QO
®
Circuit Breaker Load Centers—Class 1130
Technical Information
3-Phase, 4-Wire, 208Y/120 Vac; 3-Phase, 4-Wire, 240/120 Vac, Delta;
3-Phase, 3-Wire, 240 Vac, Delta; Main Lugs, Main Circuit Breaker  In door
Mains
Rating
in Amps
Load Center
Catalog Number
Load Center
Cover Catalog
Number
UL Listed
Service
Equipment
(See Notes)
Maximum UL
Short Circuit
Rating
1
1
Short circuit current rating depends on lowest AIR rating of branch circuit breaker installed.
Ma i n Wi r e Si z e
AWG/kcmil
Al/Cu
Enclosure
No.
(Page 26)
Top or
Bottom
Mains
Position
UL Listed for
Corner
Grounded Delta
Systems
Fixed Mains – Factory-Installed Main Lugs – Copper Bus
60 QO403L60NF/S Included B 22,000 A
1
#10-6 13 Top No
125
QO312L125G
2
2
Certified to IEC 60439-1 for use on 415Y/240 Vac 3-phase 4-wire, 3,000 SCCR when QODX ... branch circuit breakers are used and 10,000 SCCR when QO...VS
branch circuit breakers are used. CE marked.
QOC16UF/S B, C 65,000 A
1
#62 /0 #62/ 0 6 Both
NoQO320L125G
2
QOC24UF/S B, C 65,000 A
1
#62 /0 #62/ 0 7 Both
QO324L125G
2
QOC24UF/S B, C 65,000 A
1
#62 /0 #62/ 0 7 Both
200
QO318L200G
2
QOC30UF/S B, C 65,000 A
1
#6 250 #62 50 9 Both
No
QO330L200G
2
QOC30UF/S B, C 65,000 A
1
#6 250 #62 50 9 Both
225 QO342L225G
2
QOC42UF/S B 65,000 A
1
#6 300 #63 00 11 Both No
Convertible Mains – Factory-Installed QDL Main Circuit Breaker – Copper Bus
100 QO327M100
3
3
Includes factory-installed back-fed QO3100VH main circuit breaker.
QOC30UF/S A, D 22,000 A #42 /0 #42/ 0 9 Both No
125 QO330MQ125
2
4
4
Mains positioning from top to bottom feed: first rotate the main circuit breaker 180 degrees, then rotate the complete load center 180 degrees.
QOC342MQF/S A, D 100,000 A
5
6
5
100,000 A rms at 208 Vac symmetrical maximum when type QJL main circuit breaker from Square D
®
with 100,000 A rms minimum interrupting rating is installed
and when all installed QO
®
and Q1 branch circuit breakers have 10,000 A rms symmetrical minimum interrupting rating.
6
25,000 A rms symmetrical maximum when supplied by integral type QDL main circuit breaker from Square D
®
with 25,000 A rms minimum interrupting rating and
when all installed QO
®
and Q1 branch circuit breakers have 10,000 A rms symmetrical minimum interrupting rating.
A UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with factory-installed service disconnect.
B UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with field-installed service disconnect.
C UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) when not more than six service disconnecting means are provided and
when not used as a lighting and appliance branch circuit panelboard. See NEC Section 384-14.
D UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with field-installed main lugs, when not more than six service
disconnecting means are provided and when not used as a lighting and appliance branch circuit panelboard. See NEC Article for Lighting and Appliance Branch
Circuit Panelboard.
#4 300 #43 00 12 H No
150
QO330MQ150
2
4
QOC342MQF/S A, D 100,000 A
5
6
#4 300 #43 00 12 H
No
QO342MQ150
2
4
QOC342MQF/S A, D 100,000 A
5
6
#4 300 #43 00 12 H
200
QO330MQ200
2
4
QOC342MQF/S A, D 100,000 A
5
6
#4 300 #43 00 12 H
No
QO342MQ200
2
4
QOC342MQF/S A, D 100,000 A
5
6
#4 300 #43 00 12 H
225 QO342MQ225
2
4
QOC342MQF/S A, D 100,000 A
5
6
#4 300 #43 00 12 H No