Full Product Manual
Table Of Contents
- Section 1 Load Centers
- EZ Selector - Selection Assistance
- QO™ Miniature Circuit Breakers
- QO™ Load Centers
- Homeline™ Miniature Circuit Breakers
- Homeline™ Load Centers
- QO/Homeline Load Center Value Packs and Accessories
- QO/Homeline Load Center Dimensions
- Combination Service Entrance Devices
- Solar Ready PoN CSEDs
- Wiser Energy™ and Wiring Devices
- Enclosed Devices
- Servicepak™ Power Outlet Panels
1-6
© 2022 Schneider Electric
All Rights Reserved
March 1, 2022
QO™ Miniature Circuit Breakers QO Plug-On Circuit Breakers
www.se.com/us
Class 685, 690, 730, 912, 950 / Refer to Catalog: 0730CT9801
1
LOAD CENTERS
QO-EPD/EPE Circuit Breakers
QO 1P
With Shunt Trip
QO-EPD/EPE circuit breakers provide overload and short circuit protection combined
with Class B ground fault protection. They are designed to provide ground fault
protection of equipment at a 30 mA level (EPD) or 100 mA level (EPE). They are not
designed to protect people from electrical shock.
Table 1.9: QO-EPD Circuit Breakers
Ampere
Rating
[19]
1P
120 Vac
10 k AIR
1 Space Required
2P Common Trip
120/240 Vac
10 k AIR
2 Spaces Required
3P Common Trip
240 Vac
10 k AIR
3 Spaces Required
15
QO115EPD QO215EPD QO315EPD
OBS
QO315EPE [20]
20
QO120EPD QO220EPD
QO320EPD [20] QO320EPE [20]
25
QO125EPD
OBS
QO225EPD
— —
30
QO130EPD QO230EPD
QO330EPD [20] QO330EPE [20]
40 —
QO240EPD
QO340EPD [20] QO340EPE [20]
50 —
QO250EPD
QO350EPD [20] QO350EPE [20]
60 —
QO260EPD [21]
— —
OBS
This product is obsolete.
QO Switch Neutral Common Trip Circuit Breakers (QO-SWN)
Two-wire
QO-SWN
Three-wire
QO-SWN
Switch Neutral Common Trip 2008 NEC
®
514.11
Table 1.10: QO-SWN Circuit Breakers
Ampere
Rating [22]
2 Wire 120 Vac
10 k AIR
2 Spaces Required
3 Wire 120/240 Vac
10 k AIR
3 Spaces Required
10
QO210SWN
OBS
QO310SWN
15
QO215SWN QO315SWN
OBS
20
QO220SWN QO320SWN
25
QO225SWN
OBS
QO325SWN
30
QO230SWN
OBS
QO330SWN
OBS
40
QO240SWN
OBS
QO340SWN
OBS
50
QO250SWN
OBS
QO350SWN
OBS
OBS
This product is obsolete.
QO High Intensity Discharge Circuit Breakers (QO-HID)
HID circuit breakers are for use on circuits feeding fluorescent and high intensity
discharge (HID) lighting systems such as mercury vapor, metal halide, or high pressure
sodium. These circuit breakers are physically interchangeable with QO circuit breakers.
Table 1.11: QO-HID Circuit Breakers
Ampere
Rating [22]
1P 120/240 Vac
10 k AIR
1 Space Required
2P Common Trip
120/240 Vac
10 k AIR
2 Spaces Required
3P Common Trip
240 Vac
10 k AIR
3 Spaces Required
15
QO115HID
OBS
QO215HID
OBS
QO315HID
OBS
20 —
QO220HID QO320HID
25
QO125HID
OBS
QO225HID
OBS
QO325HID
OBS
30
QO130HID
OBS
QO230HID
OBS
QO330HID
OBS
40
QO140HID
OBS
QO240HID
OBS
—
50
QO150HID
OBS
QO250HID
OBS
—
OBS
This product is obsolete.
QO Key Operated Circuit Breakers (QO-K)
QO-K Key Operated
Key operated QO circuit breakers are available in single-pole construction and can be
mounted in any single-pole space which will accept a standard QO circuit breaker. These
circuit breakers can be turned ON or OFF or to RESET with a special key (catalog
number QOK10) included with the circuit breaker. These circuit breakers are UL Listed
and available as shown in the table.
Table 1.12: QO-K Circuit Breakers
120 Vac—10 k AIR (1 Space Required)
Ampere
Rating [22]
Cat. No.
Ampere
Rating [22]
Cat. No.
10
QO110K
OBS
25
QO125K
15
QO115K
OBS
30
QO130K
OBS
20
QO120K
OBS
— —
OBS
This product is obsolete.
[19] 10–30 A circuit breakers are suitable for use with 60
o
C or 75
o
C conductors. 35–60 A circuit breakers are suitable for use with 75
o
C conductors.
[20] See note in Instruction Bulletin when using in an enclosure with a QO403 or QON prefix.
[21] Suitable only for feeding 240 Vac and 208 Vac two-wire loads. Does not contain load neutral connection.
[22] 10–30 A circuit breakers are suitable for use with 60oC or 75oC conductors. 35–60 A circuit breakers are suitable for use with 75oC conductors.