Specification

© 1998–2008 Schneider Electric
All Rights Reserved
QO
®
and QOB Miniature Circuit Breakers
Special Application Circuit Breakers
10
07/2008
Proper Application of Qwik-Gard GFCIs
Do not connect to swimming pool equipment installed before adoption of the 1965 National Electric
Code
Do not connect to electrical ranges or clothes dryers whose frames are grounded by a connection
to the grounded circuit conductor.
Do not use as a main circuit breaker in a panelboard or in reverse connected (backfed)
applications.
Do not megger, high-voltage or hi-pot test. Any voltage in excess of 240 Vac will damage the GFCI
electronics so that the circuit breaker will not protect against low-level ground faults.
Must be located no more than 250 ft. (76 m) from the load being served.
RequiresS the same mounting space as standard QO circuit breakers.
One-Pole Qwik-Gard Ground-Fault Circuit Interrupters
One-pole Qwik-Gard GFCIs must be installed on independent circuits. Circuits which have a neutral
common to more than one panel circuit conductor cannot be protected against ground faults by a one-
pole GFCI because the current returning to the source through the neutral cannot be effectively split to
prevent the Qwik-Gard GFCI from tripping under normal use.
Figure 2: Typical One-Pole Qwik-Gard GFCI Wiring
N
AB
120/240 Vac Source
Hot
Duplex
Receptacle
Neutral
Equipment Ground
S/N
GND
120 V
240 V
One-pole
Circuit
Breaker
with
GFCI or EPD
120 V
120 V
07303106