Specification

Homeline
®
Circuit Breakers and Load Centers—Class 1170
Main Lugs and Main Circuit Breakers Ratings
49
03/2007
© 2007 Schneider Electric All Rights Reserved
MAIN LUGS AND MAIN CIRCUIT BREAKERS RATINGS
Single-Phase, Three-Wire, 120/240 Vac Main Lugs  Indoor
Mains
Rating
in
Amps
Load Center
Catalog Number
L o a d C e n t e r
C o v er
Catalog
Number
UL Listed
Se rv ice
Equipment
(See Notes)
Maximum
UL Short
Circuit
Rating
1
M a i n W i r e S i z e
AWG/kcmil
Al/Cu
Enclosure
No.
(Page 27)
Top or
Bottom
Mains
Position
UL Li ste d for
Corner Grounded
Delta Systems
Fixed Mains – Factory-Installed Main Lugs
70 HOM24L70F/S Included B 10,000 A
#123
#144
2 Top No
100 HOM612L100F/S Included B, C 10,000 A #81 4 Top No
125 HOM48L125GC Included B, C 10,000 A #42/ 0 21 Top No
Convertible Mains – Factory-Installed Main Lugs
QOM1 Main Frame Size – Convertible to 22,000 AIR Main Circuit Breaker
125
HOM816L125C Included B, C 10,000 A #62/ 0 6 Both
No
HOM816L125TC Included B, C 10,000 A #62/ 0 6 Both
HOM12L125C Included B, C 10,000 A #62/ 0 6 Both
HOM1224L125TC Included B, C 10,000 A #62/ 0 6 Both
HOM1624L125C Included B, C 10,000 A #62/ 0 8 Both
HOM20L125C Included B, C 10,000 A #62/ 0 8 Both
HOM20-24L125TC Included B, C 10,000 A #62/ 0 8 Both
HOM24L125TC Included B, C 10,000 A #62/ 0 8 Both
Convertible Mains – Factory-Installed Main Lugs
QOM2 Main Frame Size – Convertible to 22,000 AIR Main Circuit Breaker
150
HOM30L150C Included B, C 10,000 A #4250 10 Both
No
HOM30L150TC Included B, C 10,000 A #6250 10 Both
200
HOM1632L200TC Included B, C 10,000 A #4250 9 Both
HOM1632L200TCFT
2
Included B, C 10,000 A #6250 10 Both
HOM2040L200TC Included B, C 10,000 A #6250 9 Both
HOM30L200C Included B, C 10,000 A #6250 10 Both
HOM30L200TC Included B, C 10,000 A #6250 9 Both
HOM3040L200TC Included B, C 10,000 A #6250 10 Both
HOM40L200C Included B, C 10,000 A #6250 12 Both
HOM40L200TC Included B, C 10,000 A #6250 12 Both
225
HOM42L225C Included B, C 10,000 A #6250 10 Both
1
UL short circuit rating with optional QOM-VH main circuit breaker, 22,000 AIR.
2
Supplied with feed-thru lugs.
B UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with field-installed service disconnect.
C UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) when not more than six service disconnecting means are provided and
when not used as a lighting and appliance branch circuit panelboard.