QO® and Homeline® Load Centers and Enclosures Catalog Class 1100 1100CT0501 2007 CONTENTS Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page QO® Circuit Breakers and Load Centers . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 QO®, QOM2 and Q-Frame Enclosed Circuit Breakers . . . . . . . . . . . . . . . 34 Homeline® Circuit Breakers and Load Centers . . . . . . . . . . . . . . . . . . . . .
QO® and Homeline® Load Centers and Enclosures Table of Contents TABLE OF CONTENTS Product Description 3 Features 3 QO® Catalog Number Description 4 General information and Application Data 5 Service 5 Ratings 5 Branch Circuit Breakers 5 Indoor Enclosures (Type 1) 6 Indoor Covers 6 Rainproof Enclosures (Type 3R) 6 Bolt-On Hubs 6 Class CTL 7 Phasing 7 Line Lugs 7 Neutral Assemblies 7 Single Phase, 2 16 Circuits, 30 125 A, Fixed Mains 8 Single-Phase,12 42 Circuits, 100 225 A, Convertible Mains 9 Special Purpos
QO® and Homeline® Load Centers and Enclosures Product Description PRODUCT DESCRIPTION QO® Circuit Breaker Load Centers from Square D® are Underwriters Laboratories (UL) Listed panelboards. They are designed to meet residential, commercial, and industrial requirements to protect electrical systems, equipment, and people.
QO® and Homeline® Load Centers and Enclosures Catalog Number Description CATALOG NUMBER DESCRIPTION QO® Load Centers Number Segment Load Center Family Character Description QO® UL and NOM Listed CQO CSA® Certified Phase 1 Spaces / Circuits 3040 Mains Type QO® 1 3040 L 200 G — — Blank or 1 = Single 3 = Three M Main circuit breaker MX Main circuit breaker for Automatic Transfer Switch L Main lugs U Universal mains (studs only) Blank Purchase separately G Included N Neutral in
QO® and Homeline® Load Centers and Enclosures General Information and Application Data GENERAL INFORMATION AND APPLICATION DATA Circuit breaker load centers for use on electrical systems are UL Listed under File E-6294 (panelboards) and meet Federal Specifications W-P-115c, Type 1, Class 2 for use in government housing.
QO® and Homeline® Load Centers and Enclosures General Information and Application Data Indoor Enclosures (Type 1) Welded sheet steel with knockouts at top, bottom, back, and sides Finish: gray baked enamel, electrodeposited over cleaned, phosphatized steel Most 100 225 A indoor enclosures are 14.25 in. (362 mm) wide (see Dimensions and Knockouts on page 26) 300 A and 400 A indoor enclosures are 20 in.
QO® and Homeline® Load Centers and Enclosures General Information and Application Data Class CTL Class CTL load centers are UL Listed Circuit breaker mounting rails have slots to accept tandem circuit breakers, on specified load centers Meets paragraph 408.
QO® and Homeline® Load Centers and Enclosures General Information and Application Data Single Phase, 2–16 Circuits, 30–125 A, Fixed Mains UL Listed File E-6294 Suitable for use as service equipment 75 °C wire rating (see Technical Information on page 20) Federal Specification W-P-115c, Type 1, Class 2 CSA Certified File LL-89066-21 For other CSA certified load centers, see Supplemental Digest 174.
