Brochure
PowerPact H-, J-, and L-Frame Circuit Breakers
Trip Units
98
02/2016 © 2011–2016 Schneider Electric
All Rights Reserved
Mounting
The IFE interface and IFE interface + gateway are DIN rail mounting devices. A stacking accessory
enables the user to connect several IFMs (ULP to Modbus interfaces) to an IFE interface + gateway
without additional wiring.
24 Vdc Power Supply
The IFE interface and the IFE interface + gateway must always be supplied with 24 Vdc.
The IFMs stacked to an IFE interface + gateway have power supplied by the IFE interface + gateway,
thus it is not necessary to supply them separately. It is recommended to use a UL listed and
recognized limited voltage/limited current or a class 2 power supply with a 24 Vdc, 3 A maximum.
Required Circuit Breaker Communication Modules
The connection to an IFE interface or IFE interface + gateway requires a communication module
embedded into the circuit breaker:
•
PowerPact and Compact (fixed or drawout) circuit breakers: BSCM communication module
•
Drawout PowerPact and Compact circuit breakers: BSCM and its respective I/O (Input/Output)
application module.
All connection configurations for PowerPact and Compact circuit breakers require the circuit breaker
ULP cord. The insulated NSX cord is mandatory for system voltages greater than 480 Vac. When the
second ULP RJ45 connector is not used, it must be closed with a ULP terminator (TRV00880).
Figure 8: IFE Interface, IFE Interface + Gateway Screen