Specification

QO
®
and Homeline
®
Load Centers and Enclosures
Technical Information
25
03/2007
© 2007 Schneider Electric All Rights Reserved
Mains
Rating
in
Amps
Load Center
Catalog Number
Load Center
Cover
Catalog
Number
UL
Listed Service
Equipment
(See Notes)
Maximum UL
Short
Circuit Rating
1
M a i n W i r e S i z e
AWG/kcmil
Al/Cu
Enclosure
No.
(Pages 26
and 27)
Top or Bottom
Mains Position
UL Listed for
Corner Grounded
Delta Systems
Load Center with Cover – 1-Phase, 3-Wire, 120/240 Vac – UL Listed; Complete QO
®
Load Center – Box, Interior and Combination Cover (in one package)
Convertible Mains – Factory-Installed Main Lugs; QOM1 Main Frame Size – Convertible to Main Circuit Breaker – Copper Bus
125
QO112L125GC Included B, C 65,000 A
2
3
#42 /0 6 Both Yes
QO11224L125GC Included B, C 65,000 A
2
3
#42 /0 6 Both Yes
QO120L125GC Included B, C 65,000 A
2
3
#42 /0 7 Both Yes
Convertible Mains – Factory-Installed Main Lugs; QOM2 Main Frame Size – Convertible to Main Circuit Breaker – Copper Bus
150 QO130L150TC Included B, C 65,000 A
2
3
#42 50 9 Both Yes
200 QO13040L200GC Included B, C 65,000 A
2
3
#42 50 9 Both Yes
Convertible Mains – Factory-Installed Main Circuit Breaker – 22,000 RMS Symmetrical Amperes Short Circuit Current Rating
QOM1 Main Frame Size – Convertible to Main Lugs – Copper Bus
100
QO112M100C Included A, D 22,000 A
2
#4-1/0 5 Both Yes
QO11220M100C Included A, D 22,000 A
2
#4-1/0 5 Both Yes
QO116M100C Included A, D 22,000 A
2
#4-1/0 6 Both Yes
QO120M100C Included A, D 22,000 A
2
#4-1/0 6 Both Yes
Convertible Mains – Factory-Installed Main Circuit Breaker – 22,000 RMS Sym. Amperes Short Circuit Current Rating
QOM2 Main Frame Size – Convertible to Main Lugs – Copper Bus
150
QO12030M150C Included A, D 22,000 A
2
#42 50 9 Both No
QO130M150C Included A, D 22,000 A
2
#42 50 9 Both No
200 A
QO12040M200C Included A, D 22,000 A
2
#42 50 9 Both No
QO130M200C Included A, D 22,000 A
2
#42 50 9 Both No
QO13040M200C Included A, D 22,000 A
2
#42 50 9 Both No
QO140M200C Included A, D 22,000 A
2
#42 50 10 Both No
Non-Metallic 1-Phase, 3-Wire, 120/240 Vac – Main Lugs Only
60 QO24L60NRNM Included B, C 10,000 A #14 4 1NM Bottom No
Riser , 1-Phase, 3-Wire, 120/240 Vac – Factory-Installed Main Lugs – Offset Interior Wide Gutter QOM1/QOM2
4
Main Frame Size – Convertible to Main Circuit Breaker – Copper Bus
3
125
QO11224L125WG
QOC20UFWG
B, C 65,000 A
2
#42 /0 14 Both
Yes
QO12030L125WG B 65,000 A
2
#42 /0 14 Both
200
QO13040L200WG
QOC30UFW
B, C 65,000 A #42 50 23 Both
Ye s
Generator Panel, 1-Phase, 3-Wire, 120/240 Vac – Factory-Installed Main Circuit Breakers with Mechanical Interlock
30 QO48M30DSGP
Included
No 10,000 A #148 4 Bottom
No
60 QO48M60DSGP A 10,000 A #8 2 4 Bottom
Generator Panel - Use with Automatic Transfer Switch, 1-Phase, 3-Wire, 120 / 240 Vac, Factory- / Field-Installed Main Circuit Breaker –
22,000 RMS Sym. Amperes Short Circuit Current Rating
5
150 QO13842MX150
QOC38MXUF
A 22,000 A #4-250 12 Both No
200 QO13842MX200 A 22,000 A #4-250 12 Both No
225
QO13842MX225 A 22,000 A #4-250 12 Both No
QO13842UX225 B 22,000 A #4-250 12 Both No
150
QO11428MX150FTRB
6
Included A 22,000 A #4-250 7R Both No
200
QO11428MX200FTRB
6
Included A 22,000 A #4-250 7R Both No
QO11428UX200FTRB
6
Included B 22,000 A #4-250 7R Both No
1
Short circuit current rating depends on lowest AIR rating of main or branch circuit breaker installed.
2
22,000 A rms symmetrical maximum when supplied by integral type QOM-VH main circuit breaker from Square D
®
with 22,000 A rms symmetrical minimum interrupting rating
and when all installed QO
®
branch circuit breakers have 10,000 A rms symmetrical minimum interrupting rating.
3
UL Listed for 5000 A rms symmetrical short circuit rating when used in 3-phase, 240 Vac, corner grounded Delta systems, when used as main lugs load center only. Use QO-
H 240 Vac circuit breakers only.
4
QOM2 Load Center is ONLY convertible to main circuit breaker when used with QOC cover.
5
One main circuit breaker is included with panel. Alternate source main circuit breaker (QO 125 A max.) must be ordered separately. Automatic transfer switch and generator kit
for secondary power sources are ordered through a Kohler
®
authorized dealer or contractor.
6
Side-hinge door device allow 1.25 in. (32mm) on the left side for the door to open.
A UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with factory-installed service disconnect.
B UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with field-installed service disconnect.
C UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) when not more than six service disconnecting means are provided and when not
used as a lighting and appliance branch circuit panelboard. See NEC Article for Lighting and Appliance Branch Circuit Panelboard.
D UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with field-installed main lugs and not more than six service disconnecting means
are provided and when not used as a lighting and appliance branch circuit panelboard. See NEC Article for Lighting and Appliance Branch Circuit Panelboard.