QO® and Homeline® Load Centers and Enclosures General Information and Application Data Single-Phase, 12–42 Circuits, 100–225 A, Convertible Mains UL Listed File E-6294 Federal Specification W-P-115c, Type 1, Class 2 Suitable for use as service equipment 75 °C wire rating (see Technical Information on page 20) Short Circuit Current Rating Main Circuit Breaker Main lugs: up to 65,000 AIR (depends on lowest interrupting rating of branch circuit breakers installed) Main circuit breaker: 22,000 AIR standard 22,
QO® and Homeline® Load Centers and Enclosures General Information and Application Data Single-Phase, 12–42 Circuits, 100–225 A, Convertible Mains, Continued Covers Flush and surface covers sold separately Flush covers have spring-loaded interior trim for automatic flush adjustment Positive action, easy-open door latch Main Lugs Kits Field-installable in main circuit breaker or main lugs load centers QOL125 kit for use in 100 125 A load centers QOL225 kit for use in 150 225 A load centers Main Circuit Breake
QO® and Homeline® Load Centers and Enclosures General Information and Application Data Special Purpose Recreational Vehicle and Manufactured Housing Load Centers UL Listed (File E-6294) and CSA Certified (LL89066-14) Single-phase, 2- and 3-wire Factory-installed equipment grounding bar Covers included with load centers Load Centers with Covers QO2L30TTS Combination flush/surface cover included with load centers Equipment grounding bar included on main lug load centers Top or bottom feed on incoming service
QO® and Homeline® Load Centers and Enclosures General Information and Application Data Generator Panels Generator Panel Manu al Transfer Connects utility and standby power to installed branch circuits Includes two factory-installed 2-pole main circuit breakers tied together with a mechanical interlock 30 A and 60 A main circuit breaker versions Supply up to 8 branch circuits using tandem circuit breakers Available indoor enclosure only Cover with door included QO48M60DSGP Generator Panel Automatic Transfe
QO® and Homeline® Load Centers and Enclosures General Information and Application Data Three-Phase, 3–42 Circuits, 60–225 A, Convertible or Fixed Mains UL Listed File E-6294 Suitable for use as service equipment 75 °C wire rating (see Technical Information on page 19) Short Circuit Current Rating Main lugs: up to 65,000 AIR (depends on lowest interrupting rating of branch circuit breakers installed) Main circuit breaker up to 225 A: 22,000 AIR standard; optional up to 65,000 AIR for 100 A to 225 A main circ
QO® and Homeline® Load Centers and Enclosures General Information and Application Data Three-Phase, 3–42 Circuits, 60–225 A, Convertible or Fixed Mains (Continued) Main Lugs Kits Field-installable in main circuit breaker or main lugs load centers QOL3125 kit for use in 100 125 A load centers QOL3225 kit for use in 150 225 A load centers Main Circuit Breakers Field-installable in main circuit breaker load centers 25,000 AIR QDL main circuit breakers series rated with 10,000 AIR QO® branch circuit breakers 1
QO® and Homeline® Load Centers and Enclosures General Information and Application Data Single-Phase, 12–42 Circuits, 300–400 A, Fixed Mains UL Listed File E-6294 Suitable for use as service equipment 75 °C wire rating (see Technical Information on page 20) Short Circuit Current Rating Main lugs: up to 65,000 AIR Main circuit breaker: 42,000 AIR fully rated (see Technical Information on page 20) Mains Factory-installed main lugs and main circuit breaker Multiple wire terminals for phases and neutral Top or b
QO® Circuit Breaker Load Centers—Class 1130 General Information and Application Data Accessories Grounding Bar Kits Field-installable in all load centers Same wire size as terminals (see page 19) PG18GTA Grounding Bar Kit Suitable for copper or aluminum wire Available with #1 4/0 lug PK15GTA-L, PK18GTA-L, and PK23GTA-L (see page 19) Flush Lock Kits Available for indoor load centers Two keys provided with each lock kit PK6FL for convertible 12 42 circuit load centers PK4FL for 300 and 400 A load centers PK
QO® and Homeline® Load Centers and Enclosures General Information and Application Data Accessories (Continued) Surgebreaker® Secondary Surge Arrester QO2175SB UL Listed secondary surge arrester Easy plug-on installation for QO® load centers LED indicates operational status Plug-on design requires two pole spaces Designed to protect electrical service and major household appliances , excluding electronic devices Back-Fed Main Circuit Breaker Retaining Kits Back-fed main circuit breaker retaining kits secure
QO® Circuit Breaker Load Centers—Class 1130 General Information and Application Data Accessories (Continued) Auxiliary Gutters and Tap Kits Field-installable on the left or right side of load centers Auxiliary gutters are 13.50 in. wide x 26.12 in. height x 3.75 in. deep Conduit riser sizes: 1-3/4, 2, 2-1/2 or 3 in. (3 in.
