Specification

QO
®
and QOB Miniature Circuit Breakers
Trip Curves
19
07/2008
© 1998–2008 Schneider Electric
All Rights Reserved
Trip Curves
The tripping characteristics of QO and QOB circuit breakers can be represented by a characteristic
tripping curve that plots tripping time versus current level. The curve shows the amount of time
required by a circuit breaker to trip at a given overcurrent level. The curve has a performance band that
is bound by a minimum and a maximum value of clearing time. Total clearing time is the sum of the
sensing time, unlatching time, mechanical operating time and arcing time of the circuit breaker. For
currents in excess of 135% of the circuit breaker rating at rated ambient temperature (40°C), the circuit
breaker will automatically open the circuit within limits specified by the band.
Thermal Tripping Characteristics
The upper left portion of each trip curve displays the thermal response of the circuit breaker. On low-
fault current levels, up to the magnetic tripping level, thermal tripping occurs when a bimetal in the
circuit breaker responds to heat associated with the overcurrent. The bimetal deflects, unlatching the
mechanism and mechanically causing the circuit breaker to trip and open the circuit. The greater the
overcurrent, the faster the circuit breaker will operate to clear the circuit.
Magnetic Tripping Characteristics
The lower right portion of each trip curve displays the magnetic tripping response of the circuit breaker.
This takes place when overcurrents of sufficient magnitude operate in an internal magnetic armature
which unlatches the mechanism. Magnetic tripping occurs with no intentional time delay.
Figure 9: Typical QO Trip Curve