6 1/10 3/4 3/4 450 A GV2ME06 GV2P06
1.6–2.5 1/6 1/6 1/2 1/2 1 1.5 450 A GV2ME07 GV2P07
2.5–4 1/8 1/4 1/3 3/4 3/4 2 3 450 A GV2ME08 GV2P08
4–6.3 1/4 1/2 1/2 3/4 1 1.5 3 5 450 A GV2ME10 GV2P10
6–10 1/2 1 1.5 1 2 3 5 7.5 450 A GV2ME14 GV2P14
9–14 3/4 2 2 2 3 3 10 10 450 A GV2ME16 GV2P16
13–18 1 2 3 2 5 5 10 15 450 A GV2ME20 GV2P20
17–23 1.5 3 3 3 5 7.5 15 20 450 A GV2ME21 GV2P21
20–25 2 7.5 7.5 15 20 450 A GV2ME22 GV2P22
24–32 2 5 5 5 7.5 10 20 25 450 A GV2ME32 GV2P32
9–13 1/2 1.5 3 3 7.5 10 GV3P13
12–18 3/4 2 3 5 7.5 10 GV3P18
17–25 1.5 3 5 7.5 15 20 GV3P25
23–32 2 3 7.5 7.5 20 25 GV3P32
30–40 3 5 10 10 25 30 GV3P40
37–50 3 7.5 10 10 30 40 GV3P50
48–65 3 10 15 15 40 50 GV3P65
GV7RE20
Table 18.124: GV7
Thermal Setting (A)
Maximum Three-Phase Horsepower Ratings
Toggle Operator
Standard
Interrupt
High Interrupt
200 V 230 V 460 V 575 V
Catalog No. Catalog No.
12–20 5 10 15 GV7RE20 GV7RS20
15–25 7.5 15 20 GV7RE25 GV7RS25
25–40 10 30 30 GV7RE40 GV7RS40
30–50 15 30 40 GV7RE50 GV7RS50
48–80 30 60 75 GV7RE80 GV7RS80
60–100 30 75 100 GV7RE100 GV7RS100
90–150 50 100 150 GV7RE150 GV7RS150
132–220 75 150 200 GV7RE220 GV7RS220
Accessories: page 18-36
Dimensions: page 18-77 and page 18-79
18
CONTACTORS AND STARTERS-IEC
[31] For spring terminals add 3 to the catalog number (for example, GV2ME013). GV2ME32 is not available with spring terminals. For ring terminals, add 6.
9/13/2019