QO® and Homeline® Load Centers and Enclosures Technical Information TECHNICAL INFORMATION Slot / Robertson screw Grounding Bar Kits 0.437 [11] All PK equipment grounding kits are supplied with mounting screws, necessary installation instructions, and an Equipment Grounding Terminal self-adhesive label. Terminals Catalog Number 0.3125 [8] Quantity Each Size See “Wire Range Table” below. I Cross Section of Size 1 Ground Bar in.
QO® Circuit Breaker Load Centers—Class 1130 Technical Information Main Lugs and Main Circuit Breaker Ratings Single-Phase, Three-Wire, 120/240 Vac; Main Lugs Mains Rating in Amps Load Center Catalog Number Load Center Cover Catalog Number Indoor UL Listed Service Equipment (See notes) Maximum UL Short Circuit Rating 1 Main Wire Size AWG/kcmil Al/Cu Enclosure No.
QO® and Homeline® Load Centers and Enclosures Technical Information Single-Phase, Three-Wire, 120/240 Vac; Main Circuit Breaker Ind oor Mains Rating in Amps Load Center Catalog Number Load Center Cover Catalog Number UL Listed Service Equipment (See Notes) Maximum UL Short Circuit Rating 1 Main Wire Size AWG/kcmil Al/Cu Enclosure No.
QO® and Homeline® Load Centers and Enclosures Technical Information Single-Phase, Three-Wire, 120/240 Vac; Main Lugs Mains Rating in Amps Load Center Catalog Number Load Center Cover Catalog Number 1 Rainproof UL Listed Service Equipment (See Notes) Maximum UL Short Circuit Rating 2 Main Wire Size AWG/kcmil Al/Cu Enclosure No.
QO® and Homeline® Load Centers and Enclosures Technical Information Single-Phase, Three-Wire, 120/240 Vac; Main Circuit Breaker Mains Rating in Amps Load Center Catalog Number Load Center Cover Catalog Number 1 UL Listed Service Equipment (See Notes) Rainproof Maximum UL Short Circuit Rating 2 Main Wire Size AWG/kcmil Al/Cu Enclosure No.
QO® Circuit Breaker Load Centers—Class 1130 Technical Information 3-Phase, 4-Wire, 208Y/120 Vac; 3-Phase, 4-Wire, 240/120 Vac, Delta; 3-Phase, 3-Wire, 240 Vac, Delta; Main Lugs, Main Circuit Breaker In door Mains Rating in Amps Load Center Catalog Number UL Listed Load Center Service Cover Catalog Equipment Number (See Notes) Maximum UL Short Circuit Rating 1 Main Wire Size AWG/kcmil Al/Cu Enclosure No.
QO® and Homeline® Load Centers and Enclosures Technical Information Mains Rating in Amps Load Center Catalog Number Load Center Cover Catalog Number UL Listed Service Equipment (See Notes) Maximum UL Short Circuit Rating 1 Main Wire Size AWG/kcmil Al/Cu Enclosure No.
QO® Circuit Breaker Load Centers—Class 1130 Indoor Dimensions W Indoor Dimensions H D Box No. in. mm in. mm in. mm 1 3.81 97 6.72 171 3.00 76 2 4.81 122 9.30 236 3.19 3 4.81 122 9.30 236 3.19 4 8.88 226 12.57 319 5 14.25 362 14.92 6 14.25 362 17.92 7 14.25 362 8 14.25 362 9 14.25 10 11 12 W Box No. H A D in. mm in. mm in. mm 13 5.88 149 13.12 333 3.38 86 81 14 14.25 362 20.92 531 3.75 95 81 15 20.00 508 50.00 1270 5.
