Specification
QO
®
 and Homeline
®
 Load Centers and Enclosures
General Information and Application Data
7
03/2007
© 2007 Schneider Electric All Rights Reserved
Class CTL
Class CTL load centers are UL Listed
 Circuit breaker mounting rails have slots to accept tandem circuit 
breakers, on specified load centers
 Meets paragraph 408.35 of the 2005 National Electrical Code
®
 (NEC
®
)
Phasing
Load centers have distributed phase bussing 
 Most branch circuit breakers can be mounted in any position 
Line Lugs
All lugs suitable for 75 °C copper or aluminum wires (see Main Lugs 
and Main Circuit Breaker Ratings on page 20)
 Main lugs and main circuit breaker load centers have wire binding screw 
torque values on the wiring diagrams and circuit breaker labels
Neutral Assemblies 
All lugs suitable for copper or aluminum wire (see Main Lugs and Main 
Circuit Breaker Ratings on page 20)
 Branch neutral terminals suitable for one #14#4 AWG copper or one 
#12#4 AWG aluminum wire
 Three #141/0 AWG copper or #14#6 AWG aluminum terminals 
provided on 1242  circuits, 100 225 A load centers
 Suitable lugs provided on the neutrals for termination of the grounding 
conductor
 All unused neutral terminals may be used to terminate bare or green 
equipment grounding conductors when the load center is used as 
service equipment:
 one or two #14# 12 AWG copper
 one or two #12# 10 AWG aluminum
Tandem circuit breaker mounts on rails.
Branch Circuit Breaker
Neutral assemblies accept copper or aluminum wire.