Brochure
PowerPact H-, J-, and L-Frame Circuit Breakers
Trip Units
89
02/2016
© 2011–2016 Schneider Electric
All Rights Reserved
Micrologic 5/6 A or E Trip Units
Micrologic 5/6 A (Ammeter) or E (Energy) trip units can be used on PowerPact H-, J-, and L-frame
circuit breakers with performance levels D, G, J, or L. They all have a front display module. They offer
basic LSI protection (Micrologic 5 trip unit) or LSI and ground-fault protection G (Micrologic 6 trip unit).
They also offer measurement, alarm and energy values.
The capabilities of Micrologic 5/6 A and E trip units come into full play with the front display module.
When the two are connected using a simple cable with RJ45 connectors, the combination offers full
Power Meter capabilities and all the measurements required to monitor the electrical installation.
Ii (x In)
35
15
2
3
4
8
6
10
12
15
20
25
30 40
45
50
60
1.5
Ig tg
6.2E
Measurement
Display
Maintenance
Settings
Measurements Operating and Maintenance Assistance
Communication
Network
Ammeter
(Micrologic A
Trip Unit)
Current measurements
• Phase and neutral currents I
A
, I
B
, I
C
, I
N
• Average current of the 3 phases I
avg
• Highest current of the three phases I
max
• Ground-fault current Ig (Micrologic 6.2 / 6.3 A) trip units
• Maximum and minimum current measured
Indicators, alarms and histories
•Fault types
• Alarms for high/low alarm thresholds linked to I
measurements
• Trip, alarm and operating histories
• Time-stamped tables for settings and maximum current
Maintenance indicators
• Operation, trip and alarm counters
• Operating hours counter
• Contact wear
• Load profile and thermal image
Modbus with
add-on module
Energy
(Micrologic E
Trip Unit)
Current measurements
• Phase and neutral currents I
A
, I
B
, I
C
, I
N
• Average current of the 3 phases I
avg
• Highest current of the three phases I
max
• Ground-fault current I
g
(Micrologic 6.2 / 6.3 A trip units)
• Maximum and minimum current measured
• Current unbalance between phases
Voltage measurements
• Phase-to-phase (V) and phase-to-neutral (U) voltages
• Average voltages V
avg
, U
avg
• Ph-Ph (V) and Ph-N (U) voltage unbalance
Frequency measurements
• Frequency (f)
Power-quality indicators
• Total harmonic distortion (THD) for current and voltage
Power measurements
• Active, reactive and apparent power, total and per phase
• Power factor and cos ij
Maximum and minimum
• For all I, V, f, P, E measurements
Demand current and power measurements
• Demand values, total and per phase
• Maximum demand
Energy metering
• Active, reactive and apparent energy, total and per phase
Indicators, alarms and histories
•Fault types
• Alarms for high/low thresholds linked to I, V, f, P, E
measurements
• Trip, alarm and operating histories
• Time-stamped tables for settings and I, V, f, P, E
maximum values
Maintenance indicators
• Operation, trip and alarm counters
• Operating hours counter
• Contact wear
• Load profile and thermal image
Modbus with
add-on module