QO® and Homeline® Load Centers and Enclosures Outdoor Dimensions and Knockouts OUTDOOR DIMENSIONS AND KNOCKOUTS 2.5 in. (64 mm) Hub Max. Outdoor Dimensions 2.5 in. (64 mm) Hub Max. W H D Box No. Box 1NM Box 1R Box 2R 2.5 in. (64 mm) Hub Max. 2.5 in. (64 mm) Hub Max. C, D, E F, G C, D, C, D, E, F E, F A A, C, D, A, B, C B E, F, G C, D, E F C, D, E F, G C A A, C, D,A,EB, F, G B Box 3R, 4R Box 5R 1 2.5 in. (64 mm) Hub Max. in. mm in. mm 1NM 6.52 166 8.79 223 3.90 99 1R1 4.
QO® Circuit Breaker Load Centers—Class 1130 QO Single-Phase Labels QO SINGLE-PHASE LABELS The labels below represent typical labels. Information may not be applicable or may change without notice. See the actual label in the load center for the latest information. QO Single-Phase Box Label Sample Number of circuits maximum. Enclosure catalog number. Catalog number of covers; flush or surface. See panelboard interior for the catalog number. Voltage ratings. Amperage rating.
QO® and Homeline® Load Centers and Enclosures QO Three-Phase Label Samples QO THREE-PHASE LABEL SAMPLES The labels below represent typical labels. Information may not be applicable or may change without notice. See the actual label in the load center for the latest information. QO Three-Phase Box Label Sample Number of circuits maximum. Enclosure catalog number. Catalog number of covers; flush or surface. See panelboard interior for the catalog number. Voltage ratings. Amperage rating.
QO® Circuit Breaker Load Centers—Class 1130 Wiring Diagrams WIRING DIAGRAMS G/B S N S N QO2L30S QO2L40RB G/B S N S N G B QO2L30TTS S N QO24L70F/S QO24L70RB QO24L60NRNM S/N QO24L70TS S N S/N S/N S N G B S N QO612L100F/S QO612L100DF/S QO612L100DFCU/SCU QO612L100RB QO612L100RBCU Line QO816L100TF/S QO816L100DTF/S S N S N QO24L50TTS S N S N S N S/N G B QO816L100F/S QO816L100DF/S QO816L100DFCU/SCU QO816L100RB QO816L100RBCU G B QO35FM30TTF/S QO12030L150G QO120L125G QO120L125GC S N
QO® and Homeline® Load Centers and Enclosures Wiring Diagrams S N S N MAIN MAIN S N S N S N MAIN S N S N MAIN S N MAIN S N S N S N S F S N MAIN QO112M100 QO112M100RB QO112M100C QO1816M150FTRB QO1816M200FTRB QO1612M125FTRB S N S N MAIN QO116M100 QO116M100RB QO116M100C S N S N MAIN QO1428MX150FTRB QO1428MX200FTRB QO1428UX200FTRB S N S N QO120M100 QO120M100RB QO120M100C QO12030M150 QO12030M150RB QO12030M150C S N S N MAIN MAIN S N S N S N QO130M150 QO130M200 QO130M150RB
QO® Circuit Breaker Load Centers—Class 1130 Wiring Diagrams S N S N S N S N S N S N S N QO403L60NF/S QO403L60NRB QO312L125G QO312L125GRB QO320L125G QO320L125GRB S N S N S N S N S N QO318L200G QO318L200GRB S N QO324L125G QO330L200G QO330L200GRB QO342L225G QO342L225GRB 3-Phase, 4-Wire Main Lugs S N S N MAIN S N S N S N MAIN S N M A I N QO327M100 QO327M100RB QO330MQ125 QO330MQ150 QO330MQ200 QO330MQ125RB QO330MQ150RB QO330MQ200RB QO342MQ150 QO342MQ200 QO342MQ225 QO342MQ200RB QO342MQ2
QO®, QOM2 and Q-Frame Enclosed Circuit Breakers—Class 1131 Table of Contents TABLE OF CONTENTS General Information and Application Data 34 Type 34 Service 34 Ratings 34 Enclosure 34 Type 3R Rainproof 34 Circuit Breakers 35 Knockouts 35 Equipment Grounding Bar 35 Neutral Assemblies 35 Bolt-On Hubs 35 Technical Information 36 Enclosed Molded-Case Circuit Breaker Ratings 36 Dimensions and Knockouts 37 NOTE: For information on Replacement Parts with specific part numbers, go to www.schneider-electric.
