Specification

Homeline
®
Circuit Breakers and Load Centers—Class 1170
General Information and Application Data
44
© 2007 Schneider Electric All Rights Reserved 03/2007
Single-Phase, 2–12 Circuits, 70–125 A, Fixed Mains
UL Listed
File E-6294
Suitable for use as service equipment
75 °C wire rating (see Technical Information on page 49)
Short Circuit Current Rating
Main lugs: up to 10,000 AIR (see Technical Information on page 49)
Interior
Tin plated aluminum bus
Mains
Factory-installed fixed main lugs
Top mains positioning only
Top or bottom feed (see Technical Information on page 49)
A backfed main circuit breaker can be field installed in a 612 load
center using the HOM1RK retaining kit
Cover
Combination flush and surface cover
Single-Phase, 12–42 Circuits, 100–225 A, Convertible Mains
UL Listed
File E-6294
Suitable for use as service equipment
75 °C wire rating (see Technical Information on page 48)
Short Circuit Current Rating
Main lugs: up to 10,000 AIR
Main circuit breaker: 22,000 AIR standard (see Technical Information
on page 48)
Interior
Tin plated aluminum bus
Removable interior with single, captive mounting screw
Split branch neutral with up to 50% more terminations than required
Multiple mounting locations for equipment ground bar kits: left, right, bottom
Mains
HOM612L100F
Flush Cover
Combination Cover with Door
Factory-Installed Main Lugs
Convertible to Main Circuit Breaker
Factory-Installed Main Circuit Breaker
Convertible to Main Lugs
Load Center
Amperage
Main Circuit
Breaker Kit
Amperage
Main Circuit
Breaker
Amperage
Main Lug
Kit
Amperage
Load
Center
Amperage
125 50 - 125 100 125 100
150 100 - 150 125 125 125
200 100 - 200 150 225 150
225 100 - 225 200 225 200
225 225 225
Top or bottom mains positioning, by rotating the complete indoor load center 180 degrees.
(see Technical Information on page 48)