Specification

QO
®
and Homeline
®
Load Centers and Enclosures
General Information and Application Data
13
03/2007
© 2007 Schneider Electric All Rights Reserved
Three-Phase, 3–42 Circuits, 60–225 A, Convertible or Fixed Mains
UL Listed
File E-6294
Suitable for use as service equipment
75 °C wire rating (see Technical Information on page 19)
Short Circuit Current Rating
Main lugs: up to 65,000 AIR (depends on lowest interrupting rating of
branch circuit breakers installed)
Main circuit breaker up to 225 A: 22,000 AIR standard; optional up to
65,000 AIR for 100 A to 225 A main circuit breakers
Mains
Factory-installed main lugs or main circuit breaker
Main neutral terminal located next to the phase terminals on 1252 25 A
main circuit breaker devices
Top or bottom feed (see Technical Information on page 24)
Fully convertible from main circuit breaker to main lugs (100 225 A)
100 A maximum back-fed main QO
®
circuit breaker; requires the use of
retaining kit PK3MB
Cover
Flush- and surface-mount covers sold separately
Flush covers have spring-loaded interior trim for automatic flush
adjustment
Positive action, easy-to-open door latch
Interior
Shielded one-piece plated copper bus on 1002 25 A
Removable interior with single, captive mounting screw on 10022 5 A
(indoor only)
Main lugs load centers have equipment grounding bar kits included
(not factory-installed)
Branch Neutral Termination
Suitable for copper or aluminum wire
Terminals suitable for one #14#4 AWG coppe r or one #12 #4 AWG
aluminum wire
Positioned on both sides of the mains compartment
Slot/square drive wire binding screws
Three (3) #141 /0 AWG copper or #14# 6 AWG aluminum terminations
standard on 124 2 circuits, 10022 5 A load centers
QO330L200G
QO330MQ150