QO®, QOM2 and Q-Frame Enclosed Circuit Breakers—Class 1131 General Information and Application Data GENERAL INFORMATION AND APPLICATION DATA Type Enclosed molded case circuit breakers are UL® Listed; File E136861, for enclosures and File E10027 for circuit breakers. Molded case circuit breakers meet Federal Specifications W-C-375-B. Enclosed molded case switches are UL Listed under File E59921.
QO®, QOM2 and Q-Frame Enclosed Circuit Breakers—Class 1131 General Information and Application Data Circuit Breakers Visi-Trip® indication (QO® circuit breakers) Lugs suitable for aluminum or copper wire (refer to catalog sections listed below:) QOM2200VH QO Class 730 QB, QD, QG and QJ Class 734 QOM2 Class 736 Molded-case switches Class 601 Knockouts Located in back, side and bottom of all devices Equipment Grounding Bar Field-installable PKOGTA2 Suitable for #6 AWG 2/0 aluminum or #10 AWG 2/0 AW
QO®, QOM2 and Q-Frame Enclosed Circuit Breakers—Class 1131 Technical Information TECHNICAL INFORMATION Enclosed Molded-Case Circuit Breaker Ratings Circuit Breaker 1 Enclosure Service Rating in Amperes Type 1 Catalog Number Enclosure UL® Listed No.
QO®, QOM2 and Q-Frame Enclosed Circuit Breakers—Class 1131 Dimensions and Knockouts DIMENSIONS AND KNOCKOUTS Dimensions W Enclosure No. H D in. mm in. mm in. mm 1 5.88 149 13.12 333 3.38 86 2 5.88 149 16.12 409 3.38 86 1R 4.56 116 6.50 165 3.88 99 2R 6.92 176 13.12 333 4.12 105 3R 6.92 176 16.12 409 4.12 105 3 7.56 192 23.12 587 4.25 108 4 9.62 244 26.12 663 4.75 121 4R 7.56 192 23.24 590 4.75 121 5R 9.62 244 26.24 666 5.50 140 6 8.
QO®, QOM2 and Q-Frame Enclosed Circuit Breakers—Class 1131 Dimensions and Knockouts 38 © 2007 Schneider Electric All Rights Reserved 03/2007
Homeline® Circuit Breakers and Load Centers—Class 1170 Table of Contents TABLE OF CONTENTS Product Description 40 Features 40 Homeline® Catalog Number Description 41 General Information and Application Data 42 Type 42 Service 42 Ratings 42 UL Listed 42 Class CTL 42 Branch Circuit Breakers 42 Main Circuit Breaker QOM-VH 42 Indoor Enclosures (NEMA Type 1) 43 Indoor Covers 43 Rainproof Enclosures (NEMA Type 3R) 43 Bolt-On Hubs 43 Single-Phase, 2 12 Circuits, 70 125 A, Fixed Mains 44 Single-Phase, 12 4 2 Circu
Homeline® Circuit Breakers and Load Centers—Class 1170 Product Description PRODUCT DESCRIPTION Homeline® circuit breaker load centers from Square D® are UL Listed panelboards. They are designed to meet residential, commercial, and industrial requirements to protect electrical systems, equipment, and people.
