TeSys™ U Enclosed Combination Starters Motor Starters and Protectors
Refer to Catalog MKTED210011EN
2.1 Choose the thermal overload protection type
Table 18.101: Thermal Overload Protection Types
Advanced Control Unit Multifunction Control Unit
No Control Unit
(Ordered later on independently)
Single Phase
3-Phase
Thermal Overload Protection Type Code
A B C D N1 N3
Protection Type
Single phase, Class 10
3-phase, Class 10
3-phase, Class 20
3-phase, Selectable Class 5–30
Protection Functions
Short circuit
Over current
Thermal overload
Phase loss
Phase imbalance
Ground fault
Underload, long start, jam
Control Functions
Automatic or local/remote reset
Fault differentiation
Thermal alarm
Motor load display
Fault history
Alarm threshold adjustment
Tripping test
Complete the Thermal Overload Relay Selection by adding the full load amperage code after the thermal overload protection type code.
Built-in Control Unit.
Available when combined with appropriate Function module.
2.2 Choose the Motor Full Load Amperage
Table 18.102: Full Load Amperage Code
Full Load Amperage Setting Range (A) Full Load Amperage Code
0.15–0.6 A
0.3–1.4 B
1.25–5.0 C
3–12 D
4.5–18 E
8–32 F