Specification

Homeline
®
Circuit Breakers and Load Centers—Class 1170
Main Lugs and Main Circuit Breakers Ratings
51
03/2007
© 2007 Schneider Electric All Rights Reserved
Single-Phase, Three-Wire, 120/240 Vac Main Lugs  Rainproof
Mains
Rating
in
Amps
Load
Center Catalog
Number
Load
C e n t e r C o v e r
Catalog
Number
UL Li ste d
S er v ic e
Equipment
(See Notes)
Maximum
UL Short
Circuit
Rating
1
1
UL short circuit rating with optional QOM-VH main circuit breaker, 22,000 AIR.
A UL Listed as suitable for use as service equipment (neutral bonded at time of installation) with factory-installed service disconnect.
B UL Listed as suitable for use as service equipment (neutral bonded at time of installation) with field-installed service disconnect.
C UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with field-installed main lugs when not more than six service
disconnecting means are provided and when not used as a lighting and appliance branch circuit panelboard.
M a i n W i r e S i z e
AWG/kcmil
Al/Cu
Enclosure
No.
(Page 28)
Top or
Bottom
Mains
Position
UL Listed for
Corner Grounded
Delta Systems
Fixed Mains – Factory-Installed Main Lugs
70 HOM24L70RB Included B 10,000 A
#123 Al
#144 Cu
1R Top No
100 HOM612L100RB Included B, C 10,000 A #8 1 2R Top No
125 HOM48L125GRB Included B, C 10,000 A
#122/ 0 Al
#14 2/0 Cu
16R Top No
Convertible Mains – Factory-Installed Main Lugs – QOM1 Main Frame Size – Convertible to 22,000 AIR Main Circuit Breaker
125
HOM816L125RB Included B, C 10,000 A #62 /0 3R Top
No
HOM12L125RB Included B, C 10,000 A #62 /0 3R Top
HOM1224L125RB Included B, C 10,000 A #62 /0 3R Top
HOM20L125RB Included B, C 10,000 A #62 /0 4R Top
Convertible Mains – Factory-Installed Main Lugs – QOM2 Main Frame Size – Convertible to 22,000 AIR Main Circuit Breaker
200
HOM12L200RB Included B, C 10,000 A #6 250 5R Top
No
HOM2040L200RB Included B, C 10,000 A #6 250 6R Top
HOM30L200RB Included B, C 10,000 A #6 250 7R Top
HOM40L200RB Included B, C 10,000 A #6 250 8R Top
Single-Phase Three Wire 120/240 Vac Main Breaker  Rainproof
Convertible Mains – Factory-Installed Main Circuit Breaker
QOM1 Main Frame Size – Convertible to Main Lugs or Lower Amperage Main Circuit Breaker
100
HOM816M100RB Included A, C 22,000 A #42 /0 3R Top
No
HOM12M100RB Included A, C 22,000 A #42 /0 3R Top
HOM20M100RB Included A, C 22,000 A #42 /0 4R Top
HOM24M100RB Included A, C 22,000 A #42 /0 6R Top
125 HOM24M125RB Included A, C 22,000 A #42 /0 6R Top No
Convertible Mains – Factory-Installed Main Circuit Breaker
QOM2 Main Frame Size – Convertible to Main Lugs or Lower Amperage Main Circuit Breaker
150 HOM30M150RB Included A, C 22,000 A #4 250 7R Top No
200
HOM2040M200RB Included A, C 22,000 A #4 250 6R Top
No
HOM30M200RB Included A, C 22,000 A #4 250 7R Top
HOM3040M200RB Included A, C 22,000 A #4 250 7R Top
HOM40M200RB Included A, C 22,000 A #4 250 8R Top
225
HOM1624M225RB Included A, C 22,000 A #4-250 Top
No
HOM42M225RB Included A, C 22,000 A #4-250 Top
Factory-Installed Main Circuit Breaker with Feed-Thru Lugs
150 HOM816M150FTRB Included A, C 22,000 A #4 250 6R Top No
200 HOM816M200FTRB Included A, C 22,000 A #4 250 6R Top No
Universal Main Circuit Breaker with Feed-Thru Lugs
200 HOM816U200FTRB Included B 22,000 A #4 250 6R Top No