Homeline® Circuit Breakers and Load Centers—Class 1170 Product Description Homeline® Load Centers Number Segment Character Description Load Center Family HOM UL Listed Spaces / Circuits 3040 M Main circuit breaker Mains Type L Main lugs U Universal mains HOM 3040 L 200 — C Amps Ground Bar Special Construction Cover G Factory included T Factory-installed Blank Purchase separately FT Feed-thru C Combination flush / surface indoor cover F Flush RB Rainproof S Surface Homel
Homeline® Circuit Breakers and Load Centers—Class 1170 General Information and Application Data GENERAL INFORMATION AND APPLICATION DATA Type Circuit breaker load centers for use on ac systems. They are UL Listed under file E-6294 (panelboards) and meet Federal Specifications W-P-115b NEMA Type 1, Class 2.
Homeline® Circuit Breakers and Load Centers—Class 1170 General Information and Application Data Indoor Enclosures (NEMA Type 1) Welded sheet steel with knockouts at top, bottom, back and sides Finish: gray baked enamel electrodeposited over cleaned, phosphatized steel Most indoor enclosures are 14.
Homeline® Circuit Breakers and Load Centers—Class 1170 General Information and Application Data Single-Phase, 2–12 Circuits, 70–125 A, Fixed Mains UL Listed File E-6294 Suitable for use as service equipment 75 °C wire rating (see Technical Information on page 49) Short Circuit Current Rating Main lugs: up to 10,000 AIR (see Technical Information on page 49) Interior Tin plated aluminum bus Mains HOM612L100F Factory-installed fixed main lugs Top mains positioning only Top or bottom feed (see Technical Infor
Homeline® Circuit Breakers and Load Centers—Class 1170 General Information and Application Data Single-Phase, 12–42 Circuit, 100–225 A, Convertible Mains, Continued Cover Combination flush and surface cover included with load centers Optional door lock kit for indoor load centers Positive action, easy open door latch Main Circuit Breaker with Feed-Thru Lugs Rainproof only, side hinged 150 and 200 A mains rating Space for up to 8 single-pole circuit breakers Factory-installed main circuit breaker Factory-ins
Homeline® Circuit Breakers and Load Centers—Class 1170 General Information and Application Data Accessories Bolt-On Hubs Equipment with an RB suffix, meaning Rainproof NEMA Type 3R construction, uses the bolt-on hubs listed below. RB de vices will accept 0.75 in (19 mm) through 2.50 in (64 mm) bolt-on hubs without the use of reducers. Off-center conduit thread openings and elongated mounting holes provide quick and easy adjustment to eliminate costly conduit offsets and bends.
Homeline® Circuit Breakers and Load Centers—Class 1170 General Information and Application Data Back-Fed Main Circuit Breaker Retaining Kits HOM1RK: secures circuit breaker to interior when used as back-fed main for HOM612L100F/S and RB load centers HOM4RK2LA: mounts on the right side of HOM 100 125 A convertible main load centers, series S01 and S02 (retains one 2-pole HOM circuit breaker) HOM4RK2HA: mounts on the right side of HOM 150 2 25 A convertible main load centers, series S01 and S02 (retains one 2
Homeline® Circuit Breakers and Load Centers—Class 1170 Technical Information TECHNICAL INFORMATION Grounding Bar Kits Slot / Robertson screw All PK equipment grounding bar kits are supplied with mounting screws, necessary installation instructions and an Equipment Grounding Terminal self-adhesive label. Terminals 0.437 [11] Catalog Number Quantity Each Size See “Wire Range Table” below. Total Qty. I 0.
Homeline® Circuit Breakers and Load Centers—Class 1170 Main Lugs and Main Circuit Breakers Ratings MAIN LUGS AND MAIN CIRCUIT BREAKERS RATINGS Single-Phase, Three-Wire, 120/240 Vac Main Lugs Mains Rating in Amps Load Center Catalog Number LoadCenter Cover Catalog Number Indoor UL Listed Service Equipment (See Notes) Maximum UL Short Circuit Rating 1 B 10,000 A Main Wire Size AWG/kcmil Al/Cu Enclosure No.
