Brochure
PowerPact H-, J-, and L-Frame Circuit Breakers
Trip Units
96
02/2016 © 2011–2016 Schneider Electric
All Rights Reserved
Four Functional Levels
All PowerPact H-, J-, and L-frame circuit breakers devices can be equipped with the communication
function using a pre-wired connection system and a Modbus™ communication interface module. The
interface module can be connected directly or through the front display module (FDM121).
The PowerPact H-, J-, and L-frame circuit breakers can be integrated in a Modbus communication network.
Four functional levels can be used separately or combined to adapt to all supervision requirements.
Modbus Principle
The Modbus RS 485 (RTU protocol) system is an open bus on which communicating Modbus devices
(PowerPact and Masterpact circuit breakers, Power Meter PM700, PM800, etc.) are installed. All types
of PLCs and microcomputers may be connected to the bus.
Number of Devices
The maximum number of devices that may be connected to the Modbus bus depends on the type of
device (PowerPact circuit breaker with Modbus COM, PM700, PM800, Masterpact circuit breaker,
etc.), the baud rate (19200 is recommended), the volume of data exchanged and the desired response
time. The RS 485 physical layer offers up to thirty-two connection points on the bus (one master, thirty-
one slaves).
Length of Bus
The maximum recommended length for the Modbus bus is 3940 feet (1200 meters).
Bus Power Source
A 24 Vdc power supply is required (less than 20% ripple, insulation class II).
Level Function
Communication of status indications
Compatible with PowerPact H-, J- and L-frame circuit breakers and automatic
switches. Use the BSCM module to access the following information:
• ON/OFF position
• trip indication
• fault-trip indication
Communication of commands
Available on all circuit breakers and automatic switches with communicating motor
operators, the remote control can be used to:
• open
• closed
• reset
Communication of measurements with
Micrologic 5/6 A or E trip unit
This level provides access to:
• instantaneous and demand values
• maximums/minimums
• energy metering
• demand current and power
• power quality
Communication of operating assistance with
Micrologic 5/6 A or E trip unit
This level also provides access to:
• protection and alarm settings
• time-stamped histories and event tables
• maintenance indicators