Specification
© 1998–2008 Schneider Electric
All Rights Reserved
QO
®
and QOB Miniature Circuit Breakers
Special Application Circuit Breakers
10
07/2008
Proper Application of Qwik-Gard GFCIs
•
Do not connect to swimming pool equipment installed before adoption of the 1965 National Electric
Code
• Do not connect to electrical ranges or clothes dryers whose frames are grounded by a connection
to the grounded circuit conductor.
• Do not use as a main circuit breaker in a panelboard or in reverse connected (backfed)
applications.
• Do not megger, high-voltage or hi-pot test. Any voltage in excess of 240 Vac will damage the GFCI
electronics so that the circuit breaker will not protect against low-level ground faults.
• Must be located no more than 250 ft. (76 m) from the load being served.
• RequiresS the same mounting space as standard QO circuit breakers.
One-Pole Qwik-Gard Ground-Fault Circuit Interrupters
One-pole Qwik-Gard GFCIs must be installed on independent circuits. Circuits which have a neutral
common to more than one panel circuit conductor cannot be protected against ground faults by a one-
pole GFCI because the current returning to the source through the neutral cannot be effectively split to
prevent the Qwik-Gard GFCI from tripping under normal use.
Figure 2: Typical One-Pole Qwik-Gard GFCI Wiring
N
AB
120/240 Vac Source
Hot
Duplex
Receptacle
Neutral
Equipment Ground
S/N
GND
120 V
240 V
One-pole
Circuit
Breaker
with
GFCI or EPD
120 V
120 V
07303106