Homeline® Circuit Breakers and Load Centers—Class 1170 Main Lugs and Main Circuit Breakers Ratings Single-Phase, Three-Wire, 120/240 Vac Main Circuit Breaker Mains Rating in Amps Load Center Catalog Number Load Center Cover Catalog Number UL Listed Service Equipment (See Notes) Indoor Maximum UL Short Circuit Rating 1▲ Main Wire Size AWG/kcmil Al/Cu Enclosure No.
Homeline® Circuit Breakers and Load Centers—Class 1170 Main Lugs and Main Circuit Breakers Ratings Single-Phase, Three-Wire, 120/240 Vac Main Lugs Mains Rating in Amps Load Center Catalog Number Load Center Cover Catalog Number Rainproof UL Listed Service Equipment (See Notes) Maximum Main Wire Size UL Short AWG/kcmil Circuit Al/Cu Rating 1▲ Enclosure No.
Homeline® Circuit Breakers and Load Centers—Class 1170 Homeline Label Samples HOMELINE LABEL SAMPLES For information on two-tier and three-tier series ratings, see Data Bulletin number 4100DB0301, Square D® Load Center Short Circuit Current Ratings , located on the Technical Library at www.SquareD.com. Homeline Box Label Sample Number of circuits maximum. Enclosure catalog number. Catalog number of covers; flush or surface. See panelboard interior for the catalog number. Voltage ratings. Amperage rating.
Homeline® Circuit Breakers and Load Centers—Class 1170 Wiring Diagrams WIRING DIAGRAMS S/N S N S/N S N S N HOM24L70F/S HOM24L70RB HOM48L125GC HOM48L125GRB S N S N HOM612L100F/S HOM612L100RB S N S N S N G B HOM816L125TC S N HOM12L125C HOM12L125RB HOM12L200RB S N HOM20L125C HOM20L125RB S N S N S N HOM1224L125RB HOM1624L125C S N S N G B HOM1632L200TC HOM246125TC S N S N S N HOM1632L200TCFT S N S N HOM2040L200TC G B HOM30L150C HOM30L200C HOM30L200RB HOM30L200TC HOM3040L200TC
Homeline® Circuit Breakers and Load Centers—Class 1170 Wiring Diagrams S N S N MAIN S N HOM816M100C HOM816M100RB S N S N MAIN G B HOM816M100TC S N S N MAIN HOM12M100C HOM12M100RB HOM816M150FTRB HOM816M200FTRB S N S N S N S N MAIN HOM1224M100TC HOM1224M125TC HOM1224M200TC HOM1224M125C S N S N MAIN S N MAIN S N MAIN G B HOM1624M225RB HOM1632M150TC HOM1632M200TC MAIN S N S N G B HOM2030M150TC MAIN S N S N HOM2040M200C HOM2040M200RB S N G B HOM20M100C HOM20M100RB MAIN
QO® and Homeline® Load Centers and Enclosures Index 1100CT0501 03/2007 INDEX A F N accessories cover filler plates 16, 46 flush lock kits 16, 47 generator circuit breaker interlock kit 17, 47 grounding bar kits 16, 19, 51 manual transfer equipment kit 17 secondary surge arrester 17, 46 assemblies base 35 neutral 7, 35 auxiliary gutters and tap kits 18 neutral lugs 16, 46 feed-thru lugs 11, 45, 53, 51 universal main 45, 47 fixed main lugs, single-phase 8, 15, 20, 45, 47 main lugs, three-phase 13 mains,
QO® and Homeline® Circuit Breaker Load Centers and Enclosures Catalog Schneider Electric USA 1601 Mercer Road Lexington, KY 40511 USA 1-888-SquareD (1-888-778-2733) www.us.SquareD.com Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. 1100CT0501 © 2007 Schneider Electric All Rights Reserved Replaces 1100CT9901 dated September 2000.