Brochure
© 2019 Schneider Electric
All Rights Reserved
18-11
www.se.com/us
TeSys™ F Contactors and Overload Relays Contactors and Overload Relays
Refer to Catalog MKTED210011EN
TeSys™ F Non-Reversing Contactors
Table 18.31: TeSys F Contactors—2, 3, and 4 Pole
Maximum Three-Phase Horsepower Ratings Maximum Current (A)
Continuous
Current
Rating (A)
Number of
Poles
Catalog Number [54]
200 V 230 V 460 V 575 V
Inductive
AC-3
Resistive
AC-1
Panel Mount
with Screws
LC1F330
30 40 75 100 115 200 175
3 LC1F115
4 LC1F1154
40 50 100 125 150 250 200
3 LC1F150
4 LC1F1504
50 60 125 150 185 275 200
3 LC1F185
4 LC1F1854
60 75 150 150 225 315 250
3 LC1F225
4 LC1F2254
60 75 150 200 265 350 285
3 LC1F265
4 LC1F2654
75 100 200 250 330 400 370
3 LC1F330
4 LC1F3304
100 125 250 300 400 500 420
2 LC1F4002
3 LC1F400
4 LC1F4004
LC1F1700, F2100
150 200 400 500 500 700 700
2 LC1F5002
3 LC1F500
4 LC1F5004
250 300 600 800 630 1000 1000
2 LC1F6302
3 LC1F630
4 LC1F6304
350 400 800 900 800 1000 1000 3 LC1F800
— 450 900 900 780 1600 1350
3 LC1F780
4 LC1F7804
Current Rated
1400 1400 3 LC1F1400
1700 1700 3 LC1F1700
2100 2100 3 LC1F2100
Table 18.32: TeSys F Coil Voltage Codes [55]
Contactor Hz
Coil
Prefix
24 V 48 V 110 V 120 V 208 V 220 V 240 V 440 V 480 V 600 V
AC
F115, F150, F185, and F225
60 LX1 B6 — — — — — — — — X6
40–400 LX9 — E7 F7 G7 L7 M7 U7 R7 S7 —
F265 and F330 40–400 LX1 B7 E7 F7 G7 L7 M7 U7 R7 S7 X7
F400–F780 40–400 LX1 — E7 F7 G7 L7 M7 U7 R7 S7
X7 [56]
F1400–F2100 40–400 LX1 — — F7 G7 L7 M7 U7 R7 S7 —
Contactor Coil Prefix 24 V 48 V 110 V 125 V 220 V 250 V 440 V
DC [57]
F115–F330 LX4 BD ED FD GD MD UD RD
F400–F630 LX4 — ED FD GD MD UD RD
F780, F1400–F2100
LX4 — — FD GD MD UD RD
Table 18.33: Coil Voltage Codes for AC and DC Voltages for F800 (includes built-in surge suppressor)
Vac/Vdc Hz
Coil
Prefix
110 V 120 V 127 V 220 V 240 V 380 V 400 V 415 V
Code 40–400 LX4 FW FW FW MW MW
QW QW QW
TeSys™ F Overload Relays
Table 18.34: TeSys F 3-Phase Overload Relays—Solid State, Separate Mounting [58]
Current Setting Range A
For Direct Mounting to Contactor
LC1●●●●
Class 10 Catalog Number Class 20 Catalog Number
Class 10/20 Selectable Catalog
Number
30–50 F115–F185 LR9F5357 LR9F5557 LR9F57
48–80 F115–F185 LR9F5363 LR9F5563 LR9F63
60–100 F115–F185 LR9F5367 LR9F5567 LR9F67
90–150 F115–F185 LR9F5369 LR9F5569 LR9F69
132–220
F185[59]–F400
LR9F5371 LR9F5571 LR9F71
200–330 F225–F500 LR9F7375 LR9F7575 LR9F75
300–500 F330–F500 LR9F7379 LR9F7579 LR9F79
380–630
F400–F630, F800
LR9F7381 LR9F7581 LR9F81
E164862
CCN NLDX
LR43364
Class 3211 04
TeSys F contactor accessories: page 18-15
TeSys F overload relay accessories: page 18-21
TeSys F replacement coils and parts: page 18-57, page 18-53, and page 18-56
TeSys F dimensions: page 18-62 and page 18-70
18
CONTACTORS AND STARTERS-IEC
[54] Complete the catalog number with the coil voltage code from Table 18.32 and Table 18.33 (for example, LC1F115G7). All coils except F780 include 1 N.O. holding circuit interlock contact.
The F780 uses 2 coils that must be wired in series.
[55] For additional voltage codes refer to the Control and Protection Components Catalog MKTED210011EN.
[56] Not available for LC1F780. The 600 V coils for LC1F400-LC1F630 do not include an auxiliary contact for holding circuits.
[57] DC coils for 3-pole contactors are fitted with built-in surge suppression as standard.
[58] When mounting overload relays LR9F5●57–LR9F5●71 and LR9F57–LR9F71 directly beneath the contactor, supporting the relays with a mounting plate is recommended. With overload
relays LR9F7●75–LR9F7●81 and LR9F75–LR9F81, use of a support mounting plate is mandatory. Refer to page 18-21.
[59] Interconnection kit LA7F407 is required to mount an LR9F5●71 and LR9F71 to an LC1F185.
9/13/2019