Brochure

© 2019 Schneider Electric
All Rights Reserved
18-11
www.se.com/us
TeSys™ F Contactors and Overload Relays Contactors and Overload Relays
Refer to Catalog MKTED210011EN
TeSys™ F Non-Reversing Contactors
Table 18.31: TeSys F Contactors—2, 3, and 4 Pole
Maximum Three-Phase Horsepower Ratings Maximum Current (A)
Continuous
Current
Rating (A)
Number of
Poles
Catalog Number [54]
200 V 230 V 460 V 575 V
Inductive
AC-3
Resistive
AC-1
Panel Mount
with Screws
LC1F330
30 40 75 100 115 200 175
3 LC1F115
4 LC1F1154
40 50 100 125 150 250 200
3 LC1F150
4 LC1F1504
50 60 125 150 185 275 200
3 LC1F185
4 LC1F1854
60 75 150 150 225 315 250
3 LC1F225
4 LC1F2254
60 75 150 200 265 350 285
3 LC1F265
4 LC1F2654
75 100 200 250 330 400 370
3 LC1F330
4 LC1F3304
100 125 250 300 400 500 420
2 LC1F4002
3 LC1F400
4 LC1F4004
LC1F1700, F2100
150 200 400 500 500 700 700
2 LC1F5002
3 LC1F500
4 LC1F5004
250 300 600 800 630 1000 1000
2 LC1F6302
3 LC1F630
4 LC1F6304
350 400 800 900 800 1000 1000 3 LC1F800
450 900 900 780 1600 1350
3 LC1F780
4 LC1F7804
Current Rated
1400 1400 3 LC1F1400
1700 1700 3 LC1F1700
2100 2100 3 LC1F2100
Table 18.32: TeSys F Coil Voltage Codes [55]
Contactor Hz
Coil
Prefix
24 V 48 V 110 V 120 V 208 V 220 V 240 V 440 V 480 V 600 V
AC
F115, F150, F185, and F225
60 LX1 B6 X6
40–400 LX9 E7 F7 G7 L7 M7 U7 R7 S7
F265 and F330 40–400 LX1 B7 E7 F7 G7 L7 M7 U7 R7 S7 X7
F400–F780 40–400 LX1 E7 F7 G7 L7 M7 U7 R7 S7
X7 [56]
F1400–F2100 40–400 LX1 F7 G7 L7 M7 U7 R7 S7
Contactor Coil Prefix 24 V 48 V 110 V 125 V 220 V 250 V 440 V
DC [57]
F115–F330 LX4 BD ED FD GD MD UD RD
F400–F630 LX4 ED FD GD MD UD RD
F780, F1400–F2100
LX4 FD GD MD UD RD
Table 18.33: Coil Voltage Codes for AC and DC Voltages for F800 (includes built-in surge suppressor)
Vac/Vdc Hz
Coil
Prefix
110 V 120 V 127 V 220 V 240 V 380 V 400 V 415 V
Code 40–400 LX4 FW FW FW MW MW
QW QW QW
TeSys™ F Overload Relays
Table 18.34: TeSys F 3-Phase Overload Relays—Solid State, Separate Mounting [58]
Current Setting Range A
For Direct Mounting to Contactor
LC1●●●●
Class 10 Catalog Number Class 20 Catalog Number
Class 10/20 Selectable Catalog
Number
30–50 F115–F185 LR9F5357 LR9F5557 LR9F57
48–80 F115–F185 LR9F5363 LR9F5563 LR9F63
60–100 F115–F185 LR9F5367 LR9F5567 LR9F67
90–150 F115–F185 LR9F5369 LR9F5569 LR9F69
132–220
F185[59]–F400
LR9F5371 LR9F5571 LR9F71
200–330 F225–F500 LR9F7375 LR9F7575 LR9F75
300–500 F330–F500 LR9F7379 LR9F7579 LR9F79
380–630
F400–F630, F800
LR9F7381 LR9F7581 LR9F81
E164862
CCN NLDX
LR43364
Class 3211 04
TeSys F contactor accessories: page 18-15
TeSys F overload relay accessories: page 18-21
TeSys F replacement coils and parts: page 18-57, page 18-53, and page 18-56
TeSys F dimensions: page 18-62 and page 18-70
18
CONTACTORS AND STARTERS-IEC
[54] Complete the catalog number with the coil voltage code from Table 18.32 and Table 18.33 (for example, LC1F115G7). All coils except F780 include 1 N.O. holding circuit interlock contact.
The F780 uses 2 coils that must be wired in series.
[55] For additional voltage codes refer to the Control and Protection Components Catalog MKTED210011EN.
[56] Not available for LC1F780. The 600 V coils for LC1F400-LC1F630 do not include an auxiliary contact for holding circuits.
[57] DC coils for 3-pole contactors are fitted with built-in surge suppression as standard.
[58] When mounting overload relays LR9F5●57–LR9F5●71 and LR9F57–LR9F71 directly beneath the contactor, supporting the relays with a mounting plate is recommended. With overload
relays LR9F7●75–LR9F7●81 and LR9F75–LR9F81, use of a support mounting plate is mandatory. Refer to page 18-21.
[59] Interconnection kit LA7F407 is required to mount an LR9F5●71 and LR9F71 to an LC1F185.
9/13/2019