TeSys™ F Reversing Contactors
LC1F265
Components are available for customer assembly of TeSys F reversing contactors. For
example, the following components must be ordered to build a reversing contactor, 75 hp
@ 460 V, with a 120 V / 60 Hz coil:
Table 18.35: Example of Components
Description Quantity Catalog Number
Contactors 2 LC1F115G6
Lugs (page 18-20)
6 DZ2FF1
Auxiliary contacts
2 LADN11
Power connections 1 LA9FF976
Mechanical interlock 1 LA9FF970
Table 18.36: 3-Pole Contactors
Maximum Three-Phase
Horsepower Ratings
Maximum Current (A)
Continuous
Current
Rating (A)
Holding Circuit
Contact Built
Into Coil
Catalog
Number [60]
Inductive
AC3
Resistive
AC1
200 V 230 V 460 V 575 V N.O. N.C.
30 40 75 100 115 200 175 1 0 LC1F115
40 50 100 125 150 250 200 1 0 LC1F150
50 60 125 150 185 275 200 1 0 LC1F185
60 75 150 150 225 315 250 1 0 LC1F225
60 75 150 200 265 350 285 1 0 LC1F265
75 100 200 250 330 400 370 1 0 LC1F330
100 125 250 300 400 500 420 1 0 LC1F400
150 200 400 500 500 700 700 1 0 LC1F500
250 300 600 800 630 1000 1000 1 0 LC1F630
350 400 800 900 800 1000 1000 0 0 LC1F800
— 450 900 900 780 1600 1350 0 0 LC1F780
Table 18.37: Auxiliary Contact (Electrical Interlocking)—2 must be purchased
For use with
Number of
Contacts
Maximum Number
of Blocks
Per Contactor
Contact Arrangement
Catalog
Number
N.O. N.C.
LC1F
to be ordered
separately
1 1
1 —
LADN10 [61]
— 1 LADN01
2 2
1 1 LADN11
2 —
LADN20 [61]
4 2
2 2 LADN22
1 3 LADN13
4 —
LADN40 [61]
— 4 LADN04
3 1 LADN31
2 2
LADC22 [62]
Table 18.38: Accessories—For the Assembly of 3-Pole Reversing Contactors
(Horizontal Mounting)
With 2 Identical
Contactors [63]
Set of Power Connections
Catalog Number
Horizontal Mounting
Mechanical Interlock Kit
Catalog Number
LC1F115 LA9FF976 LA9FF970
LC1F150 LA9F15076 LA9FF970
LC1F185 LA9FG976 LA9FG970
LC1F225 LA9F22576 LA9FG970
LC1F265 LA9FH976 LA9FJ970
LC1F330 LA9FJ976 LA9FJ970
LC1F400 LA9FJ976 LA9FJ970
LC1F500 LA9FK976 LA9FJ970
LC1F630, F800
LA9FL976 LA9FL970
Table 18.39: Definite Purpose Ratings, 3-Phase, Breaking All Lines, 100,000 Cycles
(Hermetic Refrigeration Compressor)
Device FLA
LRA
240 V 480 V 600 V
LC1D09 (AC coil only)
9 54 45 36
LC1D12 (AC coil only)
12 72 60 48
LC1D18 (AC coil only)
18 108 90 72
LC1D25 (AC coil only)
25 150 125 100
LC1D32 (AC coil only)
32 192 160 128
LC1D40A 40 240 200 160
LC1D50A 50 300 250 200
LC1D65A 65 390 325 260
LC1D80 75 450 375 300
LC1D115 115 690 575 460
LC1D150 150 900 750 600
TeSys F contactor accessories: page 18-15
TeSys F overload relay accessories: page 18-21
TeSys F replacement coils and parts: page 18-57, page 18-53, and page 18-56
TeSys F dimensions: page 18-62
E164862
CCN NLDX
LR43364
Class 3211 04
18
CONTACTORS AND STARTERS-IEC
[60] Complete the catalog number with the coil voltage code from and (for example, LC1F115G7). All coils except F780 include 1 N.O. holding circuit interlock contact. The F780 uses 2 coils that
must be wired in series.
[61] Cannot be used for interlocking.
[62] Including 1 N.O. + 1 N.C. make-before-break overlapping contacts.
[63] For two contactors of different size, refer to page 18-19.
9/13/2019